Tender For Electrical Safety Related External Electrification Work At Lala Lajpat Rai And Affiliated Govt. Medical College, Kanpur, Kanpur Nagar-Uttar Pradesh

Uttar Pradesh Housing And Development Board-UPAVP has published Tender For Electrical Safety Related External Electrification Work At Lala Lajpat Rai And Affiliated Govt. Medical College, Kanpur. Submission Date for this Tender is 08-04-2024. Electrification Work Tenders in Kanpur Nagar Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43015939
Corrigendum : Tender For Electrical Safety Related External Electrification Work At Lala Lajpat Rai And Affiliated Govt. Medical College, Kanpur
Open Tender
Indian
Uttar Pradesh
Kanpur Nagar
08-04-2024

Tender Details

Tender For Electrical Safety Related External Electrification Work At Lala Lajpat Rai And Affiliated Govt. Medical College, Kanpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Apr-2024 Regarding Corrigendum Letter Date Technical Bid 08-04-2024

Key Value

Document Fees
INR 7080 /-
EMD
INR 990000.0 /-
Tender Value
INR 4.94 Crore /-

BOQ Items

NAME WORK :ELECTRICAL SAFETY RELATED EXTERNAL ELECTRIFICATION WORK AT LALA LAJPAT RAI AFFILIATED GOVT. MEDICAL COLLEGE, KANPUR.
Sl. No. Item Description
111 KV DOUBLE POLE STRUCTURE
2a. 2 Nos. 11 mtr. long SP-55 MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc.
3b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection.
4c .3 set 11KV Insulator complete with spindles & hardware complete as required.
5e. 1 No. 150 mm dia GI pipe class "B" (for XLPE cable protection) as required.
6f. 2 Set 50mm dia 3m long GI pipe earting with 25 x 3 mm GI earth strip complete as required
7g. 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices. [MAKE :- ONLY THOSE MANUFACTURER WHOSE G.T.P. ISAPPROVED BY KESCO]
8Supply of 11KV grade 3core Brand Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS 7098 / (PART-II) 1985 with latest amendments.[MAKE :-POLYCAB /GLOSTER/ STERLITE/ TORRENT/ L.S./ HAVELL"S/ UNIVERSAL/KEI AS PER G.T.P. APPROVED BY KESCO]
9240sq.mm 3 core
10300sq.mm 3 core
11Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
12Above 120 sq. mm and upto 400 sq. mm
13Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier orizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
14Above 120 sq. mm and upto 400 sq. mm
15Laying of one number XLPE power cable of 11/33 kV grade of following size direct in ground by mechanical mean alongwith laying of pipe as required.
16Above 120 sq. mm and upto 400 sq. mm
17Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : [MAKE:-RAYCHEM/M.SEAL/3M]
18240sq.mm 3 core/300sq.mm 3 core
19300sq.mm 3 core
20Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :[MAKE:-RAYCHEM/M.SEAL/3M]
21240sq.mm 3 core/300sq.mm 3 core
22300sq.mm 3 core
23Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : [MAKE:-RAYCHEM/M.SEAL/3M]
24240sq.mm 3 core/300sq.mm 3 core
25300sq.mm 3 core
26Supply of Heavy density poly ethylene pipes ISI marked anti radiant grade OD-160mm dia PN-6 grade having minimum wall thickness 9.5mm as per IS Code 4984 with socket coupler with trenchless excavation system. Complete in all respects Rex/Duraline/Time/Pioneer/EonnPlast/Narendra plast. make. As per direction of E/I.[MAKE :- THOSE MANUFACTURER WHOSE G.T.P.IS APPROVED BY ANY DISCOM]
27Supply & Installation of Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbarand connections from transformer to LT ACB will be by busbar connections. [MAKE-ABB/ SIEMENS/ KIRLOSKAR/ SCHNEIDER/ AREVA]
28Unitised Sub Station will have the following equipment
29H.T SWITCHGEAR
30Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.
31RMU NON Extensible (2 isolators, 1 VCB with CU Busbar
32Function type- 3 position disconnector and earthing switch equipped with separate drive unit.
331. Operation of LBS manual
342. Cable switch rating 11KV,630A, 25KA for 1 sec
353. Cable bushing rating 630A.
364. Cable cover- As per our standard.
375. Fixed type capacitive voltage indication provided.
386. ON/OFF/Earth indication on the front mimic of the panel.
397. Bottom cable termination-suitable upto 1 No. 3C X 300sq.mm
408. Cable entry bottom, front.
419. Fault passage indicator (FPI)-E/F
42FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. Breaker equipped with over current time release for transformer protection.
431. VCB 11KV, 630A, 25kA/1sec.
