Tender For Repair/ Replacement And Servicing Of Central Air Conditioning/ Distribution Unit At Bb Cantt Srinagar Under Ge 864 Ews, Srinagar-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair/ Replacement And Servicing Of Central Air Conditioning/ Distribution Unit At Bb Cantt Srinagar Under Ge 864 Ews. Submission Date for this Tender is 20-04-2024. Air Conditioner Tenders in Srinagar Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

43078211
Corrigendum : Tender For Repair/ Replacement And Servicing Of Central Air Conditioning/ Distribution Unit At Bb Cantt Srinagar Under Ge 864 Ews
Open Tender
Indian
Jammu And Kashmir
Srinagar
20-04-2024

Tender Details

Tender For Repair / Replacement And Servicing Of Central Air Conditioning / Distribution Unit At Bb Cantt Srinagar Under Ge 864 Ews

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 02-Apr-2024 Corrigendum Other 13-04-2024
2 13-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 39998.0 /-
Tender Value
INR 19.99 Lakhs /-

BOQ Items

Name of Work: REPAIR/ REPLACEMENT AND SERVICING OF CENTRAL AIR CONDITIONING/ DISTRIBUTION UNIT AT BB CANTT SRINAGAR UNDER GE 864 EWS
Sl. No. Item Description
1Required only for man power as a well qualified technician / mechanic or technical rep of existing manufacture make of AC plant suitable for the purposed of to know about the defect in AC plant with having working principle air cooled / water cooled type based operational along with microprocessor control panel basedsystem of make - Voltas/Blue star/Caryaire/ Daikin etc. The technician to know full fill knowledge about the defect rectification problemof any type/size any capacity & model of ACplant package type/ central type unit system and it all connected eqpt/machine parts of items including it mircoprocess control panel system etc and also immediately to attend AC plant and it related work complaints & defect problem along with repairing work and to be ensure that make itimmediately repair & rectification the work defect/problem of complaint and repairing work and make it serviceable condition of complete plant system with control panel .The Contractor to be ensure that after attend complaints and to do rectify the defects problem work along with resetting of controls panel or repair/ replacement work in all AC palnt system carried out complete work etc should be completed as per standard engineering practice, along with providing all necessaryminor spare parts of items,tools and plants etc complete all as specified and directed by Engr-in-Charge.
2Required only for man power as a well qualified technician / mechanic or technical rep of existing manufacture make of centre heating plant suitable for the purposed of to know about the defect in all type of air and water based heating generating plant system along with control panel based etcThe technician to know full fill knowledge about the defect problemof any type/size any capacity & model of heating generating plants system and it all connected eqpt/machine parts of items including it control panel system etc and also immediately repair & rectification the work defect/problem of complaint and to do repairing work and make it serviceable condition of complete plant system with control panel .The Contractor to be ensure that after attend complaints and rectify the defects problem work in all heating plants along with resetting of controls panel or repair/ replacement work carried out of complete work etc should be completed as per standard engineering practice, along with providing all necessary minor spare parts of items, tools and plants etc complete all as specified and directed by Engr-in-Charge. Notes for Sl item No 1 & 2 :- (i) Repair work of all type of plant shall be carried out by well experienced technicians/ mechanic who has well experienced / working about this field and providing all type proper tools and safety measures etc. (ii) All minor spare parts of items/ petty small parts required for repair i.e. nuts, bolts, washers screws, saddles, grease, oil/ lubricants, wire , thimbles etc shall be provided by the contractor without any extra cost to the department. (iii) Contractor shall be responsible and to be provide conveyance /transportation & required all type of working T&P etc for attend the complaints. (iv) Contractor shall be responsible for arranging security passes from the concern department through there guidelines / procedure. (v) All type of attend complaints related problem service / defect problem of complaints for repairing work and make it immediately ectification the work defect problem of work will be attend & addressed with in 24 hrs from the time of receipt of complaints. If the contractor and his tradesman fail to attend the complaint and also to solve it rectification defect problem work within the given time period , the compensation / penalty of Rs-1000 (Rupee one thousand) per day for per complaints shall be recovered from the contractor dues or as the decision and direction of EIC/GE in this regard shall be final and binding. All the complaints problem is required to be rectify with in 24 Hrs duration.
3Required sufficient all type of cleaning and servicing materials ,T&P and man power as a well qualified technician / mechanicfor disconnecting of water/ refrigerant gas pipe lines , electric wiring connections and it connected electrical and mechanical fitting parts of items from inside/outside area only for indoor unit body system of existing central type AC / package type AC plant system any type/size any model of AC plant of rating cooling capacity from 08 TR to 30 TR of make- Voltas/Blue star/Caryaire/ Daikin etc and also providing carried out work like maintenance , servicing , washing and cleaning ,greasing, oiling etc work for internally compartment of AC plants like aluminum coil fins of unit system , ventilation exhaust fans, compressor unit / evaporator unit/chiller unit, blower with blower motor, body base frame area along with all connected all fixing accessories and its connected control panels etc of complete in each plant systemthrough with the help of high efficiency air pressure blower with vacuum pump or water pressure jet pump system and after work removing from the all type of wastage materials ,dust and sludge particles etc from all body compartment system after completion of cleaning and servicing work of each plantit should be clean dryproperly (The type ofair & water cleaning work of plant will be decided as per required condition at siteor as direction and all as specified & directed by EIC) and after completion of cleaning /serving work re fixing the all removing parts on same to its original position including checking / tightening and replacement of defected of all type of nut , bolt ,screws, gasket, with ‘O’ rings, Teflon sheets etc and making welding work if broken foundrequired at site and including adjustment & alignment setting of blower motor with pulley shaftand also repair/maintained and rectification ofthe minor defect /broken electrical controlling wiring and gas pipe line connection of main control panel system of plants andafter completion of complete job checking any type of leakage from electric/ gas system and ensure that making it gas leakages proofand also testing it on full load complete all as satisfaction and all as specified & directed byEngrs in Charge .
