Repair Maintenance To External Electric System Lt Panels And Other Connected Works At Sumdo Under Age Em We Pooh In Ge 863 Ews, Lahul And Spiti-Himachal Pradesh

Military Engineer Services-MES has published Repair Maintenance To External Electric System Lt Panels And Other Connected Works At Sumdo Under Age Em We Pooh In Ge 863 Ews. Submission Date for this Tender is 19-04-2024. Electrical Panel Tenders in Lahul And Spiti Himachal Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43056408
Corrigendum : Repair Maintenance To External Electric System Lt Panels And Other Connected Works At Sumdo Under Age Em We Pooh In Ge 863 Ews
Open Tender
Indian
Himachal Pradesh
Lahul And Spiti
19-04-2024

Tender Details

Repair Maintenance To External Electric System Lt Panels And Other Connected Works At Sumdo Under Age Em We Pooh In Ge 863 Ews

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Apr-2024 Tender Date Postpone Date 19-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 36000.0 /-
Tender Value
INR 18 Lakhs /-

BOQ Items

Name of Work : REPAIR / MAINTENANCE TO EXTERNAL ELECTRIC SYSTEM , LT PANELS AND OTHER CONNECTED WORKS ATSUMDO UNDER AGE E/M (WE) POOH IN GE 863 EWS.
Sl. No. Item Description
1Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr in depth in soft/loose soil for laying underground cables / erection of steel tubular poles / stay pit etc complete all as specified and directed.
2Returning and filling in two parts (i) using riddled soil obtained from excavated soil upto depth of 30 cm (8 cm below cable and remaining above cable for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil complete all as specified and directed. Note- Excavated soil shall be riddled by using sieve to separate composite particles etc as per IS - 1255-1983 and refilling in trenches as in cable cushioning.
3Removing excavated surplus material to a distance n exc 50m and depositing where directed at level n. exc 1.5m above the starting point complete all as specified and directed.
4M&L for laying dry bricks old size with subclass "B" made of burnt clay best quality locally available with permissible tolerance, laid straight trench for protection of cable complete all as specified and directed.
5M&L for cement concrete (1:4:8) type D2 with 40 mm graded stone aggregate for poles foundation etc complete all as specified and directed.
6M&L for cement concrete (1:3:6) type C1 with 20 mm graded stone aggegate for pole coping & road crossing etc including foam workcomplete all as specified and directed.
7Supply and stringing in replacement ACSR conductor ,any size conductor in accordance with site requirement and binding on insulators by means of aluminium binding wire complete all as specified and directed .
8S & F in replacement of galvanised steel wire of dia 4 mm for guard wire, continuous earth wire etc complete all as specified and directed.
9S & F in replacement of Stay assembly of 20 mm stay rod dia complete with loop type insulator, stay clamps, complete all as specified and directed. Note : Earth Work and concrete shall be mearsured and paid separately.
10S & F inreplacement cross arms bracings, supports, clamps and back plates fabricated from structural steel sections incl nut & bolts , washers welding, bending cold or hot drilling holes for bolts, washers in any shape or size including two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified & directed.
11S & F in replacement of pin type, porcelain vitreous, white, brown or green insulator incl one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 100 mm height 65mm dia for 1100 Volts grade complete all as specified and directed.
12S & F in replacement shackletype porecelain vitreous white brown or green insulator for working pressure 1100 volts of 90mm dia and 75mm height incl galvanised steel straps of 31x3 mm size insulator and 12 mm dia bolt,washer & nuts complete all as specified and directed.
13Removing and dismantalling old U/S over head line conductor (ACSR) of any size ( 2/4 line) and then cleaning , restringing in original position incl binding on insulators by means of aluminium binding wire, tapes complete all as specified and directed. (a)The rate quoted are inclusive of cutting/ removing all tree branches/ vegetation around 3 mtrs with 02 run of conductor. (b) Length of span is approx 30 mtrs with 02 run of conductor. (c) Adjusting & tightning of stay assembly shall be done wherever required.
14S&F in replacementsynthetic line separator of LT OHlines with nut,bolts & washers straight type horizontal configuration fixed at a point as directed and suitable for single phase 2 wire LT lines complete all as specified and directed.
15S&F in replacementsynthetic line separator of LT OHlines with nut,bolts & washers straight type horizontal configuration fixed at a point as directed and suitable for single phase 4 wire LT lines complete all as specified and directed.
16M&L for Cleaning and preparation of surface of MS Tubular pole 9.00 Mtr long and applying, Painting of two coat with aluminium paint over a coat of red oxide primer on MS tubularpole 9 Mtr long. Writing of Pole Nos on 1.5 mtr height from coping of pole, with synthetic enamel paints in 25 CM height , complete all as specified & directed.
17S & F in replacement of GI tubing 50mm (Light grade) laid in trenches / under roador fixed to wall as mechnical protection of UG cable complete all as specified and directed.
18S & F in replacement of GI tubing 80mm (Medium grade) , laid in trenches under roadas in mechnical protection of UG cable complete all as specified and directed.
19Supplying, laying, jointing & testing in repair cable XLPE insulated in , IS 7098(Part-I)-1988, ISI marked, screened, PVC sheathed,armoured electric power cable ( heavy duty) with aluminium conductor for working voltage upto and including 1100 Volts of croos sectional area 10 Sqmm 2 core with aluminium stranded, laid in trenches / fixed on pole / wall / passed through pipe complete with jointing material of LT Cable complete all as specified and directed. Note :- Any type of road cutting shall deemed to be be included in quoted rate and making good with PCC shall be measured separately.
20All as per item no 19 above but size 16 sqmm 4 core
21All as per item no 19 above but size 25 sqmm 3.5 core
22All as per item no 19 above but size 35 sqmm 3.5 core
