| 1 | M&L for removing from existing position, window/ Split type A/C unit 1.0/ 1.5 / 2.0 TR capacity of any make for servicing the same by complete cleaning the dust including supply and replacement of damaged wires with copper wire PVC insulated of same size, tightening of loose wire, nuts, bolts, servicing of condenser motor by oiling/ greasing, changing of damaged knobs, painting the old painted surfaces with one coat of synthetic enamel paint, setting of grills alignment complete including refixing in original position, testing & commissioning all as directed. |
| 2 | All as per item No. 01 here-in-above, but for 5/ 5.5 TR ductable split type air conditioner, three phase. |
| 3 | All as per item No. 01here-in-above, but for 11 TR Package type air conditioner, three phase. |
| 4 | All as per item No. 01 here-in-above, but for 1.0/ 2.0 TR VRF type air conditioner, three phase. |
| 5 | M&L for taking out rotary type compressor unit (uncut) from the split type Air Conditioner of any make, 1.0 ton capacity and replacing the sealed unit as per existing model with reconditioned sealed unit including the following all as specified and as directed. (a) Connection to suction/ discharge pipe with necessary repair and brazing.(b) Replacing the capillary tubes of existing size and copper liquid filter.(c) Flushing of entire system before gas charging.(d) Gas charging and testing after complete replacement including installing the machine at site and testing on full load for its smooth functioning complete all as specified and directed. |
| 6 | All as per item No. 05 here-in-above, but for 1.5 ton capacity. |
| 7 | All as per item No. 05 here-in-above, but for 2.0 ton capacity. |
| 8 | All as per item No. 05 here-in-above, but for 5/ 5.5 ton ductable split type Air conditioner, three phase. |
| 9 | All as per item No. 05 here-in-above, but for 1.5 ton split type Air conditioner, single phase, suitable for Refrigeration gas of R32. |
| 10 | All as per item No. 05 here-in-above, but for 2.0 ton split type Air conditioner, single phase suitable for Refrigeration gas of R32. |
| 11 | All as per item No. 05 here-in-above, but for 1.0 ton VRF type Air conditioner, three phase suitable for Refrigeration gas of R410a. |
| 12 | All as per item No. 05 here-in-above, but for 2.0 ton VRF type Air conditioner, three phase suitable for Refrigeration gas of R410a. |
| 13 | M&L for taking out rotary type compressor unit (uncut) from the Window type Air Conditioner of any make, 1.5 ton capacity and replacing the sealed unit as per existing model with reconditioned sealed unit including the following all as specified and as directed. (a) Connection to suction/ discharge pipe with necessary repair and brazing.(b) Replacing the capillary tubes of existing size and copper liquid filter.(c) Flushing of entire system before gas charging.(d) Gas charging and testing after complete replacement including installing the machine at site and testing on full load for its smooth functioning complete all as specified and directed. |
| 14 | All as per item No. 13 here-in-above but for 2.0 ton capacity |
| 15 | M&L for taking out Condenser unit from the split type Air Conditioner of any make and type,1.0 ton capacity and replacing the same with copper Condenser unit including necessary connection and testing after complete replacement as specified and as directed. |
| 16 | All as per item No. 15 here-in-above, but for 1.5 ton capacity. |
| 17 | All as per item No. 15 here-in-above, but for 2.0 ton capacity. |
| 18 | All as per item No. 15 here-in-above, but for 5/ 5.5 ton ductable split type Air conditioner, three phase. |
| 19 | M&L for taking out Condenser unit from the Window type Air Conditioner of any make and type, 1.5 ton capacity and replacing the same with copper Condenser unit including necessary connection and testing after complete replacement as specified and as directed. |
| 20 | All as per item No. 19 here-in-above, but for 2.0 ton capacity. |
| 21 | S&F in repair of thermostat switch with knob for any make Window type Air Conditioner of capacity 1.5/ 2.0 Ton including necessary electrical connection, lugs, insulation tape etc complete all as specified and as directed. |
| 22 | S&F in repair of thermostat switch with knob for any make Split type Air Conditioner of capacity 1.0/ 1.5/ 2.0 Ton including necessary electrical connection, lugs, insulation tape etc complete all as specified and as directed. |
| 23 | M&L for insulation of split type AC of capacity 1.0/ 1.5/ 2.0 Ton complete all as specified and as directed. |
| 24 | M&L for insulation of Ductable type AC of capacity 5/ 5.5 Ton complete all as specified and as directed. |
| 25 | S&F in repair fan motor suitable for Split Air Conditioner of capacity 1.0/ 1.5/ 2.0 ton complete all as directed. |
| 26 | S&F in repair fan motor suitable for ductable split Air Conditioner of capacity 5/ 5.5 ton complete all as directed. |
