Tender For Repair / Maintenance Of Lt Cable Network, Transformer, Lt Switch Gears, And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur, jaipur-Rajasthan

Military Engineer Services-MES has published Tender For Repair / Maintenance Of Lt Cable Network, Transformer, Lt Switch Gears, And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur. Submission Date for this Tender is 01-05-2024. Switch Gear Tenders in jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

43078969
Corrigendum : Tender For Repair / Maintenance Of Lt Cable Network, Transformer, Lt Switch Gears, And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur
Open Tender
Indian
Rajasthan
jaipur
01-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Repair / Maintenance Of Lt Cable Network, Transformer, Lt Switch Gears, And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-05-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 63180.0 /-
Tender Value
Refer document

Attachment

FileName File Description File Size
41db0ba7-bff1-46ae-81e7-289b1f7cec50.html Tender Notice 0 KB
BOQ_726333.xls Tender Document 0 KB
Tender76.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work : REPAIR / MAINT OF LT CABLE NETWORK, TRANSFORMER, LT SWITCH GEARS, AND CONNECTED ITEMS AT MH JAIPUR UNDER AGE E/M OF GE JAIPUR
Sl. No. Item Description
1M&L for Maint / servicing of Ring Main Unit (RMU) Out door type, 11KV 630 Amps, 4 way ofelectro mechanical componants at site etc. by cleaning,brushing & removing dust particals from body, isolating contacts, moving parts, particularly from bus bar chamber, gear mechanism, spring mechanism, tightening of nuts & bolts of all components in entire mechanism and re-connection to load, re-commissioning including consumables (Petrollium jelly) CRC, O ring, and make sure that brushings, cable plugs and gaskits are free of grease and polutionincluding testing complete with replacement of following spare parts complete all as specified and directed by Engr-in-charge. Make: Crompton Greaves Note : Spare parts shall be measured as supply only under respective item of BOQ
2Supply only Silicon Grease Grade 50
3Supply only 1.1 kv straight throught joint kit 300 Sqmm 3.5 core
4Supply only Contact mechanism piece
5Supply only 11 KV straight throught joint kit 240 Sqmm 3 core
6Supply only Vertical Cable termination boot (Indore type)
7Supply and fixing in repair transformer breather assembly oil seal type made of heavy duty transparent plastic body having top & bottom cover made of aluminium or mild steel of capacity 500 grams filled with silica gel complete all as specified and directed by Engr-in-charge.
8M&L for topping up of deficient oil level of transformers with filtered and dehydrated transformer oil (conforming to IS: 335) and to withstand dielectric strength 60 KV or above (when tested with 2.5 mm gap electrode) complete all as specified and directed by Engr-in-charge. Make - Savita / Powerlink / Poweroil or equivalent as approved by GE
9S&F in repair HV brass set stem of 12 KV grade suitable for transformer of capacities 200 KVA to 400 KVA as required complete all as specified and directed by Engr-in-charge.
10S&F in repair LV brass set stem of 1.1 KV grade suitable for transformer of capacities 200 KVA to 400 KVA as required complete all as specified and directed by Engr-in-charge.
11Dehydration / Filtration of transformer Oil of existing transformer install at site with portable plant to improve the dielectric strength 40 to 60 KV during filling after initial filtration including testing of dielectric strength after dehydration at site.
12M&L for opening up the top cover of transformer of any capacity for checking the conditions to carryout repairs at site, including draining out oil from the transformer in suitable containers (containers to be provided by the contractor) and repair the transformer with replacement of parts where required, check the lead connection from winding to bushing rods including necessary soldering/jointing etc and refilling the dehydrated oil after complete repair, making all connections and testing on full load complete all as specified & as directed. Notes :- (i) Labour component required for the replacement of unserviceable parts shall deemed to be included in the unit rate quoted against this item. (ii) Major parts where required to be replaced shall be measured and paid for separately as ‘Supply only’ under relevant items of this Schedule. (iii) All T&P and minor parts such as nuts, bolts, washers, insulating material, copper wire for delta connection, etc. shall be arranged by the contractor and the cost thereof shall be deemed to be included in the unit rate quoted against this item. (iv) Dehydration of existing transformer oil and new transformer oil required for topping up shall be measured and paid for separately under relevant items of this Schedule.
13Supply & fix in repair HT bushing complete with double check nuts, washers, gasket set for transformer of capacity 200 KVA complete all as specified and as directed.