4Required sufficient all type of cleaning and servicing materials ,T&P and man power as a well qualified technician / mechanicfor disconnecting of water/ refrigerant gas pipe lines , electric wiring connections and it connected electrical and mechanical fitting parts of items from inside/outside area only for outdoor condensingattachment unit system suitableforexisting central type AC / package type AC plant system any type/size any model of AC plant of make- Voltas/Blue star/Caryaire/ Daikin etc and also providing carried out work like maintenance , servicing , washing and cleaning ,greasing, oiling etc work for internally compartment of ac plant like aluminum condensing coil fins of unit system , ventilation exhaust fans with motor, body base frame area along with all connected all fixing accessories body in systemthrough with the help of high efficiency air pressure blower with vacuum pump or water pressure jet pump system and after work removing from the all type of wastage materials ,dust and sludge particles etc from all body compartment system after completion of cleaning and servicing work of each plantit should be clean dryproperly (The type ofair & water cleaning work of plant will be decided as per required condition of site or as direction and all as specified & directed by EIC) and after completion of cleaning /serving work re fixing the all removing parts on same to its original position including checking / tightening and replacement of defected of all type of nut , bolt ,screws, gasket,etc and making welding work if broken found required at site and including fan & motorand also repair/maintained and rectification ofthe minor defect /broken electrical controlling wiringand gas pipe line connectionand after completion of complete job checking any type of leakage from electric/ gas system and ensure that making it gas leakages proofand also testing it on full load complete all as satisfaction and all as specified and directed byEngrs in Charge .
5Required sufficient all type of cleaning and servicing materials ,T&P and man power as a well qualified technician / mechanicfor disconnecting of water/ refrigerant gas pipe lines , electric wiring connections and it connected filters, electrical and mechanical fitting parts of items from inside/outside areaof existing AHU plant system any type/size any model and also providing carried out work like maintenance , servicing , washing and cleaning and complete de scaling work in side of cooling copper tubes area,greasing, oiling etc work for internally compartment like complete de scaling work for single/double type copper cooling coil tubes with pipes along with entire inside chocked water /gas tubes and also including de scaling work out side area of outer cooling coil fins of unit system and sericing/cleanig of exhaust blower with motor, filter and body base frame area along with all connected all fixing accessories of body system throughwith the help of high efficiency air pressure blower with vacuum pump and water pressure jet pump system along with providing sufficient quality of de-scaling chemical solution (ORISCALE BLASTER) / de scaling cleaning compound material or recommended by manufacture/ technician rep and after full filling chemical solution on AHU cooling coil inside tube system with suitable proportion and storage inside system minimum up to 4 hrs duration they after circulating to solution with the help of through mechanical high speed pump with pipe and water tank arrangement system for AHU cooling coil system up to the time of clean level of AHU coiland after completion of cleaning and complete de scaling& serving work re fixing the all removing parts on same to its original position including checking / tightening and replacement of defected of all type of nut , bolt ,screws, gasket, with ‘etc and making welding work if broken found required at site and including adjustment & alignment setting of blower motor with pulley shaftand also repair/maintained and rectification ofthe minor spare defect /broken electrical controlling wiring connection of system andafter completion of complete job checking any type of leakage from water/electric/ gas system and ensure thatmaking it leakages proofand also testing it on full load complete all as satisfaction and all as specified and directed byEngrs in Charge .
6Required sufficient all qty of checking & testing of materials throught N2 gas etc and ,T&P and man power as a well qualified technician / mechanicfor disconnecting of water/ refrigerant gas pipe lines , electric wiring connections and it connected electrical and mechanical fitting parts of items from inside area only for indoor unit system of existing central type AC / package type AC plant system any type/size any model of AC plant of rating cooling capacity from 08 TR to 30 TR of make- Voltas/Blue star/Caryaire/ Daikin etc and also providing carried out workfor checking / detecting and arresting of the refrigerant gas leakage problme in only for indoor unit system areaand it all inside connected system by putting nitrogen gas (N2 Gas) by pressure to entire inside system of AC plant component like inside area of condensing coil fin system , compressor unit , evaporator unit/chiller unit and it connected refrigerant pipe line and valve and filter etc complete area only for inside area system of plantafter detecting of gas leakage problem and ensure that afterthe repairing /rectification all the nos of area found point are leakages workwhere detectedhas been carried outrepairing/ jointing work completed with the help of welding/ brazing/ soldering with copper electrode rod work and after make it air / water leak proof of complete system again after providing air vacuum pressure of holding gas stand for 24 hrs and after satisfaction work till the holding gas pressure in entire inside indoor unitsystem of AC plant. they After charging ofthe refrigerant gasas required leveland alsotop up of compressor oil if required complete all as specified and directed by Engr-in-Charge. Note-The cost of on above quoted rate is included for charging/ filling of the required quantity ofnos of times used of nitrogen gas (N2 Gas) by pressure for testing to entire system, complete shall deemed no without any extra cost to paidthe contractor for many time testing.
7Required sufficient all qty of checking & testing of materials throughtN2 gas etc and ,T&P and man power as a well qualified technician / mechanicfor disconnecting of water/ refrigerant gas pipe lines , electric wiring connections and it connected electrical and mechanical fitting parts of items from inside area of only for outdoor condensingattachment unit system suitableforexisting central type AC / package type AC plant system any type/size any model of AC plant of make- Voltas/Blue star/Caryaire/ Daikin etc and also providing carried out workfor checking / detecting and arresting of the refrigenent gas leakage in only for outdoor condensingattechment unit areaand it all inside refrigerant pipe line connected system by putting nitrogen gas (N2 Gas) by pressure to entire inside system of AC plant component like inside area of condensing coil systemand it connected refrigerant pipe line and valve etc complete only for inside area system ofunitafter detecting of gas leakage problem and ensure that afterthe repairing /rectification all the nos of leakages workwhere detectedhas been carried out completed with the help of welding/ brazing/ soldering with copper electrode rod work and after make it leak proof of complete system again after providing air vacuum pressure of holding stand for 24 hrs and after satisfaction till the holding gas pressure in entire inside outdoor unitsystem of AC plant. Note-(i)The cost of on above quoted rate is included for charging/ filling of the required quantity of many times used of nitrogen gas (N2 Gas) by pressure testing to entire system, complete shall deemed no without any extra cost to paidthe contractor for many time testing.