23All as per item no 19 above but size 50 sqmm 3.5 core
24All as per item no 19 above but size 70 sqmm 3.5 core
25All as per item no 19 above but 95 Sqmm 3.5 core
26All as per item no 19 above but 150 Sqmm 3.5 core
27Supplying and fixing in repair 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 Sqmm stranded conductor ,complete all as specified & directed.
28All as per item no 27 above but size 16 sqmm.
29S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 400 Amps with breaking capacity 36 KA ,complete all as specified & directed. Make : Havells Cat Part No - IHLLSEB40400 or equavalent as approved.
30S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 250 Amps with breaking capacity36 KA ,complete all as specified & directed. Make : Havells Cat Part No - IHLLSEB40250 or equavalent as approved.
31S&F in repairMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 250 Amps with breaking capacity 25 KA, complete all as specified & directed. Make : Havells Cat Part No - IHLLSEB40250 or equavalent as approved.
32S&F in repair MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 200 Amps with breaking capacity 36 KA, complete all as specified & directed. Make : Havells Cat Part No - IHLLSEB40200 or equavalent as approved.
33S&F in repair MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 160 Amps with breaking capacity 25/27 KA, complete all as specified & directed. Make : Havells Cat Part No -IHA13DB40160 or equavalent as approved.
34S&F in repair MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 100 Amps with breaking capacity 16 KA, complete all as specified & directed. Make : Havells Cat Part No - IH13DB40100 or equavalent as approved.
35S&F in repair MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 63 Amps with breaking capacity 16 KA, complete all as specified & directed. Make : Havells Cat Part No - IHA13DBF0063or equavalent as approved.
36Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 63 amps complete all as specified & directed.
37Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 100 amps complete all as specified & directed.
38Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 160 amps complete all as specified & directed.
39Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 200 amps complete all as specified & directed.
40Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 250 amps complete all as specified & directed.
41Supply and fix in replacement of32 amps change overdouble pole with side operated handle, 230 volt AC, 50/60Hz, complete all as specified & directed.
42Supply and fix in replacement of 63 amps change overfour pole with side operated handle, 415 volt AC, 50/60Hz, complete all as specified & directed. Make : Havells Cat no IHBFFE0063 or equavalent as approved.
43Supply and fix in replacement of 100 amps change overfour pole with side operated handle, 415 volt AC, 50/60Hz, complete all as specified & directed. Make : Havells Cat No IHBFFE0100 or equavalent as approved.
44Supply and Fix in replacment of terminal box made out of PVC with hinged door and locking arrangements of size 240x130x95 mm including four way connector, fixed on pole with necessary clamps complete all as specified & directed.. Make Sintex, Cat No- GSJB-2014 or equavalent as approved.
45Supply and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified & directed.
46Supply and fix in replacement of Bus bar chamber box in sheet metal enclosure of 100 Amps capacity, 4 way, 415 V complete all as specified & directed. Make:Havells Cat Part No IHBC010004 or equavalent as approved.
47Supply, installing , testing and commissioning factory made and tested LT Panel box out door type , platform mounted suitable for 3 phase 3 wire, 50 HZ , AC Supply system base bus bar chamber with insulated Aluminium bus bar of rating more than 1.5 times of Main Incomer and suitable amps for neutral rating installed on porcelain insulator.The panel shall be dust and vermin proof IP65 class protection and made out of 3.15 mm thick CRCA MS sheet and fabricated with 40x40x6mm thick angle iron frame work for mounting , including PCC (1:2:4) type B1 using stone aggregate foundation and powder coated finish over one coat of red oxide primer outside two coats of primer inside and front & back opening type with double door shutter and proper space for cable entry and exit including provision of locking arrangement with 65mm Godrej (freedom) lock - 02 Nos with with following items complete all as specified & directed. :- (a)MCCB 200 Amps , 4 Pole , 25 KA Adjustable thermal & fixed magnetic type - 02 Nos (One Reserve) (b)MCCB 160 Amps , 4 Pole , 25 KA Adjustable thermal & fixed magnetic type - 02 Nos. (One Reserve) (c)MCCB 100 Amps , 4 Pole , 25 KA Adjustable thermal & fixed magnetic type - 02 Nos. (One Reserve) (d)MCB SPN 6-32 Amps - 02 Nos. (e)Phase indicator lamp - 01 set of three (f)Digital volt meter and Amps meter with selector switch- 01 Set Note : Drawing of panel will be approved by Engineer - in - Charge before fabrication.
48Material & labour in repairearthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below ground level at any type of strata) with top edge of the earth plate not less than 1.5mtr below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all around the plate. Connected by 32x6 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type C1 (using 20mm graded stone aggregate) with fair finish, internal surface of concrete chamber shall be given internal dia 300mmx300mm, 15mm thick plaster in CM 1:4) funnel with wire mesh,RCC pit cover of 320x320x80mm size in (1:2:4) Type B1 (using 20mm graded stone aggregate ) reinforced with XPM all as shown in electrical plate No 3 of MES SSR Part-1 (2009) and specified including and provision of GI strip upto 7.5 mtrs long with 40 mm dia light grade GI pipe for protection and watering pipe of GI 20 mm bore, medium grade, including all excavation and earth work and connecting the earthling stripto panel, including testing on completion complete all as specified and directed. Note : (i) RCC pit cover shall be precast of RCC(1:2:4) type B1, 80mm thick reinforced with XPM weighting not less than 4kg/sqm in lieu of CI cover.
49Note:- The total shall subject to adjustment of credit of Rs84285.00 for old Materials as per Schedule of Credit.
Disclaimer :