14Supply only HT bushing complete with double check nuts, washers, gasket set for transformer of capacity 315 KVA to 400 KVAcomplete all as specified and as directed.
15Supply only LT bushing with brass spindle complete with double check nuts, insulation washers for transformer of capacity 200 KVA complete all as specified and as directed.
16Supply only LT bushing with brass spindle complete with double check nuts, insulation washers for transformer of capacity 315to 400 KVA complete all as specified and as directed.
17Supply only Gasket set made of rubberised cork/neoprene material for transformer of capacity200 KVA complete all as specified and as directed.
18Supply only Gasket set made of rubberised cork/neoprene material for transformer of capacity315 KVA to 400 KVAcomplete all as specified and as directed.
19M&L for disconnecting existing transformer step down 11 KV/0.433 KV indoor/outdoor type of capacity 200 KVA, taking down from site of installation, opening the top cover of transformer, draining out transformer oil from the housing in suitable containers (containers to be provided by the contractor) and deposit the oil in store yard of AGE MFFR, inspecting / assessing the defective / burnt parts, core assembly, etc in the presence of Engineer-in-Charge, shifting the transformer to workshop for repair including loading, unloading, transportation etc, cleaning and making good surface including internal cleaning, removing sludge, etc and painting with one coat of zinc chromate paint to the inner side of the transformer body and one coat of synthetic enamel paint (grey) on outer body of transformer by using spray machine after cleaning & removing oil spots etc, carrying out necessary repair to transformer at workshop, re-assembling, shifting back to site, reinstalling, re-connecting, re-commissioning the transformer and testing at site on full load, complete all as specified and as directed.
20,---Ditto--- all as per item no 14 above but for Transformer of capacity 315 to 400 KVA complete.
21Supply only the following spares/items for repair/replacement to transformers under serial item No. 14.00 to15.00 here-in-before :- (a) LT coil made out of super enameled copper conductor wire of suitable gauge and size as per requirement for distribution transformer complete all as directed.
22(b) HT coil made out of super enameled copper conductor wire of suitable gauge and size as per requirement for distribution transformer complete all as directed.
23S&F 11000 volt grade heavy duty HTXLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 120 Sqmm nominal cross section 3 core laid in trenches, fixed to pole or passing through pipes including all necessary clamps, nuts, bolts washers complete all as specified and directed.
24Cable jointing kit for 11 KV (Earthed)grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120sqmm 3 core.
25Material and labour for fault investigation of HT /LT electic supply line of any sizewith fault lacator machine for LT / HT line including rectification of fault with cutting/disconnecting of cable and jointing with suitable size of cable jointing kit ,excavation or as speciffied and as directed.
26Providing area cleaning/sweeping of preimises and clearing away all grass vegetation, saplings, shrubs, brushwood, undergrowth, roots, and trees n exc 30 cm girth (measured one metre above ground level) and maintaining the ground surrounding transformers, LT Panels, 02 Pole structures, 04 Pole Structures, etc at various sub stations / E&M installations and removing the same out side the defence area as directed by Engr in charge. Notes for serial item No: 2.00to 20.00 :- (i) Labour component required for the replacement of unserviceable parts shall deemed to be included in the unit rate quoted against this item. (ii) HT/LT coils where required shall be measured and paid for separately as ‘Supply only’ under relevant items of this Schedule. (iii) All minor parts such as nuts, bolts, washers, insulating material, copper wire for delta connection, etc. shall be arranged by the contractor and the cost thereof shall be deemed to be included in the unit rate quoted against this item. (iv) Testing of transformer shall be arranged by the contractor for Type Test & Routine Test which shall be carried out in the presence of Engineer-in-Charge and contractor shall submit test certificates to this effect before processing the RAR for payment.
27M&L for taking out old unservicable LT cable of any size from trenches complete all as specified and directed
28S&F 1100 volt grade heavy duty XLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 400 Sqmm nominal cross section 3.5 core laid in trenches, fixed to pole or passing through pipes including all necessary clamps, nuts, bolts washers complete all as specified and directed.
29,---ditto--- all as per srl item No. 23 above but cable of size 300 Sqmm nominal cross section 3.5 core complete.
30,---ditto--- all as per srl item No. 23 above but cable of size 240 Sqmm nominal cross section 3.5 core complete.