8Supply and fixing in replacement ofpre airfilters / Air flow pre fine filter of approximate size 32 inch long x 19 inch width x 2 inch thickbox type or all as per existing sample/model/make etcThe pre filter outer body and support made out of mild steel framing work and inside area of fitted fixing / fittingofnon woven synthetic fiber media material along with and dullycover it by with the help of MS mesh complete set and suitable use for AHU system including taking out existing old filters complete all as specified and directed by Engr-in-Charge.
9Supply and fixing in replacement ofpre airfilters / Air flow pre fine filter of appox size 23.5 inch long x 23.5 inch width x 5.5 inch thick box type or all as per existing sample/model/make etcThe pre filter outer body and support made out of mild steel framing work and inside area of fitted fixing / fittingofnon woven synthetic fiber media material along with and dullycover it by with the help of MS mesh complete set and suitable use for AHU system including taking out existing old filters complete all as specified and directed by Engr-in-Charge.
10Supply and fixing in replacement ofpre airfilters / Air flow pre fine filter of approximate size 66 inch long x 63 inch width x 2 inch thickbox type or all as per existing sample/model/make etcThe pre filter outer body and support made out of mild steel framing work and inside area of fitted fixing / fittingofnon woven synthetic fiber media material along with and dullycover it by with the help of MS mesh complete set and suitable use for AHU system including taking out existing old filters complete all as specified and directed by Engr-in-Charge.
11Supply and fixing in replacement ofpre airfilters / Air flow pre fine filter of approximatesize51 inch long x 42 inch width x 2 inch thickbox type or all as per existing sample/model/make etcThe pre filter outer body and support made out of mild steel framing work and inside area of fitted fixing / fittingofnon woven synthetic fibermedia material along with and dullycover it by with the help of MS mesh complete set and suitable use for AHU system including taking out existing old filters complete all as specified and directed by Engr-in-Charge.
12Supply and fixing in replacement of Microprocessor controller card assembly with having showing as operating LCD display unit complete set all as per model No- VLRP singleor VLRP single V3 Adelux type suitable of range 6/5/4 type and Aux supply 8 V & 12 V complete set of Make - Softhard and suitable use it for operation of central AC plantsystem of make- Voltas including providing of interference controller cable leadand after fixing testing onload complete all as specified and directed by Engr-in-Charge.
13Supply and fixing in replacement of Microprocessor based controller card as per model No- PMN MPD TWIN typeof suitable range7 to 22 A and having Aux supply 230 Volt complete set of Make - Softhard and suitable use it for operation of panel system including providing of interference controller cable lead and after fixing testing onload complete all as specified and directed by Engr-in-Charge.
14Supply and fixing in replacement of Microprocessor controller operating display unit with havingoperating LCD display suitable for operation for plant system all as per model No- PMN MPD complete set of Make - Softhard including providing of interference controller cable lead complete and after fixing testing onload complete all as specified and directed by Engr-in-Charge.
15Supply and fixing in replacement of Microprocessor controller MVPD card unit as per model No- EC type MVPD of suitable range 30 to 220 Amps and Aux supply 220 Voltcomplete set of Make - Softhard and suitable use it for operation of panel system including providing of interference controller cable lead complete and after fixing testing onload complete all as specified and directed by Engr-in-Charge.
16Supply and fixing in replacement of Microprocessor controller card unit as per model No-M2PD-WOD of suitable range 01 to 10 Amps complete set ofMake - Softhard and suitable use it for operation of panel system including providing of interference controller cable lead complete and after fixing testing onload complete all as specified and directed by Engr-in-Charge.
17Supply & charging of refrigerant gas R- 22 in company sealed cylinder / Tin of as required demand capacity including providing of cylinders after refilling and testing of gas of complete work including providing of gas test certificate by authorized agencies complete all as specified and directed by Engr-in-Charge.
18Supply & charging of refrigerant gas R-410 A in company sealed cylinder / Tin of as required demand capacity including providing of cylinders after refilling and testing of gas of complete work including providing of gas test certificate by authorized agencies complete all as specified and directed by Engr-in-Charge.
19Supply and filling in replacement of non freezing compressor oil or all as per existing sample/grade/type etc in company sealed standard size containers / barrels/drum after refilling and testing it complete all as specified and directed by Engr-in-Charge.
20Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- VP104KSE-TFP-423 of make -Emerson Copeland or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.
21Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- ZR72KC-TFD-522 or ZR72KC-TFD-52E of make -Emerson Copeland or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.
22Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- ZR108KF-TFD-550 of make -Emerson Copeland or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.
23Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- SM120S4EA of make- Danfoss or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.
24Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- SM110S4EA of make- Danfoss or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.
25Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- HLM072T4LC6 of make- Danfoss or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe comcomplete all as specified and directed by Engr-in-Charge.
26Supply and fixing in replacement new one vertical type sealed scroll compressor unit assembly complete set for three phase supply system all as per compressor of model No- JTIGCVDKYR of make- Daikin or all as per equivalent model, rating capacity and technical specification as per the existing type of sample/model of compressor unit of other equivant make and suitable use for smooth operational of existing package type/ central type AC plant system and including also providing of first time initial full fill of the refrigerant gas filling work as per the suitable type as manufacture recommended refrigerant gas and compressor oil in new one compressor complete unit system and duly fixed it in side of of AC plant system with the help of making / jointing of refrigerant pipe line connection on existing system complete work after fixing the compressor unit work providing of vacuum pressure for checking leakage and defect rectification of the gas leakage problem work in system ,if gas found leakage at entire site system than to making arrangement for by any method and ensure that make it perfectly air leak proof of complete work after completion of complete worktrails to it on load run testing till to as a satisfaction level ofEIC including dismantling and taking out of old compressor unit withgas pipe complete all as specified and directed by Engr-in-Charge.Note forall Compressor unit from Sl item No 20 to 26 -Before installation of all type/size/capacity of compressor unit contractor to be submit the manufacture test certificate of compressor unit along with warranty cardand purchase voucher to produce Engineer In Charge for their verification purposed.