| 27 | S&F in repair blower motor suitable for Windows type Air Conditioner of capacity 1.5/ 2.0 ton complete all as specified and as directed. |
| 28 | S&F in repair blower motor sutable for Split Air Conditioner of capacity 1.0/ 1.5/ 2.0 ton complete all as specified and as directed. Make: Suitable for carrier /Voltas /LG /Blue star/ Amtrex spilt AC as per manufacturers make. |
| 29 | S&F in repair blower motor sutable for Ductable Split Air Conditioner of capacity 5/ 5.5 ton, as per existing make and model complete all as specified and as directed. |
| 30 | M&L for taking out defective burnt fan motor from the Split/ Window Air Conditioner of capacity 1.0/ 1.5/ 2.0 Ton, dismantling the same, taking out burnt copper winding and rewinding the same with super enameled copper winding wire of appropriate size and gauge, including replacement of defective bearing and bushes of existing size and standard make including varnishing to copper winding, over hauling the motor by replacing the clamps, nuts, bolts and rubber rag etc for smooth working of motor, re-assembling the motor and testing the motor at medium and full load complete all as directed. |
| 31 | All as per item No. 30 here-in-above, but rewinding for fan motor of 5/5.5 Ton ductable split air conditioner of any make and model. |
| 32 | All as per item No. 30 here-in-above, but rewinding for fan motor of 1.0 /2.0 Ton VRF type air conditioner for outdoor unit of any make and model. |
| 33 | M&L for taking out defective burnt blower motor from the Split type Air Conditioner of capacity 1.0/ 1.5/ 2.0 Ton, dismantling the same, taking out burnt copper winding and rewinding the same with super enameled copper winding wire of appropriate size and gauge, including replacement of defective bearing and bushes of existing size and standard make including varnishing to copper winding, over hauling the motor by replacing the clamps, nuts, bolts and rubber rag etc for smooth working of motor, re-assembling the motor and testing the motor at medium and full load complete all as directed. |
| 34 | All as per item No. 33 here-in-above, but rewinding for blower motor of5/5.5 Ton ductable split air conditioner of any make and model. |
| 35 | All as per item No. 33 here-in-above, but rewinding for blower motor of1.0/ 2.0 Ton VRF type air conditioner for indoor unit of any make and model. |
| 36 | S&F in repair blower for 1.0/1.5/2.0 ton capacity split Air Conditioner complete all as directed. Make: Suitable for carrier/ Voltas/ LG/ Blue star/ Amtrex spilt AC as per manufacturers make. |
| 37 | S&F in repair overload protector relay suitable for Window type AC of 1.5/ 2.0ton capacity including necessary electric connections, lugs, insulation tape etc complete all as specified and as directed. Make: AEI/ Shriram or make as approved by GE. |
| 38 | S&F in repair of overload protector relay suitable for 11 TR package type Air Conditioning including necessary electric connections, lugs, insulation tape etc complete all as specified and as directed. Make: AEI/ Shriram |
| 39 | S&F in repairs single pole and neutral enclosure with a two pin and earth plug and socket complete 240 V with one single pole MCB 32 Amps, \"C\" Curve complete all as directed. |
| 40 | S&F in repair remote circuit suitable for split type AC 1.0/1.5/2.0 Ton capacity as per existing make/ model complete all as specified and as directed. |
| 41 | S&F in repair remote circuit suitable for Window type AC 1.5/2.0 Ton capacity as per existing make/ model complete all as specified and as directed. |
| 42 | S&F in repair remote circuit suitable for 5/5.5 ton capacity Ductable type Air conditioning as per existing make/ model complete all as specified and as directed. |
| 43 | S&F in repair remote circuit suitable for 11 Ton capacity package type Air conditioning as per existing make/ model complete all as specified and as directed. |
| 44 | S&F in repair remote circuit suitable for 1.0/ 2.0 Ton capacity VRF type Air conditioning of indoor unit as per existing make/ model complete all as specified and as directed. |
| 45 | S&F in repair remote circuit suitable for 1.0/ 2.0 Ton capacity VRF type Air conditioning of Outdoor unit as per existing make/ model complete all as specified and as directed. |
| 46 | S&F in repair remote suitable for Window/split type AC 1.0/1.5/2.0 Ton capacity as per existing make/ model complete all as specified and as directed. |
| 47 | S&F in repair of air filter set suitable for split type AC of 1.0/ 1.5/ 2.0 tone capacity of any make and type complete all as specified and as directed. |
| 48 | S&F in repair of air filter set suitable for Window type AC of 1.5/ 2 tone capacity of any make and type complete all as specified and as directed. |
| 49 | S&F in repair of air filter set suitable for Ductable type AC of 5/ 5.5 tone capacity of any make and type complete all as specified and as directed. |