31,---ditto--- all as per srl item No. 23 above but cable of size 185 Sqmm nominal cross section 3.5 core complete.
32,---ditto--- all as per srl item No. 23 above but cable of size 95 Sqmm nominal cross section 3.5 core complete.
33,---ditto--- all as per srl item No. 23 above but cable of size 70 Sqmm nominal cross section 3.5 core complete.
34,---ditto--- all as per srl item No. 23 above but cable of size 50 Sqmm nominal cross section 3.5 core complete.
35,---ditto--- all as per srl item No. 23 above but cable of size 35 Sqmm nominal cross section 3.5 core complete.
36,---ditto--- all as per srl item No. 23 above but cable of size 16 Sqmm nominal cross section 4 core complete.
37S&F galvanised steel tubes "light grade "of 80 mm bore (ISI marked) with all fitting (ISI marked) and fixed to walls and ceilings or laid in floors/ trenches and under road complete all as specified and directed.
38,---ditto--- all as per srl item No. 32 above but tube of 100 mm size complete.
39M&L steel tubular swaged poleswith ISI marked complete with cast iron base plate finial taper plugbolts, nuts & screws all as base plate finial taper plugbolts, nuts & screws specifed type 410 SP -31 (9 mtr long LT poles) and incl painting with one coat of red oxide and two coats of aluminium paint and black bitumen paint on hidden surface in foundation all as specified (excavation and PCC work shall be measured and paid separetaly at appropriate items.
40M&L 4mm thick mild steel chequred plates for cable duct cover of suitable size for sub station / installation complete all as specified and directed.
41Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in soft/loose soil complete all as specified and directed
42Excavation in trenches not exceeding 1.5 m wide and but exceeding 1.5 m in depth upto 3.00 mtr and getting out in soft/loose soil for laying of cable or foundation etc. complete all as specified and as directed.
43Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in hard and dense soil
44Removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point.
45M & L Sand cushioning to under ground cable with screened and washed sand (non cohessive), 8 cm before laying cable and 15cm after laying and punned to 18cm after laying of cable complete all as specified and directed by Engineer-in-Charge. Note : Punned thickness shall be considered for payment purpose.
46M & L bricks for protection cover to UG cable (with old size sub class B bricks) with width equal to length of brick, laid dry and flat abutting each other with gaps between adjecent bricks not exceeding 10mm complete all as specified and directed.
47M&L PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) for pole foundations including all type of form work and wastage all as specified.
48M&L PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) in foundations, filling and mass-concrete including nacessary form work complete all as specified and as directed.
49M&L for replacement of digital voltmeter of suitable rangeincluding wiring with copper conductor cable of suitable size all as specified and as directed by Engineer-in-Charge.
50M&L for replacement of digital ammeter of suitable rangeincluding wiring with copper conductor cable of suitable size all as specified and as directed by Engineer-in-Charge.
51M&L for rewiring of LT panel/feederof any size including replacemnt of wornout parts , nut , bolts,backlite surfaceand cleaning of burnt/rusted surface/all as specified and as directed by Engineer-in-Charge.
52M&L for preparation of the old painted surfaces of feeder piller boxes/panels/boards / transformer of any size any description and in any position including removal of faded & deteriorated paint eaither by hand scrapping or by blow lamps, applying necessary filler coat and scrspping as required and applying two coats of synthetic enamelled paint (grey in colour) with using spray machine on old prepared surfaces complete all as spcified and as directed by Engineer- in Charge.
53Supply and fixing in replacement of spreder links of capacity 200 to 400 Amps in existing LT panel/ etc including provision of insulation tape RYB in colour and holes, nuts & bolts etc complete all as directed by Engineer-in-Charge.
54Supply and fixing in replacement of spreder links of capacity 100 to 200 Ampsin existing LT panel/ etc including provision of insulation tape RYB in colour and holes, nuts & bolts etc complete all as directed by Engineer-in-Charge.
55Supply and fixing in replacement Copper bus bar 800 Amp capacity in existing LT panel/feeder piller /Transformer etc including provision of insulation tape RYB in colour and holes, nuts & bolts etc complete all as directed by Engineer-in-Charge.
56Supply and fixing in replacement Copperbus bar 630 Amp capacity in existing LT panel/feeder piller etc including provision of insulation tape RYB in colour and holes, nuts & bolts etc complete all as directed by Engineer-in-Charge.