27Disconnecting of water/gas pipe lines connections with outer grill with unit system any type any position and removing of electric wiring connections from each ceiling mounted cassette type of square shape fan coil condensing unit system any type any model and any capacity and also dismantling /opening of all type offitted nut, bolt locking patch and filter parts from inside and outside area of complete system including providing adequate servicing material and lobour and all type of T&P for cleaning of condenser coil unit and it connected fixing accessories of complete system including removing of blower fan with motor from condenser unit body system and cleaning it with the help of high efficiency air pressure blower with vacuum pump including providing of suitable cleaning & washing chemical materials for clean of inside and outside body area and removing dust particles and sludge and also providing of oiling and greasing servicing work on moving parts etc of body system after complete cleaning /servicing work, re fixing the all removing items on same to its original position including checking of tightness of all the nuts & bolts of units system andthey after testing it on load complete all as specified and directed by Engr-in-Charge.
28Disconnecting of water/gas pipe lines connections with outer grill with unit system any type any position and electric wiring connections from each wall mounted indoor type of rectangular shape fan coil condensing unit system any type any model and any capacity and also dismantling /opening of all type offitted nut, bolt, locking patch and filter parts from inside and outside area of complete system including providing adequate servicing material and lobour and all type T&P for cleaning of condenser coil unit and it connected fixing accessories of complete system including removing of blower fan with motor from condenser unit body system and cleaning it with the help of high efficiency air pressure blower with vacuum pump including providing of suitable cleaning & washing chemical materials for clean of inside and outside body area removing of dust particles and sludge and also providing of oiling and greasing servicing work on moving parts etc of body system after complete cleaning /servicing work, re fixing the all removing items on same to its original position including checking of tightness of all the nuts & bolts of units system andthey after testing it on load complete all as specified and directed by Engr-in-Charge.
29Disconnecting of refrigenent gas pipe lines and electric wiring connections and removing of old burnt/ unserviceable defective compressor unit all as per existing type twin port compressor unit of model No-06D-018 of make- Voltas from AC plant site and after dismantling work, opening & removing of all type of nut, bolt, and it old unserviceable fitted components from inside area of complete compressor body system including providing ofwell qualified technician / mechanic or technical rep of existing manufacture make of AC plant compressore with alltype of T&Pfor replacement and reassembling of this semi hermetic existing twin port compressor unit system with the help of providing of all new one spare parts for compressor unit system all as per model No-06D-018 of make- Voltas. The all new parts of items should be properly match to each other as per the existing parts or all as per existing type/sample and model & rating capacity and technical specification of existing compressor parts complete.and also replacement and reassemble inside area of existing compressore unit system, after replacement/ re fixing and reassembling of all below mention nos of new spare components / parts of items and after completion of complete work duly fixed to compressore unit in side ofAC plant system with the help of making / jointing of refrigerant pipe line connection on existing system etc complete job after fixing the compressor unit work providing of vacuum pressure for checking gas leakage and defect rectification of the gas leakage problem work in system , if gas found leakage at site system than to making arrangement for by any method and ensure that make it perfectly gas leak proof of complete work after satisfaction of work also full fill of the refrigerant gas and compressor oil of complete inside unit system and trails to it on load run testing till to as a satisfaction level oftechnician rep and complete all as specified and directed by Engr-in-Charge. Note - (i) All new one spares fitting components/ parts of itemsfor existing compressor unit model No-06D-018 of make- Voltas as mentioned blow of this schedule of items and measured items as supply only.
30Supply only piston set along with piston pin, complete all asspecified and directed by Engr-in-Charge.
31Supply onlypiston rings set & piston pin lock washer set complete all as specified and directed by Engr-in-Charge.
32Supply onlyconnecting rod complete all asspecified and directed by Engr-in-Charge.
33Supply only valve plate complete all asspecified and directed by Engr-in-Charge.
34Supply only discharge reel and Suction reed complete all asspecified and directed by Engr-in-Charge.
35Supply only discharge reed retainer cap complete all asspecified and directed by Engr-in-Charge..
36Supply onlycompressor oil filter complete all asspecified and directed by Engr-in-Charge..
37Supply only crank shaft of compressor complete all asspecified and directed by Engr-in-Charge..
38Supply only compressor oil pump with lock washer and screw complete set complete complete all as specified and directed by Engr-in-Charge.
39Supply only release valve complete all as specified and directed by Engr-in-Charge.
40Supply only gasket set complete all as specified and directed by Engr-in-Charge.
41Supply onlyrewinding of compressor motor complete all as specified and directed by Engr-in-Charge.
42Supply only thrust washer complete all as specified and directed by Engr-in-Charge.
43Supply only CC heater complete all as specified and directed by Engr-in-Charge.
44Supply only connection plate with thimble complete all as specified and directed by Engr-in-Charge.
45Supply only metal bush complete all as specified and directed by Engr-in-Charge.
46Supply and fixing in replacement of new PCB card unit assembly complete suitable used for ceiling mounted4 way cassette type of square shape fan coil condensing unit system and matching with as per existing cooling capacity 24566BTU/HR and air circulation 1360CMH of unitsystem suitable for all as per model No - MCMA or MCA-800D series type of make -Cayaire or all as per equivalent sample/model rating capacity and specification as per existing type of unitand suitable use for smooth operation of system and after replacement of PCB unit work trails to it on load run testing till to as a satisfaction level ofEIC including dismantling of old PCB complete all as specified and directed by Engr-in-Charge.
47Supply and fixing in replacement of new PCB card unitcomplete set all as per PCB model No/Type- CRC 2052 or all as per equivalent sample/model rating capacity and specification as per existing type and suitable use for smooth operation of AC system with having cooling capacity 3 to 5 TR and after replacement of PCB unit work trails to it on load run testing till to as a satisfaction level of EIC including dismantling of old PCB complete all as specified and directed by Engr-in-Charge.