442. Operation of breaker-Manual
453. Self powered electronic numerical protection relay providing over current and earth fault protection.
464. Tape wound protection current transformer
475. Capacitive voltage indication fixed type.
486. ON, OFF, EARTH indication on the frount mimic of the panel
497. Cable box for termination of cable.
508. Cable cover stand.
519. Emergency trip push button.
5210. Shunt trip coil.
5311. Operation counter.
5412. Ammeter.
55RMU accessories-
56Manual Operating handle-1nos.
57Standard manometer for SF6 GAS pressure indication.
58Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm
59Transformer (Manufactured as per IS 1180 Level-II)
60Type- ONAN, Hermatically sealed corrugated tack.
611. Ratio- 11KV/433V
622. Capacity 800KVA
633. Vector group DYn11
644. Off load tappings +5% to -10% in steps of 2.5%
655. Winding- Double wound copper
666. Class of insulation-A
677. Ambient temp. 40 degree C
688. Temp. rise in oil over ambient- 40 deg. C
699. Temp. rise in winding over ambient- 45 deg. C
70Transformer Accessories
71Oil Temperature indicator
72LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar
731. Voltage rating 433V
742. Current rating- 1500 Amp.
75L.T Panel
76Incoming # 1
771600Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture
78ON, OFF TRIP lamp.
79R/Y/B indicating lamp.
80Multifunction meter
81CT-1600/5A, CL1.0, 10VA
82Incoming # 2 For Inbuilt 380KVAR APFC Panel
83800Amp. 50KA, TP ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel
84ON, OFF TRIP lamp.
85R/Y/B indicating lamp.
86Multifunction meter
87CT-800/5A, CL1.0, 10VA
88ENCLOSURE for PSS
89Rated temperature enclosure class should be K10
90Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick
91Earthing- Internal earthing connection by using 50X6 Aluminium strips.
92Unitised Sub Station (11KV / 415 V) 800 KVA With 1 I/C & 3 O/G (With Natural cooling)
93Supply & Installtion of Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/ Busbarand connections from transformer to LT ACB will be by busbar connections. [MAKE-ABB/ SIEMENS/ KIRLOSKAR/ SCHNEIDER/ AREVA]
94Unitised Sub Station will have the following equipment
95H.T SWITCHGEAR
96Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.
97RMU NON Extensible (2 isolators, 1 VCB with AL Busbar
98Function type- 3 position disconnector and earthing switch equipped with separate drive unit.
991. Operation of LBS manual
1002. Cable switch rating 11KV,630A, 25kA/1sec.
1013. Cable bushing rating 630A.
1024. Cable cover- As per our standard.
1035. Fixed type capacitive voltage indication provided.
1046. ON/OFF/Earth indication on the front mimic of the panel.
1057. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm
1068. Cable entry bottom, front.
1079. Fault passage indicator (FPI)-E/F
108FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection.
1091. VCB 11KV, 630A, 25kA/1sec.
1102. Operation of breaker-Manual
1113. Self powered electronic numerical protection relay providing over current and earth fault protection.
1124. Tape wound protection current transformer
1135. Capacitive voltage indication fixed type.
1146. ON, OFF, EARTH indication on the frount mimic of the panel
1157. Cable box for termination of cable.
1168. Cable cover stand.
1179. Emergency trip push button.
11810. Shunt trip coil.
11911. Operation counter.
12012. Ammeter.
121RMU accessories-
122Manual Operating handle-1nos.
123Standard manometer for SF6 GAS pressure indication.
124Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm
125Transformer (Manufactured as per IS 1180 Level-II)
126Type- ONAN, Hermatically sealed corrugated tack.
1271. Ratio- 11KV/433V
1282. Capacity 400KVA
1293. Vector group DYn11
1304. off load tappings +5% to -10% in steps of 2.5%
1315. Winding- Double wound copper
1326. Class of insulation-A
1337. Ambient temp. 40 degree C
1348. Temp. rise in oil over ambient- 40 deg. C
1359. Temp. rise in winding over ambient- 45 deg. C
136Transformer Accessories
137Oil Temperature indicator
138LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar
1391. Voltage rating 433V
1402. Current rating- 1000 Amp.
141L.T Panel
142Incoming
143800Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture
144ON, OFF TRIP lamp.
145R/Y/B indicating lamp.
146Multifunction meter
147CT-1000/5A, CL1.0, 10VA
148Incoming # 2 For Inbuilt 200KVAR APFC Panel