57Supply and fixing in replacement Copper bus bar 400 Amp capacity in existing LT panel/feeder piller etc including provision of insulation tape RYB in colour and holes, nuts & bolts etc complete all as directed by Engineer-in-Charge.
58Supply and fixing in replacement danger notice plate of size 20x15cm made out of MS sheet 1.6 mm thick, vitreous enameled white, with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts, nuts on LT poles complete all as directed by Engineer-in-Charge.
59M&L for cable jointing kit for upto 1.1 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 35 sqmm 3.5 core XLPE armoured aluminium conductor cable complete all as directed by Engineer-in-Charge.
60,---ditto--- all as per srl item No. 54 above but cable of 50 sqmm 3.5 core size complete.
61,---ditto--- all as per srl item No. 54 above but cable of 70 to 120 sqmm 3.5 core complete.
62,---ditto--- all as per srl item No. 54 above but cable of 240 to 300 sqmm 3.5 core complete.
63,---ditto--- all as per srl item No. 54 above but cable of 400 sqmm 3.5 core complete.
64M& L for shifting of existing LT Panel disconnecting existing electrical connection from MCCBs / MCB / Bus bar, taking out required length from loop of cable and reconnecting with electrical connection at new location including breaking / cutting existing PCC foundationand fixed at new locationin PCC 1:3:6 using 20 mm graded stone aggregate incluting paitning with danger sign on Panel not beyond 300mtr or as specifiied by the Engr In Charge
65M&L for pipe in pipe chemical earthing with GI pipe electrode 3.0 m long having outer pipe dia 80 mm & inner pipe dia 50 mm duly filled with highly conductive and anti corrosivecompound of required quantity having chemical composition Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% burried in ground by digging a bore of 150 mm dia surrounded by soil friendly backfill compound non soluble in water including connection with galvanised earth strip 32 x 6 mm, making PCC pit of size 0.3 m x 0.3 m x 0.3 m (inner size) in mix 1:3:6 type C1 with RCC 1:2:4type B-1, 40 mm thick cover reinforced with 8 mm dia MS bars 3 Nos both ways with lifting hook made out of 8 mm dia bar and testing point on completion to achieve value not more than 2.0 ohm complete. (Note - GI strip size 32x6 mm upto 7.5 m included in the item).
66M&L for earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6.0mm buried directly in ground, vertically to depth not less than 2.25mtr below normal ground level with top edge of the earth plate at depth not less than 1.5 metre below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI strip of size 32x6mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe medium grade 20mm bore for watering, 40mm bore GI pipe medium grade for protection of GI strip upto test point including providing funnel and wire mesh GI frame and 10cm thick suitably reinforced RCC pit cover, PCC chamber pit with PCC (1:3:6) type C2 using 40mm graded stone aggregates complete including excavation and earth work in any type of strata, disposal of surplus soil to a distance not exceeding 50 mtr, all as specified ans shown in Electrical plate No. 3 of SSR Part-1, PCC pit shall be provided at least 50 cm away from the earth pit and not just on earth pit including testing on completion complete. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
67S&F in repair of MCCB 63 Amps, 4 pole,415V, 16 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
68Supply and fixingin repair of MCCB 125 amp, 4 pole, 16 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
69Supply and fixingin repair of MCCB 160 amp, 4 pole, 16 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
70Supply and fixingin repair of MCCB 250 amp, 4 pole, 25 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
71Supply and fixingin repairl of MCCB 400 amp, 4 pole, Icu 36 KA (Ics=100% Icu), electronic release and adjustable between 40% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
72Supply and fixingin repair of MCCB 630 amp, 4 pole, Icu 50 KA (Ics=100% Icu), electronic release and adjustable between 40% to 100% with spreader links on both sides complete all as directed by Engineer-in-Charge.
73Supply and fixingin repair of ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 800 Amps,DMXSP-Icu=lcs 50 KA,compact dimention ,in built temperature protection (50-100%),(Ics=100% Icu), electronic release LCD display with current metering triping alarm history and logistic selectivity etc. with spreader links on both sides complete all as directed by Engineer-in-Charge.
74S &F in repair ofONLINE Changeover of cap 400 amp, TPN, front handle type complete all as directed by Engineer-in-Charge.
75Supply and fixingin repair ofONLINE Changeover of cap 200 amp, TPN, front handle type complete all as directed by Engineer-in-Charge.