| 50 | S&F in repair of air filter set suitable for Package type AC of 11 TR capacity of any make and type complete complete all as specified and as directed. |
| 51 | S&F in repair of swing motor for 1.0/1.5/2.0 ton capacity split type AC of different types and makes, Each make of motor shall be same as original complete all as specified and as directed. |
| 52 | S&F in repair Fan Blade suitable for split type AC of capacity 1.0/1.5/2.0 ton complete all as directed. |
| 53 | S&F in repair contactor for split type AC, 1.0/ 1.5/ 2 Ton capacity as per existing make and capacity/ model etc complete all as directed. |
| 54 | S&F in repair contactor for Package type AC 11 TR capacity as per existing make and capacity/ model etc complete all as directed. |
| 55 | S&F in repair of PVC drain pipe of 15 mm dia 1.5 mtr length suitable for Split AC 1.0/ 1.5/ 2.0 ton capacity including necessary connection and fittings etc complete all as specified and as directed. |
| 56 | S&F in repair Selector switch suitable for Window type AC 1.5/ 2.0 Ton capacity as per existing make/ model complete all as specified and directed. |
| 57 | S&F in repair stand factory made for outdoor unit of split type AC 1.0/ 1.5/ 2.0 ton capacity complete all as specified and as directed. |
| 58 | S&F in repair service valve suitable for split AC of capacity 1.0/ 1.5/ 2.0 ton complete all as specified and as directed. |
| 59 | S&F in repair 2-4 mfd capacitor for window & Split AC of 1.0/ 1.5/ 2.0 Ton capacity including necessary electrical connections, lugs, insulation tape etc complete all as specified and as directed. Make: SIMCAP/ Unicop/ Usha/ Epcos |
| 60 | All as per item No. 59 here-in-above, but 6-10 mfd Capacity |
| 61 | All as per item No. 59 here-in-above, but 25 mfd Capacity |
| 62 | All as per item No. 59 here-in-above, but 36 mfd Capacity |
| 63 | All as per item No. 59 here-in-above, but 45 mfd Capacity |
| 64 | All as per item No. 59 here-in-above, but 50 mfd Capacity |
| 65 | All as per item No. 59 here-in-above, but 80-100 mfd Capacity |
| 66 | All as per item No. 59 here-in-above, but 100-120 mfd Capacity |
| 67 | S&F in repair capacity control solenoid valve suitable for 11 TR package type air conditioning, 230 V, 50 Hz including necessary control wiring, testing complete all as directed. |
| 68 | M&L for taking out Split type Air Conditioner of capacity 1.0/ 1.5/ 2.0 ton and re-fixing the same in existing or new location as directed by Engineer-in-Charge including making opening in the wall by cutting drilling, hammering the wall for placing ducts, pipes etc. and making good to match with existings specification and testing the same after re-fixing complete all as directed. |
| 69 | M&L for removing water cooler of 40/60/80/120/150 Ltr capacity from existing position after disconnecting from inlet water connection and plugged the water line and servicing the water cooler by cleaning the water tank cleaning the internal parts by blower and removing the burned wires and replacing the same with proper size copper conductor cable, repair/ replacement of damaged hinges, drain pipe up to 1.5m long, replacement of rusted nuts and bolts, tightening the all connections, refixing in original position connecting the water inlet and testing to the entire satisfaction complete all as specified and as directed by the Engineer-in-charge. (Note: Refrigerant filling will be measured and paid separately) |
| 70 | M&L for taking out defective burnt fan motor from the Water Cooler of capacity 40/60/80/120/150 ltr, dismantling the same, taking out burnt copper winding and rewinding the same with super enameled copper winding wire of appropriate size and gauge, including replacement of defective bearing and bushes of existing size and standard make including varnishing to copper winding, over hauling the motor by replacing the clamps, nuts, bolts and rubber rag etc for smooth working of motor, re-assembling the motor and testing the motor at medium and full load complete all as directed. |
| 71 | M&L for taking out old rotary compressor unitfrom water cooler storage type, 40/60/80 Ltr/hr cooling capacity and replacing the sealed unit as per existing capacity & model with reconditioned sealed unit including the following: (a) Connection to suction/discharge pipe with necessary replacement and brazing,(b) Replacing capillary tube of existing size and copper liquid filters.(c) Flushing of entire system before gas charging.(d) Gas charging and testing after complete replacement including installing the machine at site and testing on full load for its smooth functioning complete all as specified and directed. |
| 72 | All as per item No. 71 here-in-above, but for water cooler storage type of 120/150 Ltr/hr cooling capacity. |