48Supply and fixing in replacement of new PCB card unitcomplete set all as per PCB model No- RXYQ12PRY6 with power supply 380-415 voltand suitable for mode input for cooling 8.93 KW and heating 9.06 kw or all as per equivalent sample/model rating capacity and technical specification as per existing type and suitable use for outdoor system of package type AC unit VRV III invertors type of capacity 11 TRMake -Daikin and after completion / replacement ofPCB worktrails to it on load run testing till to as a satisfaction level of technician including dismantling of old PCB complete all as specified and directed by Engr-in-Charge.
49Supply , fixing, testing ,commissioningin replacement of new one Main controller unit with HMI screen display controller complete set all as per controller model No- SZ4070C-B of make- SUB ZERO with rating power supplyDC 24 V . 7W and including making programming cum uploading/setting work for operating of existing system or all as per equivalent sample/model rating capacity and technical specification as per existing type and suitable used operation and smooth working functional for automation operation system for package type AC plant for as model no- TCA 401XH , Make- Caryire of capacity 15 TR including providing along with it connectedelectronic circuit controller cardwith connecting controlling input / output communication cable with adaptors ports / USB port interference adaptor lead complete set and including full filling uploading setting of all the programmable captures feature data for any customized process with LCD display along with adjustment setting of key pad buttons with indication complete work includng providing and making of electrical connection andtrails to it on load run testing till to as a satisfaction level of EIC including taking down of old controller unit complete all as specified and directed by Engr-in-Charge.
50Supply and fixing in replacement of newline voltage monitor regulator controller unit (VMRC) all as per VMRC model No- VMRC-10/1 of make- SUB ZERO complete set or all as per equivalent sample/model rating capacity and technical specification as per existing type and suitable used operation and smooth working functional for automation plant paneling system and after replacement ofparts worktrails to it on load run testing till to as a satisfaction level of EIC including dismantling of old PCB complete all as specified and directed by Engr-in-Charge.
51Supply and fixing in replacement of new PCG unit or EEV unit (Electronic expansion valve)all as per PCG model No- PCG101-080844731 of make- SUB ZERO complete set with having power 5W max and power supply 24 VDCand temp range0 - 60 Degree centigrade and R.H.20 - 85 % or all as per equivalent sample/model rating capacity and technical specification as per existing type and suitable used operation and smooth working functional for automation plant paneling system and after replacement ofparts worktrails to it on load run testing till to as a satisfaction level of technician including dismantling of old PCB complete all as specified and directed by Engr-in-Charge.
52Supply and fixing in replacement of SMPS unit with having suitable rating output 24 Volt DC system and input 230 volt AC with current of rating 3 to 10 Ampor all as per equivalent sample/model rating capacity and technical specification as per existing type complete all as specified and directed by Engr-in-Charge.
53Supply and fixing in replacement of SMPS unit with having suitable rating output 24 Volt 2A all as per unit device model No-ME48Wand input power supply 110/220V +-15% Make Staror all as per equivalent sample/model rating capacity and technical specification as per existing type complete all as specified and directed by Engr-in-Charge.
54Supply and fixing in replacement of cast iron sluice valve of size80 mm dia bore PN 1.6 class with having flanged and drilled ends, type pattern, along with havingbrass spindle ,operating wheel including providing suitable size jointing materials as rubber washers/gaskets along with suitable type / size of bolts and nuts, etc, including taking downand removal of old sluice valve, complete all as specified and directed by Engr-in-Charge.
55Supply and fixing in replacement of cast iron sluice valve of size50 mm dia bore PN 1.6 class with having flanged and drilled ends, type pattern, along with havingbrass spindle ,operating wheel including providing suitable size jointing materials as rubber washers/gaskets along with suitable type / size of bolts and nuts, etc, including taking downand removal of old sluice valve, complete all as specified and directed by Engr-in-Charge.
56Supply and fixing in replacement of cast iron sluice valve of size 25 mm dia bore PN 1.6 class with having flanged and drilled ends, type pattern, along with havingbrass spindle ,operating wheel including providing suitable size jointing materials as rubber washers/gaskets along with suitable type / size of bolts and nuts, etc, including taking downand removal of old sluice valve, complete all as specified and directed by Engr-in-Charge.
57Supply, fixing in replacement ofMS pipe line of size 80 mm bore medium grade along with providing all type/ sizes fittings,or including duly fixing and jointing with the help of cutting/welding/brazing of hot/cold any type/description of work or and laying in trenches/fixed along walls or laid under floors/ wall,after including replacing, jointing/connection along with existing branch pipeline connections system works complete all as specified and directed by Engr-in-Charge.
58Supply, fixing in replacement ofMS pipe line of size 50 mm bore medium grade along with providing all type/ sizes fittings,or including duly fixing and jointing with the help of cutting/welding/brazing of hot/cold any type/description of work or and laying in trenches/fixed along walls or laid under floors/ wall,after including replacing, jointing/connection along with existing branch pipeline connections system works complete all as specified and directed by Engr-in-Charge.
59Supply, fixing in replacement ofMS pipe line of size 40 mm bore medium grade along with providing all type/ sizes fittings,or including duly fixing and jointing with the help of cutting/welding/brazing of hot/cold any type/description of work or and laying in trenches/fixed along walls or laid under floors/ wall,after including replacing, jointing/connection along with existing branch pipeline connections system works complete all as specified and directed by Engr-in-Charge.
60Supply, fixing in replacement ofMS pipe line of size 25 mm bore medium grade along with providing all type/ sizes fittings,or including duly fixing and jointing with the help of cutting/welding/brazing of hot/cold any type/description of work or and laying in trenches/fixed along walls or laid under floors/ wall,after including replacing, jointing/connection along with existing branch pipeline connections system works complete all as specified and directed by Engr-in-Charge.