76S&F thermoplastic, IP65 cable junction box of size 200 x 160 x 98 mm with metric knockouts on all sides for cable entry or Secure duly fitted with followings:- (a) DIN Rail (35 mm) - 1 No (b) ELMEX or equivalent make connector of 10 sqmm - 4 Nos (c) ELMEX or equivalent make end plate - 1 No (d) ELMEX or equivalent make end clamps - 2 Nos (e) MCB SP 6 amp, 10 KA, "C" series - 1 No
77M&L for street light junction box made out of 2 mm thick MS sheet of size 250x200x150 mm incl 04 nos aluminium busbar of size 20x3 mm thick mounted on porcelain insulators and one MCB SP 6 amps etc having provn of cable glands for incoming and outgoing cables, fixed to pole with proper fixing arrangement and painting complete all as specified and directed.
78Supply and fix timer relay having green and red clips or they are a push -in style of timer adjust the time automatically day and night time when the light are in operation suitable for 230 /415 voltalongwith street light complete new wiring in existing panel all as per directed.
79M & L for maint/servicing of AMF panel of any make model and repair of unsv wiring of size (A-Z,0-9) including cleaning resetting / adjustment of relays, calibration of timing, relays, conract checking and replacing following parts etc as specified and as required of existing make for for 250 KVA DG set complete all as specified and directed. Note : Parts shall be measured and paid seperately as supply only
80Supply only Advanced AMF controlled unit GCU for (Genset controller unit) for RPM, LLOP / LO battery, low water, low fuel, HTC, V belt safety etc for AMF panel of 250 KVA DG set of existing make.
81Supply and fix in repair 4 pole Power contactor MCX 43, 240 V ,400 Amp alongwith complete new wiring in existing panel complete all as specified and directed by Engr-in-charge.
82Supply and fix in repair 3 pole contactor MCX 25, suitable for 415 volt alongwith complete new wiring in existing panel complete all as specified and directed by Engr-in-charge.
83Supply and fixin repair 3 pole contactor MCX 45, suitable for 415 volt alongwith complete new wiring in existing panel complete all as specified and directed by Engr-in-charge.
84Supply and fix in repair 3 pole contactor MCX A2, suitable for 415 volt alongwith complete new wiring in existing panel complete all as specified and directed by Engr-in-charge.
85M&L for of wall mounted 6 Way bus bar chamber connsisting with bus bar 3 phase and neutral 4 Nos 200 Amp fixed on insulators including fixing in wall or as specififed by engineer in charge Make Havells cat part No IHBC020006 or equivalent in Legrand/ L&T / BCH as approved by GE.
86S&F in repair MCB distribution board, tripple pole and neutral (VTPN) powder coated CRCA steel sheetsuitable for MCCB incomer upto 160 amp, 4 way, 415 volts, degree of protection IP 43 - IK- 09 with reversible double door, recess mounted, having 250 amp insulated tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required. Note for MCBs & MCB DBs:- MCCBs, MCBs & MCB DBs shall be of the same make.
87S&F MCBs Single pole 6 to 32 amp of"C" series having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs complete all as specified and directed by Engr-in-charge.
88,---ditto--- all as per srl item No. 82 above but MCB double pole 10 to 32 amp complete
89,---ditto--- all as per srl item No. 82 above but MCB Double pole, 40 to 63 amp complete
90,---ditto--- all as per srl item No. 82 above but MCB Four pole 40 to 63 amp complete
91M&L for brick work with sub-class "B" bricks, straight or curved on plan to any radius in half brick thick walls built in cement mortar 1:4 and plastering 10 mm thick in CM 1:4 and 2 coats of white / colour washing to match the surface complete all as specified and directed.
92M&L for cross arms, bracings, supports, clamp and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of paint complete all as specified and directed.
93S& F in repair integral LED flood light 100 W 3000 K with driver inside a PDC housing complete all as specified and directed. Make : Philips cat part NoCVP 182 LED 100 W CW FG S1 PSU GR or equivalent in Havells / CG as approved by GE.
