| 1 | Comprehensive maintenance for diesel engine driven generating set by carrying out routine \"A\" check and \"B\" checkas recommended by the respective manufacturer of following capacity DG sets completeincluding cost ofminor items like petroleum jelly, grease, nut bolts etc during routine AMC checksonce in every month and attending unlimited breakdown calls.Note :-(a)Engine oil , radiator coolant oil ,filters required during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing those spares/filling of oils shall be deemed to be included in the rate quoted for this item. (b) Required T& P shall be arranged by the Contractor at site.(c) List of checks to be carried out under \"A\" and \"B\" check is enclosed in Particular specifications |
| 2 | (a) 500 KVA DG set at UAV Power house (Make - Kirloskar ) |
| 3 | (b) 250 KVA DG set at UAV Power house (Make - Kirloskar ) |
| 4 | (c) 160 KVA DG set at ATC Power house (Make - Ashok Leyland) |
| 5 | (d) 100 KVA DG set at New Adm Block (Make - Ashok Leyland) |
| 6 | (e) 82.5 KVA DG set at MI Room (Make - Kirloskar) |
| 7 | (f) 15 KVA DG set at TS Pump House (Make - Kirloskar ) |
| 8 | Dismantling the radiator and after cooler of following DG sets for removing all scales from the pipes by pressure washing using suitable solutions, checking for leakage, ,arresting leakage if any by welding / brazing , finishing, drying and refixing , filling coolant and testing complete all as directed by Engineer-in-charge. (Necessary coolant and distilled water required will be measured and paid separately under respective itemherein after). |
| 9 | (a) 500 KVA DG set at UAV Power house (Make - Kirloskar ) |
| 10 | (b) 250 KVA DG set at UAV Power house (Make - Kirloskar ) |
| 11 | (c) 160 KVA DG set at ATC Power house (Make - Ashok Leyland) |
| 12 | (d) 100 KVA DG set at New Adm Block (Make - Ashok Leyland) |
| 13 | (e) 15 KVA DG set at TS Pump House (Make - Kirloskar ) |
| 14 | Supply and fix in replacement of Battery 12 Volt 100 AH complete all as specified and directed. |
| 15 | Supply and fix in replacement of Battery 12 Volt 180 AH complete all as specified and directed. |
| 16 | Supply and fix Battery terminal heavy duty 1 mtr long standard copper cable with brass clamps, bolts, nuts, washers etc. including taking down old unserviceable item complete all as specified and directed.. |
| 17 | Supply only Engine oil SAE 15W40 high quality suitable for Kirloskar make DG set .Make : Kirloskar K-OIL |
| 18 | Supply only Engine oil SAE 15W40 high quality suitable for Ashok Leyland make DG set .Make : Servo Super / Gulf Leypower XLL Diesel Engine Oil |
| 19 | Supply only Coolant oil heavy duty suitable for KirloskarDG set.Make: Kirloskar K-Cool |
| 20 | Supply only Coolant oil heavy duty suitable for Ashok Leyland DG set. Make: Ley Power Coolant 5000/ TVS Girling Vericool Radiator Coolant Concentrate |
| 21 | Supply only Distilled water suitable for DG Set. |
| 22 | Dismantling the fuel pump from the Engine, transporting to the service center and complete servicing and overhauling of the pump including replacement of service kit ,element, delivery valve, plunger, copper washer etc all as required including re-calibration, refixing and testing for 160 kVA/100 kVA DG setcomplete all as specified and directed. |
| 23 | Dismantling the water pump from the Engine and supply and fixing new water pump of existing size and testing including taking down old unserviceable item complete all as specified and directed. |
| 24 | (a) 160 kVA/100 kVA DG set |
| 25 | (b) 500 KVA/250 kVA DG set |
| 26 | Draining out the diesel tank, cleaning / washing out the sludge using and re-filling with diesel for following DG set |
| 27 | (a) 500 KVA DG set at UAV Power house |
| 28 | (b) 250 KVA DG set at UAV Power house |
| 29 | (c)160 KVA DG set at New Adm Block |
| 30 | (c)100 KVA DG set at New Adm Block |
| 31 | (f) 15 KVA DG set at TS Pump House |
| 32 | Material and labour for Heating and varnishing of alternator for DG set 160 KVA DG set complete all as specified and directed. |
| 33 | Supply and replacement of the following items for DG set any capacity complete all as specified and directed. |
| 34 | (a) Oil pressure gauge. |
| 35 | (b) Radiator Cap |
| 36 | (c) Fuel Tank Cap with Lock |
| 37 | (d) Door lock of any type and size complete Set. |
| 38 | (e) Door gasket of any type and size complete set. |
| 39 | (f) AVRSuitable for 15 KVA Alternator |
| 40 | (g) AVRSuitable for 100 /160 KVA Alternators |
| 41 | (h) AVRSuitable for 250KVA Alternators |
| 42 | (j) AVRSuitable for500 KVA Alternators |
| 43 | (k) Multifunction digital meter |