61Supply, fixing in replacement of heavy duty shock resistance and fire resistance type insulating rubber foot mate of appoximate of size 1mtr x 2 mtr x 19 mm made out of bland of high quality natural rubber and having upper side surface of mate isrough marked and the bottomside of mate is anti and skid no slip type suitablefor conductive parts, and preventto people from being exposed to excessive voltage of 1100 voltAC supply system and to be safely dissipated & also reduce electromagnetic interference complete all as specified and directed by Engr-in-Charge.
62Supply & fixing and in replacement of thermostatic expansion valves all as per existing sample/model rating capacity and technical specification as per existing type and suitable operation used for central type / package type AC plant of rated capacity from 5.5 TR to 11 TR and duly replaced & fixed it on existing same positioning of refrigerant gas pipe line system of plant with the help of cutting/welding/brazing of hot/cold any type/description of work after replacing jointing/connection in system and they after checking and rectification the gas leakage work and making it perfectly gas leak proof after completion of complete worktrails to it on load run testing till to as a satisfaction level of technician including dismantling of old compressor complete all as specified and directed by Engr-in-Charge.
63Supply & fixing and in replacement of thermostatic expansion valves all as per existing sample/model rating capacity and technical specification as per existing type and suitable used for central type / package type AC plant of rated capacity from15 TR to 30 TR and duly replaced & fixed it on existing same positioning of refrigerant gas pipe line system of plant with the help of cutting/welding/brazing of hot/cold any type/description of work after replacing jointing/connection of refrigerant pipe line system and they after checking and rectification the gas leakage work and making it perfectly leak proof after completion of complete worktrails to it on load run testing till to as a satisfaction level of technician including dismantling of old compressor complete all as specified and directed by Engr-in-Charge.
64Supply & fixing in replacement of electronic timer with having range 1-10 Amps, 230 volts or all as per existing sample/model rating capacity and technical specification and suitable use for plant panel system complete all as specified and directed by Engineer-in-Charge
65Supply & fixing in replacement of LED indicator lamps of colour red / green/ yellow etc oras per existing sample/model rating capacity and technical specification and suitable use for plant panel system complete all as specified and directed by Engineer-in-Charge
66Supply & fixing in replacement of of 8 pin type AC/DC relay with base adaptor of rating up to 250VAC/28VDC 10 A or as per existing sample/model rating capacity and technical specification and suitable use for plant panel system complete all as specified and directed by Engineer-in-Charge
67Supply & fixing in replacement of single phase preventer all as per modelVSP D 2 / VSP 3 type with having AC aux supply 415 volt50 HZ or as per existing sample/model rating capacity and technical specification and suitable use for plant panel system complete all as specified and directed by Engineer-in-Charge
68Supply and fixing in replacement of new one ceiling mounted4 way cassette type of square shape fan coil condensing unit along with outer grill and in built fitting & fixture accessories complete set all as per model No - MCMA or MCA-600D series type of make -Cayaire and with having the approximate size of unitbody frame of size23 inch long x 23 inch wide x 11.5 height or all as per existing equivalent sample/model rating capacity and technical specification etc after replacement of condensing unit complete worktrails to it on load run testing till to as a satisfaction level ofEIC and including dismantling of old unit complete all as specified and directed by Engr-in-Charge.
69Supply and fixing in replacement of new one ceiling mounted4 way cassette type of square shape fan coil condensing unit along with outer grill and in built fitting & fixture accessories complete set all as per model No - MCMA or MCA-800D series type of make -Cayaire and with having the approximate size of unitbody frame of size 29 inch long x 29 inch wide x 11.5 height or all as per existing equivalent sample/model rating capacity and technical specification etc after replacement of condensing unit complete worktrails to it on load run testing till to as a satisfaction level ofEIC and including dismantling of old unit complete all as specified and directed by Engr-in-Charge.
70M& L for dismantling & taking out existing defective/ burnt outof electric motor of any type /description & in any model of rating capacity 2 to 3 HP and carry out by transporting to workshop for rewinding with the help of providing of super enameled copper winding wire of superior quality of all as per existing size/ gauge & No of turns and insulation of the same and also providing insulating materials such as leatheriest fiber glass, illumines paper, cotton tape, glass sleeve, insulating varnish etc all as per instructions including cutting and taking out existing burnt/ short circuited winding wires and including replacement of existing defected with new bushes, bearings & starting condenser complete system and they after re-assembling and re fixing of the same motor at its original position after repair, making all necessary electric connections and than testing on load complete all as specified and directed by Engr-in-Charge.
71M& L for dismantling & taking out existing defective/ burnt outof AC electric condenser (Outdoor unit) fan motor of any type /description & in any model of rating capacity 375 /500 watt and carry out by transporting to workshop for rewinding with the help of providing of super enameled copper winding wire of superior quality of all as per existing size/ gauge & No of turns and insulation of the sameand also providing of insulating materials such as leatheriest fiber glass, illumines paper, cotton tape, glass sleeve, insulating varnish etc all as per instructions including cutting and taking out existing burnt/ short circuited winding wires and including replacement of existing defectedwith new bushes, bearings & starting condenser complete system and they after re-assembling and re fixing of the same motor at its original position after repair, making all necessary electric connections and than testing on load complete all as specified and directed by Engr-in-Charge.
72Supply and fixing in replacement of MNX type series electrical power contactor of rating capacity 9 Amp to 15 Amp with3/4 pole 415 volt AC along withover load thermal realy and auxiliary contactor relay NO/NC ytpe complete set or all as per equivalent sample/model rating capacity and specification and make of as per existing type and suitable used foroperational of existing panel controlling system including taking down of old contactor complete all as specified and directed by Engr-in-Charge.
73Supply and fixing in replacement of MNX type series electrical power contactor of rating capacity 18 Amp to 40 Amp with3/4 pole 415 volt AC along withover load thermal realy and auxiliary contactor relay NO/NC ytpe complete set or all as per equivalent sample/model rating capacity and specification and make of as per existing type and suitable used foroperational of existing panel controlling system including taking down of old contactor complete all as specified and directed by Engr-in-Charge.