94S& F in repair integral LED flood light 50 W 3000 K with driver inside a PDC housing complete all as specified and directed. Make : Philips cat part NoCVP 182 LED 100 W CW FG S1 PSU GR or equivalent in Havells / CG as approved by GE
95S&F in repair bollard LED garden light8 watt1 Mtr hightwith aluminium housing, glare free PMHA diffuser,IP-65 complete withrequired earth work,including fasteners, nuts, bolts, washers, copper connecting cable & PCC (1:2:4) type B 1 using 20 mm graded stone aggregate (size 0.40 m x 0.30 m x 0.45 m) complete all as specified and directed. Make : Havells cat part No; CONENXGBLS8WLED857PSYMTOPCM or equivelent in philips/bajaj as approved by GE
96S & F in repair LED street lightof power not exceed 70 watt including driver with a nominal system lumen output of 7200 lumens and a minimum system efficacy of 100 lumen/watt. The luminaire shall have rated system lifetime of 50,000 burning hours before reaching at L70. The luminaire should have cool white colour temperature (CCT > 5000K) and a CRI >70. The luminaire shall meet IP 66 rating & IK05 rating with THD < 20% and PF> 0.9. The luminaire housing should be made of pressure die cast aluminium with a flat glass optical cover complete all as specified and directed.
97S&F in repair integral LEDavaiation light fitting neon lamp 75VA comprising of die-cast aluminium alloy hsg with heat resistance with accessoriesprovidedincluding necessary electric connection with all accessories required for fixing/mounting on 20mm dia GI pipe including taking down old unserviceable and make good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : Bajaj Cat No 20075 BJAOL 1 with neon lamp or equivalent in Phillips / crompton.
98S&F flexible copper conductor cable of size 4 Sqmm 2 Core / 2 Nos single core in PVC conduit for lighting connection and all as specified and directed.
99Painting of street light poles 8.5 m / 9.0 long including street light brackets/clamps etc with best quality aluminium paint, making alternate black & white colour bands of 30 cms width upto a height of 1.5 m from pole coping with synthetic enamelled paint and writing pole numbers in black colour on yellow base complete all as specified and directed.
100M&L maint/servicing of Voltage Stabilizer, 3 phase, Oil cooled of capacity 75 KVA in door type of disconnect electrical and electromegnatic componants, regulate the voltage topup oil level etc. by cleaning, LT brushing & removing unsv component, particularly tightening of nuts & bolts of all components in entire mechanism and re-connection to load including brushings, cable plugs and lugs etc are specified and directed complete
101S & F in repair battery charging unit 24V, DC 6AH to 180 AH panel mounting type by replacing defective relays, selector switch, ampere meter, volt meter, internal wiring with suitable size copper conductor cables, rewinding of defective transformer etc compete.
102S&F in repair for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe orfixed to poles or any other indicated situation for loop earthing etc. as required 25x4mm galvanised iron strip and all as per directed.
103S&F in repair air termination, single pointed, copper rod 12mm dia and 300mm longwith all accessories required for fixing/mounting on 20mm GI pipe including taking down old unserviceable and make good the disturbed surface complete all as specified and as directed. Note: GI pipe 20mm dia measured and paid seperately
104S&F in repair single aluminium strip of size25x3mm in proper posion with saddles and fixing screws for roof conductors and down conducrors from top to the building air termination point to the test points of the building as required after and including taking out old unsv and make good the disturbed surface complete all as specified and directed.
105S&F in repair for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw and connected with earthing strip including taking out old unsv and make good the disturbed surface complete all as per directed.
106M & L for electric circuit diagram chart of installation size not less then 200x120x2cm made out of corrugated plastic light waight making it produce signs or displays white/black letters figures mounted on wall of installation or as per sample complete all as per specified and all as directed.
107M & L for stickers by making drawing with computer art work for letters, figures, scanning etc in approved colour in water proof glossy PUC synthetic sheet suitable for scotch/ inkjet printing with outdoor ink 300 x 720 DPI and pasted at each Lift and different places as directed of size 2 feet X 2 feet complete all as specified and directed by E-in-charge. Matter to be printed: "In case of emergency please contact following Nos, complaint cell No, Lift mechanic No, JEs No, AGEs No (GE JAIPUR/FIRE EXIT IN CASE OF FIRE)" and direction arrow etc all as specified and as directed. Note: The matter to be printed has to be approved from Engr-in-Charge before final printing
108Note:-(a) Material like MCB, MCCB, ACB, Cable, GI Pipe etc shall be procured in one time, of approved make by authorized dealer of manufacturers ad manufacturer test certificate of (where applicable) shall be submitted before claiming payment (b) The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule "A"/BOQ