149400Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel
150ON, OFF TRIP lamp.
151R/Y/B indicating lamp.
152Multifunction meter
153CT-400/5A, CL1.0, 10VA
154Earthing- Internal earthing connection by using 50X6 Aluminium strips.
155Unitised Sub Station (11KV / 415 V) 400 KVA With 1 I/C & 3 O/G (With Natural cooling)
156Supply & Installation of Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbarand connections from transformer to LT ACB will be by busbar connections. [MAKE-ABB/ SIEMENS/ KIRLOSKAR/ SCHNEIDER/ AREVA]
157Unitised Sub Station will have the following equipment
158H.T SWITCHGEAR
159Three way, 11KV 630Amp. 25KA for 1sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.
160RMU NON Extensible (3 isolators, 1 VCB with AL Busbar
161Function type- 3 position disconnector and earthing switch equipped with separate drive unit.
1621. Operation of LBS manual
1632. Cable switch rating 11KV,630A, 25kA/1sec.
1643. Cable bushing rating 630A.
1654. Cable cover- As per our standard.
1665. Fixed type capacitive voltage indication provided.
1676. ON/OFF/Earth indication on the front mimic of the panel.
1687. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm
1698. Cable entry bottom, front.
1709. Fault passage indicator (FPI)-E/F
171FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection.
1721. VCB 11KV, 630A, 25kA/1sec.
1732. Operation of breaker-Manual
1743. Self powered electronic numerical protection relay providing over current and earth fault protection.
1754. Tape wound protection current transformer
1765. Capacitive voltage indication fixed type.
1776. ON, OFF, EARTH indication on the frount mimic of the panel
1787. Cable box for termination of cable.
1798. Cable cover stand.
1809. Emergency trip push button.
18110. Shunt trip coil.
18211. Operation counter.
18312. Ammeter.
184RMU accessories-
185Manual Operating handle-1nos.
186Standard manometer for SF6 GAS pressure indication.
187Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm
188Transformer (Manufactured as per IS 1180 Level-II)
189Type- ONAN, Hermatically sealed corrugated tack.
1901. Ratio- 11KV/433V
1912. Capacity 250KVA
1923. Vector group DYn11
1934. off load tappings +5% to -10% in steps of 2.5%
1945. Winding- Double wound copper
1956. Class of insulation-A
1967. Ambient temp. 40 degree C
1978. Temp. rise in oil over ambient- 40 deg. C
1989. Temp. rise in winding over ambient- 45 deg. C
199Transformer Accessories
200Oil Temperature indicator
201LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar
2021. Voltage rating 433V
2032. Current rating- 500 Amp.
204L.T Panel
205Incoming
206500Amp. 50KA, 4P MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture
207ON, OFF TRIP lamp.
208R/Y/B indicating lamp.
209Multifunction meter
210CT-630/5A, CL1.0, 10VA
211Incoming # 2 For Inbuilt 125KVAR APFC Panel
212250Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel
213ON, OFF TRIP lamp.
214R/Y/B indicating lamp.
215Multifunction meter
216CT-250/5A, CL1.0, 10VA
217ENCLOSURE for PSS
218Rated temperature enclosure class should be K10
219Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick
220Earthing- Internal earthing connection by using 50X6 Aluminium strips.
221Unitised Sub Station (11KV / 415 V) 250 KVA With 1 I/C & 3 O/G (With Natural cooling)
222SUB STATION SAFETY EQUIPMENT :
223Supplying and fixing 1800 mm x 900 mm wide checkered rubber matting conforming to IS5424-1969 complete as required.
224Suitable for 11KV
225Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass.
226Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
227Supplyand erection of ISI marked portable fire extinguishers, wall mounted type, wall brackets complete in all respects, including fixing on walls as per the direction of engineer-in-charge Make:Minimax/ Safex/ Seasefire/ Exflame/ Life Guard /Safe Fire/ Kanex/ Kalpex)
228Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. [MAKE-BHARATI/INDIANA/SLOTEO /CONSOUL]
229Earthing with copper earth plate 600 mm X 600 mmX3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.[MAKE-BHARATI/INDIANA/SLOTEO /CONSOUL]
230Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm) [MAKE-BHARATI/INDIANA/SLOTEO /CONSOUL]
231Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brassnut bolt & spring washer spaced at 50mm)[MAKE-BHARATI/INDIANA/SLOTEO /CONSOUL]