| 73 | M&L for taking out Condenser unitfrom the water cooler of any make and type, 40/ 60/ 80/ 120/ 150 ltr capacity and replacing the same with copper Condenser unit including necessary connection and testing after complete replacement complete all as directed. |
| 74 | S&F in repair over load protector relay of water cooler of capacity 40/ 60/ 80/ 120/ 150 Ltr of make Usha/ Blue Star including necessary electrical connection, lugs, insulation tape etc complete all as specified and as directed. |
| 75 | S&F in repair of PVC drain pipe of 20 mm dia 1.5 mtr length suitable for water cooler including necessary connection and fittings etc complete all as specified and as directed. |
| 76 | S&F in repair PTMT float valve assembly 15mm bore with plastic ball including GI nipple 3 inch long for fixing float valve for water cooler complete all as specified and as directed. |
| 77 | S&F in repair PVC connection pipe 15mm bore and 45 cm long with brass joint both end and rubber washer complete all as specified and as directed. |
| 78 | S&F in repair 15mm dia concussive push button taps of CP cast copper alloy, screwed for iron pipe for water cooler complete all as specified and as directed. |
| 79 | S&F in repair thermostat switch with knob for water cooler of capacity 40/80/150 liters per hour including necessary electrical connection, lugs, insulation tape etc complete all as specified and as directed. Make: Indfoss/ Ranutrol |
| 80 | S&F in repair 3 pin 15 Amp plug top for water cooler including necessary electrical connection, lugs, insulation tape etc complete all as directed. |
| 81 | S&F in repair fan blade of water cooler of 40/ 60/ 80/ 120/ 150 liters per hour capacity suitable for make Usha/ Blue Star complete all as specified and as directed. |
| 82 | M&L for taking out rotary type compressor unit (uncut) of refrigerator for 286/300/310 Ltr capacity and replacing the sealed unit with reconditioned sealed unit of same brand including the following complete all as specified and as directed.(a) Connection to suction/ discharge pipe with necessary replacement and brazing. (b) Replacing capillary tube of existing size and copper liquid filters.(c) Flushing of entire system before gas charging.(d) Gas charging and testing the unit to the entire satisfaction. |
| 83 | M&L for taking out Condenser unit from the Refrigerator of any make, 286/300/310 ltr capacity and replacing the same with copper Condenser unit including necessary connection and testing after complete replacement complete all as specified and as directed. |
| 84 | S&F in repair of suitable box type relay with over load protector for refrigerator of capacity 286/ 300/ 310 liters of different make and size including necessary connections, lugs, insulation tape etc complete all as specified and as directed. |
| 85 | S&F in repair of thermostat switch with knob for any make refrigerator of 286/ 300/ 310 liters capacity including necessary electrical connection, lugs, insulation tape etc complete all as specified and as directed. Make: Indfoss/ Ranutrol |
| 86 | S&F in repair of cooling coil for refrigerator of 286/ 300/ 310 Ltrs capacity complete all as specified and as directed. |
| 87 | S&F in repair fan motor suitable for Deep freezer capacity upto 410 ltr complete all as directed. Make: AEU/ MEI or make as approved by GE. |
| 88 | S&F in repair 3 core, 1.5 Sqmm copper conductor flexible cable (ISI marked) for water coolers/ Window type ACs/ Split ACs/ Refrigerator/ Deep freezer etc complete all as directed. |
| 89 | All as per item No. 88 here-in-above, but flexible copper cable 3 core, 2.5 Sq.mm. |
| 90 | All as per item No. 88 here-in-above, but flexible copper cable 3 core, 4 Sq.mm. |
| 91 | S&F in repair PVC pipe 63 mm dia (ISI marked) for protection of insulation of split AC including necessary fittings complete all as specified and as directed. |
| 92 | Supplying and charging refrigeration gas F-22 or R-22 including checking complete system for any leakage for satisfactory operation at design temperature of the plant in all respects complete all as directed. |
| 93 | Supplying and charging refrigeration gas R-32 including checking complete system for any leakage for satisfactory operation at design temperature of the plant in all respects complete all as directed. |
| 94 | Supplying and charging refrigeration gas R-134a including checking complete system for any leakage for satisfactory operation at design temperature of the plant in all respects complete all as directed. |
| 95 | Supplying and charging refrigeration gas R-407 including checking complete system for any leakage for satisfactory operation at design temperature of the plant in all respects complete all as directed. |
| 96 | Supplying and charging refrigeration gas R-410 including checking complete system for any leakage for satisfactory operation at design temperature of the plant in all respects complete all as directed. |