| 1 | Wiring for circuit/submain wiring along with earth wire with the following sizes PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as reqd. |
| 2 | 2x4.0 sq mm +1x4.0 sq mm earth wire(for 188 Nos split AC) |
| 3 | 4x4.0 sq mm +2x4.0 sq mm earth wire(32 mtr lengthfor each 46nos tower AC) |
| 4 | S/D following sizes of FR PVC insulated copper conductor,single core cable in the exixting surface/recessed pvc conduit as reqd. |
| 5 | a)5x4 sqmm(Outdoor wiring for 46nos outdoor wiring of tower ac ) |
| 6 | S/F of 25mm size PVC conduit along with accessories an surface/recess including cutting the wall and making good the same in case recessed conduit as reqd. |
| 7 | S/F following way vertical type three pole and neutral,sheet steel MCB distribution board 415 volts on surface/recess,complete with tinned copper busbar,neutral busbar,earth bar,din bar,detachable gland plate,interconnections,phosphatized and powder painted including earthing etc as reqd.(But without MCB/RCCB/ISOLATOR) |
| 8 | 8 way (4 + 24), Double door, Vertical type(For Tower AC) |
| 9 | S/F 6 Amps to 32 Amps rating 240 volts \"B\" series MCB suitable for lighting and other loads of the following poles in the existing MCB DB complete with connection,testing,commisioning etc as reqd. |
| 10 | 6/32 Amps,single pole,\"B\"series(For Split AC) |
| 11 | 6/32 Amps,TPN (For Tower AC) |
| 12 | Supplying and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections etc as reqd. |
| 13 | 100amps,16KA fixed thermal setting(for incomer in TPN DB) |
| 14 | Supplying and fixing 20 amps,240 volts,SPN industrial type,socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps \"C\" series,SP MCCB,in sheet enclosure, on surface or in recess with chained metal cover for the socket outlet and complete with connections,testing and commisioning etc as reqd. |
| 15 | Supplying and fixing 20 amps, 415 volts,TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, TPN, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 16 | S/L L.T power XLPE insulated PVC sheathed(Heavy duty) aluminium conductor armoured electric cable for working voltage 1100 volts IS:1554(Part I)1989 Make-Havells/Polycab/finolex/or equi. |
| 17 | 35 sqmm,3.5 core(From feeder panel to TPN DB in different section) |
| 18 | 70sqmm,3.5core(From Main1 &2to different Feeder Panel ) |
| 19 | 95sqmm,3.5core(From Main1 &2to different Feeder Panel ) |
| 20 | 150sqmm, 3.5core(2 Run x279mtr ,From Main Panel 1 to Main Panel 2 at Court Building) |
| 21 | 240sqmm, 3.5core(2 Run x695mtr ,From Main LT Panel at Substation to Main Panel 1 at Court Building) |
| 22 | Laying of one number additional PVC insulated and PVC sheathed/XLPE power cable of 1.1KV grade of size exceeding 185sqmm but not exceeding 400sqmm direct in ground in the same trench in one tier horizontal formationincluding excavation, and refilling the trench etc as reqd. |
| 23 | Laying and fixing of of one numberPVC insulated and PVC sheathed/XLPE power cable of 1.1KV grade of size on wall surface as reqd upto 35sqmm |
| 24 | Laying and fixing of of one number additional PVC insulated and PVC sheathed/XLPE power cable of 1.1KV grade of size on wall surface as reqd above 35sqmm to 95sqmm |
| 25 | Laying and fixing of of one number additional PVC insulated and PVC sheathed/XLPE power cable of 1.1KV grade of size on wall surface as reqd above 95sqmm to 185sqmm |
| 26 | 35 sqmm aluminium lugs |
| 27 | 70 sqmm aluminium lugs |
| 28 | 95 sqmm aluminium lugs |
| 29 | 150 sqmm aluminium lugs |
| 30 | 240 sqmm aluminium lugs |
| 31 | Feeder Panel-Fabrication and installation of cubicle panel with following accessories made 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade making PCC plinth and foundation including fitting/fixing/connection & transportation up to work site,labour charge etc all complete |
| 32 | 250Amps MCCB 35KA,fixed thermal stting(Incomer)-01Nos |
| 33 | 125Amps MCCB 35KA,fixed thermal stting(Outgoing)-06Nos |
| 34 | Spreader link set of 8 Nos(Make-ABB/L&T/C&S) |
| 35 | Extended rotary handle |
| 36 | Digital Voltmeter (0-500Volt) |
| 37 | Digital Ammeter (0-500Amp) |
| 38 | Current Transformer,class 15VA for metering ratio 200/5 |
| 39 | LED Indicator lamp R/Y/B-15 Nos |
| 40 | 30 x 5 sqmm eletrolytic copper strip for Bus-Bar Incomer-50Kg |
| 41 | Main Panel 1-Fabrication and installation of cubicle panel with following accessories made 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade making PCC plinth and foundation including fitting/fixing/connection & transportation up to work site,labour charge etc all complete |
| 42 | 800Amps MCCB 35KA,fixed thermal stting(Incomer)-01No |
| 43 | 400Amps MCCB 35KA,fixed thermal stting(Outgoing)-02No |
| 44 | 250Amps MCCB 35KA,fixed thermal stting(Outgoing)-06No |
| 45 | Spreader link for 800A set of 8 Nos |
| 46 | Extended rotary handle for 800Amp |
| 47 | Spreader link for 400A set of 8 Nos(ABB/L&T/C&S) |
| 48 | Extended rotary handle(ABB/L&T/C&S) |
| 49 | Spreader link for 250A set of 8 Nos(Make-ABB/L&T/C&S) |
| 50 | Extended rotary handle for 250Amp |
| 51 | Digital Voltmeter (0-500Volt) |
| 52 | Digital Ammeter (0-500Amp) |
| 53 | Current Transformer,class 15VA for metering ratio 300/5 |
| 54 | LED Indicator lamp R/Y/B-19 Nos |
| 55 | 50 x 5 sqmm eletrolytic copper strip for Bus-Bar Incomer -80Kg |
| 56 | Main Panel 2-Fabrication and installation of cubicle panel with following accessories made 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade making PCC plinth and foundation including fitting/fixing/connection & transportation up to work site,labour charge etc all complete |
| 57 | 400Amps MCCB 35KA,fixed thermal stting(Incomer)-01No |
| 58 | 250Amps MCCB 35KA,fixed thermal stting(Outgoing)-06No |
| 59 | Spreader link for 400A set of 8 Nos(ABB/L&T/C&S) |
| 60 | Extended rotary handle(ABB/L&T/C&S) |
| 61 | Spreader link for 250A set of 8 Nos(Make-ABB/L&T/C&S) |
| 62 | Extended rotary handle for 250Amp |
| 63 | Digital Voltmeter (0-500Volt) |
| 64 | Digital Ammeter (0-500Amp) |
| 65 | Current Transformer,class 15VA for metering ratio 300/5 |
| 66 | LED Indicator lamp R/Y/B-15 Nos |
| 67 | 50 x 5 sqmm eletrolytic copper strip for Bus-Bar Incomer -60Kg |
| 68 | Chemical Earthing with 80mm dia 3 mtr length earth electrode,Backfill compound chemical 4bag(25KG) as reqd.(02 EarthingEach for MainPanel 1 & 2 and 01 earthing each for 07nos Feeder panel) |
| 69 | Supplying and laying 8 SWG copper wire 0.50 meter below ground level for conductor earth electrode,including soldering etc as reqd. |
| 70 | G.S.T @ 18% |
| 71 | Labour Cess @ 1% |