74Supply and fixing in replacement of MNX type series electrical power contactor of rating capacity 42 Amp to 70 Amp with3/4 pole 415 volt AC along withover load thermal realy and auxiliary contactor relay NO/NC ytpe complete set or all as per equivalent sample/model rating capacity and specification and make of as per existing type and suitable used foroperational of existing panel controlling system including taking down of old contactor complete all as specified and directed by Engr-in-Charge.
75Supply and fixing in replacement of round type star/stop push button switch with indication LED lamp light complete or all as per equivalent sample/model rating capacity and specification and make of as per existing typecomplete all as specified and directed by Engr-in-Charge.
76Supply & fixing in replacement of eliminator drier core catch refrigerant gas filter assembly of having high capacity 100% molecular sieve for system with as per existing samples/size suitable used for central type AC plant refrigeration system and duly fixed it in side of of AC plant system with the help of cutting / jointing of refrigerant pipe line system connection on existing system etc complete all as specified and directed by Engr-in-Charge.
77Supply & fixing in replacement ofV Belt of any type/size complete suitable use for package type AC plant blower motor pulley attachment system or all as per equivalent sample/model rating capacity and specification and make of as per existing typecomplete all as specified and directed by Engr-in-Charge.
78Supply & fixing in replacement ofcartage fuse of any type/size or all as per equivalent sample/model rating capacity and specification and make of as per existing typecomplete all as specified and directed by Engr-in-Charge.
79Supply & fixing in replacement of fan blade set ( three/four type blade set)of any type/size complete setand suitable use for package type AC plant outdoor condenser unit attachmentsystem and suitable used in ventilation fan or all as per equivalent sample/model rating capacity and specification and make of as per existing typecomplete all as specified and directed by Engr-in-Charge.
80Supply & fixing in replacement of PVC connector three phase, 4-pole, 100 Amps rated capacity of any type/size or all as per existing sample/model complete suitable use for plant panel system complete all as specified and directed by Engr-in-Charge.
81Supply & fixing in replacement of PVC connectorsingle phase, 10/20 Amps rated capacity of any type/size or all as per existing sample/model complete suitable use for plant panel system complete all as specified and directed by Engr-in-Charge.
82Supply & fixing in replacement of strip type heating element of rated capacity 2/3KW, 230 volts, or any type/size or all as per existing sample/model complete suitable use for plant chamber/ducting system and duly fixed by means cutting, welding, screwing nuts, bolts, washer work & testing on load complete including dismantling of old strip complete all as specified and directed by Engr-in-Charge.
83Supply, fixing & jointing in replacement of heavy duty copper tubing suitable use for refrigerant gas for suction piping system of any type/size all as per existing sample/model complete with insulating material and fixing supports/ saddles etc as required at site to match existing line complete all as specified and directed by Engr-in-Charge.
84Supply, fixing & jointing in replacement of heavy duty copper tubing suitable use for refrigerant gas for discharge piping system of any type/size all as per existing sample/model complete with insulating material and fixing supports/ saddles etc as required at site to match existing line complete all as specified and directed by Engr-in-Charge.
85Supply and fixing in replacement of OP/LP/HP cut off switch all as per existingsample/model and existing rating capacity and dully fixed on anydescription& in any position with existing system including making electric connection with the help of any method including after checking and testing on full load complete all as specified and directed by Engr-in-Charge.
86Supply, fixingin replacement of suction/discharge line control valve of size 3/8 to 5/8 or any type/sizeall as per existing sample/model complete suitable use and duly fixing by copper welding on discharge/ suction line system complete all as specified and directed at site by Engr-in-Charge
87M&L for taking down carefully existing of air curtain unit complete and cleaning/servicing/adjustment/overhauling of air blower with motor and oiling/ greasing work including, repair/replacement of defected parts as per existing sample like air grill and circuit system etc which is all as required at site complete including re fixing of air curtain complete system on same positioncomplete all as specified and directed by Engr-in-Charge.
88Supply & fixing in replacement of dial type water pressure gauge of suitable 4” dia of working pressure 5/10 kg / sqcum or as per existing type & size complete with suitable size of adopter and stainless steel pipe with adopter pipeincluding duly fixed with existing system by the help ofwelding ,bending cold or hot anddrilling all asper required at site complete all as specified and directed including dismantling old pressure gauge complete all as specified and directed by Engr-in-Charge.
89Supply & fixing in replacement of multi core round type PVC insulated and PVC round sheathed, flexiblemulti stranded copper conductor cable heavy duty 1100 volt grade conforming toISI mark of nominal area of cable conductor of size4 Sqmm4 core and duly fixed on wall/ceilingand making electrical connection including taking down of existing cable complete all as specified and directed by Engr-in-Charge.
90Supply & fixing in replacement of multi core round type PVC insulated and PVC round sheathed, flexiblemulti stranded copper conductor cable heavy duty 1100 volt grade conforming toISI mark of nominal area of cable conductor of size2.5 Sqmm3 core and duly fixed on wall/ceilingand making electrical connection including taking down of existing cable complete all as specified and directed by Engr-in-Charge.
91M&L for disconnecting of all type of nut bolt along with water pipe lines any type any position and electric wiring connections from each heating boiler plant system any type/size & model and any capacity and after dismantling /opening of top cover plate with all type of nut, bolt and other connected parts from inside and outside area of complete body system including providing adequatelobour and allT&P like hydra machine / chain pulley block for removing and taking out of leakages / damage existing MS heating coils double / single type cooling coilwith pipes system from inside area of plant chamber after checking leakage problem work where found it and rectifying the same leakage by with the help of cutting/welding/brazing/soldering of hot/cold any type/description of workand make it water leak proof after replacing jointing/connection of complete boiler coil pipe line work including providing ofsufficient quality of de-scaling chemical solution (ORISCALE BLASTER) / de scaling cleaning compound material duly recommended by manufacture/ technician rep and full fill it in suitable proportion including ater full filling it on coiling system till the time and storage in system minimum hrs or up to completion of deposits/scale is removed on the system then after de-scaling and cleaning with the help of chemical solution along with mechanical high speedpump arrangement system for entire inside chocked water tubes circulation system and ensure that coil are cleaned up to as satisfaction of EIC after completion of work re fixing the same coil on same place and reconnection the water pipe line connection on same position of system including replacement of all new one gasket packing seal/ with suitable defected nut & bolt ,washer etc of pipe and make it serviceable & leakage poof system and after testing it on load complete all as specified and directed by Engr-in-Charge.