| 44 | (m) Ignition switch with key for on, off and run. |
| 45 | (n) Indicator lamp for panel board as per existing size. |
| 46 | (p) No Volt Coil suitable for3 phase power contactor 300 Amps ratings |
| 47 | (q) AMF Relay 12 Volt AC for 250 kVA DG |
| 48 | (r) Battery charging alternator 24 Volt |
| 49 | (s) Temperature Gauge with sensor |
| 50 | (t) RPM Meter with connecting cable |
| 51 | (u) OilPressure Sensor |
| 52 | (v) Contactor 4 pole 250 Amps capacity |
| 53 | (w) Thermostat |
| 54 | Removing dismantling and overhauling of 12 volt starter motor, replacement of armature coil, field coil, bush bearing etc to make the starter motor serviceable complete all as specified and as directed. |
| 55 | Removing dismantling and overhauling of 24 volt starter motor, replacement of armature coil, field coil, bush bearing etc to make the starter motor serviceable complete all as specified and as directed . |
| 56 | Spray painting of diesel generating setof following capacitywith acoustic enclosure with one coat of synthetic enamel paint including writing of SM/MES No on engine and alternator, body colour shall be apple green, black for foundation base frame, red for all guards, all as specified and as directed . |
| 57 | (a) 500 KVA DG set |
| 58 | (b) 100 KVA DG set |
| 59 | Supply and replacement of auto 24 V battery charger with wiring complete all as specified and directed. |
| 60 | Supply and replacement of Canopy light 24V 18 W with wiring complete all as specified and directed. |
| 61 | Supply and replacement of Battery top lead postchanging complete all as specified and directed. |
| 62 | Supply and replacement of Asbestos rope complete all as specified and directed. |
| 63 | Supply and replacement of Emergency Stop switch complete all as specified and directed. |
| 64 | Supply and replacement of the following items for 100 kVA DG set complete all as specified and directed. |
| 65 | (a) Air filter inner and outer set . |
| 66 | (b) Oil filter . |
| 67 | (c) Fuel filter with water separator . |
| 68 | (d) Diesel Hose |
| 69 | (e) Diesel strainer |
| 70 | (f) Radiator Hose set |
| 71 | (g) Water pump radiator belt |
| 72 | Supply and replacement of the following items for 500 KVA DG set complete all as specified and directed. |
| 73 | (a) Air filter inner and outer set. |
| 74 | (b) Oil filter (2Nos) . |
| 75 | (c) Diesel filter with water separator bowl and hand priming pump . |
| 76 | (d) Diesel hose set |
| 77 | (e) Radiator Hose set |
| 78 | (f) Emergency stop switch |
| 79 | (g) Bus bar insulator |
| 80 | (h) Oil flasher unit |
| 81 | (j) Panel board glass with beading |
| 82 | (k) Radiator fan belt (3 Nos) |
| 83 | (m) Breather Hose |
| 84 | Supply and replacement of the following items for 250 kVA DG set complete all as specified and directed. |
| 85 | (a) Oil filter . |
| 86 | (b) Air filter inner and outer set. |
| 87 | (c) Fuel filter . |
| 88 | (d) Radiator fan belt |
| 89 | Supply and replacement of the following items for 15 KVA DG set complete all as specified and directed. |
| 90 | (a) Oil filter . |
| 91 | (b) Air filter . |
| 92 | (c) Fuel filter . |
| 93 | Supply and replacement of the following items for 160 kVA DG SETcomplete all as specified and directed. |
| 94 | (a) Oil filter. |
| 95 | (b) Air filter inner and outer set. |
| 96 | (c) Fuel filter . |
| 97 | (d) Fan belt |
| 98 | (e) Diesel Hose set (2 Nos) |
| 99 | Supply , erection, testing ofmaintenance free chemical earthing byauguring & installation of copper bonded rod using machine bore and filling with backfill compoundusingcopper bonded rod of dia 20 mm , length 3m , made of low carbon high tensile steel with copper plating (250+ microns)for preventing external corrosion, with top end connected with copper plated welded bus bar terminal of dimension 150mm x 50mm x 6 mm, complete conforms to IS : 3043 - 1987 and carbon based, high conductive backfill compound \"Conductolite\" with resistivity< 0.5 ohm-metre (In dry conditions) & resistivity is non-moisture dependant,pH Value : 8.0 - 9.0, electronic & ionic conduction, less susceptible to shrinkage, with hygroscopic & corrosion resistive properties and covering with heavy dutypolyplastic earth pit chamber cover . Make : M/s Ashlok Safe Earthing Electrode Limited or equivalent as approved by GE. |
| 100 | Material and Labourfor Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3mm copper strip complete all as specified and as directed by the Engineer-in-Charge |
| 101 | Schedule of credit amount brought back from Ser Page No. 31- Rs. 26,723.00 will be deducted from the above quoted amount to derive the contract sum.SIGNATURE OF CONTRACTOR |