92M&L for disconnection of electric supply cable connection from main control panel and removing of unserviceable old control panel from AC plant system complete including providing supply ,fixing, testing and commissioning of new one microprocessor control panel suitablefor three phase power based system complete with totally compact enclosures factory assemble along with in built fitting all type of paneling operating controlling fixing component accessories complete panel unit set all as per manufacture microprocessor controller panel model - 14TR PMN MPDTWIN3 Phasewith SR NO: 612/PAC/PNL/Y2K6-3 and DRG. NO : 01 SHAPL of panel manufacture Make - SofthardAutomation Pvt. Ltd and including utilization in 3 phase 415 Volt 50 Hz power supply system and suitable use for smooth operation of existing package type AC plant system with having working principle air cooled based AC plant compressore with two ooutdoor condensing unit type along with blower motor working in microprocessor control panel based operating system ofAC plant system suitable for operation of rating capacity 14/15 TRof make - Voltas.The approximate size of microprocessor control panel is approximate 19 inch length height 15 inch width and 5.5 inch depthor all as per size /type equivalent model rating capacity and utilization technical specification as per existing type of sample/model of existing control paneling system of complete.The microprocessor control panelis factory fabricated made out heavy duty mild steel sheet with powder coated and including totally enclosed weather ,dust & vermin proof having single door opening system and making locking arrangement with fabricated on MS hinges ,clamp, nut & bolt etc The panel should be fitted on inside of AC plant body system with the help of drilling and welding hot & cold working system complete with all fixing accessories all as specified and directed by Engr-in -Charge
93M&L for disconnection of electric supply cable connection from main control panel and removing of unserviceable old control panel from AC plant system complete including providing supply ,fixing, testing and commissioning of new one microprocessor control panel suitable for three phase power based system complete with totally compact enclosures factory assemble along with inbuilt fitting all type of paneling operating controlling fixing component accessories complete panel unit set and utilization in 3 phase 415 Volt 50 Hz power supply system and suitable use for smooth operation of existing package type AC plant system with having working principle air cooled based compressore unit with two outdoor condensing unit type along with blower motor working in microprocessor control panel based operating system suitable for operation ofAC plant system of rating capacity 15 TRof make - Voltas.The approximate size of microprocessor control panel is approximate 19 inch length height15 to18 inch width and 5.5 inch depth (thick) or all as per equivalent as per existing type of sample/model of existing control paneling system of complete box set .The microprocessor control panelis factory fabricated made out MS sheet heavy duty mild steel sheet with powder coated and including totally enclosed weather ,dust & vermin proof having single door opening system with gasket set and making locking arrangement with fabricated on MS hinges ,clamp, nut & bolt etc . The inside of control paneling system should be duly fitted consisting of no of required item likeincoming/outgoing feeder mounting channels ,insulator & cable connector for three/single phasing cable net working system and having suitable type /size of main three phase & neutral copper cabling connection along with suitable sizes of all inter connected interlocking control wiring system which is connected to all controlling operating item of equipments system including providing ofstart stop push button with its indication lamp and suitable three phase RYB LED indicator lamp set and internal control wiring with multi stranded copper wire and fuse box etc including dully fixed comprising of following below mentioned fixing controlling accessories complete system. The panel should be fitted on inside/outside of AC plant system with the help of drilling and welding hot & cold working system complete with all fixing accessories all as specified and directed by EIC. (a)MCB of rating capacity 100 Amps 4 pole 10 KA 415 volt- 01 No, (b)Microprocessor controller card PMN MPD TWIN type of range capacity 7-22 A along with outer display unit- 01 No(c)Power contactor MNX series type contactor of rating capacity 40Amp 3/4 pole with thermal over load relay along with Aux contacts NO / NC relay complete set suitable for power supplyAC 3 rating system including all electric inter connection wiring net work connection - 03 Nos complete set, (d)Single phasing preventer having system AC aux supply 415 volt AC 50 HZ of type/ model VSP 2 or VSP3 type complete - 01 No, (e)Electronic timer with having range 1-10 Amps, 230 volts complete - 01No,(f) "T" type relay or AC/PCB relay card of rating 12 Volt 30 Amp -01No, (g) Main fuse box and cartage fuse of complete system- 01No Set, (h)Three and single phase no of connector for complete system- 01No Set, (j) All panel fixing item inter connection wiring net work connection of complete system - 01No Job, (k) Digital type multi functionalVolt meter & Amp meter - 01No Set
94Supply and fixing in replacement of cooling/ heating sensor lead all as per existing type / size / sample and dully fixed on anydescription& in any position with existing system with the help of any method including checking and testing on full load complete all as specified and directed by Engr-in-Charge.
95Supply , fixing and replacement of 65/80 mm dia bore of butter fly valve/ hand shut down stop valve as per existing type /sample made of cast iron body with chromium plated stainless steel shaft & disc of ductile iron epoxy coated complete set including duly fixed with existing pipe line system with the help of jointing cutting, welding , nuts bolt & washer ,with flanges, etc complete including removing unserviceable valve of different sizes complete all as specified & directed by Engineer-in-Charge.
96Supply and fixing in replacement ofby new one aroma flex insulation material or runner sponge form tube shape size insulated material suitable use for chiller /condenser system & its connected refrigerant gas pipe lines area etc or all as per existing type and size/ sample/model and specification and duly fixed on and covered with layer of tap and to match and finishing with existing surface of system complete including taking down and removing old defected existing unserviceable and damaged insulation & it parts of any description and in any position complete all as specified and directed by Engr-in-Charge.