}

Tender For Repair Replacement Rerouting Of Electrical Network And Lt Panels Including Starters And Internal Wiring Street Light And Misc Items In The Aor Of Age U Ws Ii Under Ge U W S Delhi Cantt 10, delhi-Delhi

Military Engineer Services-MES has published Tender For Repair Replacement Rerouting Of Electrical Network And Lt Panels Including Starters And Internal Wiring Street Light And Misc Items In The Aor Of Age U Ws Ii Under Ge U W S Delhi Cantt 10. Submission Date for this Tender is 10-04-2024. Electrification Work Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

43010588
Tender For Repair Replacement Rerouting Of Electrical Network And Lt Panels Including Starters And Internal Wiring Street Light And Misc Items In The Aor Of Age U Ws Ii Under Ge U W S Delhi Cantt 10
Open Tender
Indian
Delhi
delhi
10-04-2024

Tender Details

Tender For Repair Replacement Rerouting Of Electrical Network And Lt Panels Including Starters And Internal Wiring Street Light And Misc Items In The Aor Of Age U Ws Ii Under Ge U W S Delhi Cantt 10

Key Value

Document Fees
INR 500 /-
EMD
INR 92000.0 /-
Tender Value
INR 46 Lakhs /-

BOQ Items

Name of Work: REPAIR/REPLACEMENT/REROUTING OF ELECTRICAL NETWORK AND LT PANELS INCLUDING STARTERS AND INTERNAL WIRING, STREET LIGHT AND MISC ITEMS IN THE AOR OF AGE (U) WS-IIUNDER GE (U) W/S DELHI CANTT - 10
Sl. No. Item Description
1Taking out existing unserviceable aluminium armoured PVC sheathed LT UG cable laid in trenches/fixed to poles & panels etc for replacement after excavation of following sizes :- (Note : (i) Earth work excavation will be measured and paid seperately under relevant items. (ii) All old unserviceable LT UG Cable shall be taken on charge and enter in demolition / salvage register in "RM" and attach the same page of salvage register with each RAR. If any serviceable cable obtained from the trench the same will be reused under respective items of BOQ.)
210 Sqmm4 Core
316 Sqmm4 Core
425 Sqmm3.5 Core
535 Sqmm3.5 Core
650 Sqmm3.5 Core
770 Sqmm3.5 Core
895 Sqmm3.5 Core
9120 sqmm3.5 core
10Relaying, testing & commissioning ofexisting LT aluminum armoured PVC sheathed UG cable laid in trenches/fixed to poles/panels after connected repair works of cable for following sizes :- (Note : (i) Earth work excavation will be measured and paid seperately under relevant items. (ii) Old serviceable cable obtained from item No 1 shall be reused after complete repair and charge of old lugs/joints with new one. Cost of lugs & joints shall be deemed included in quoted unit rate.)
1110 Sqmm4 Core
1216 Sqmm4 Core
1325 Sqmm3.5 Core
1435 Sqmm3.5 Core
1550 Sqmm3.5 Core
1670 Sqmm3.5 Core
1795 Sqmm3.5 Core
18120 sqmm3.5 core
19Supply & fixing including testing & commissioning of LT XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 1100 volts, grade of following sizes laid in trenches/fixed to poles & pannels etc:- (Note:- (i) Layout of cable shall be approved by GE before laying the same at site. (ii) Excavation & earth work shall be measured and paid seperately under respective items. (iii) LT XLPE cable shall be procured in one lot by contractor after approval of make and 1st RAR will be paid for "Material lying at site" only. (iv) Manufacturer"s test certificate, Tax invoice, purchase voucher & e-way bill shall be produced by contractor in original for verification of Engineer-in-Charge with material laid on site.)
2010 Sqmm4 Core
2116 Sqmm4 Core
2225 Sqmm3.5 Core
2335 Sqmm3.5 Core
2450 Sqmm3.5 Core
2570 Sqmm3.5 Core
2695 Sqmm3.5 Core
27120 sqmm3.5 core
28Labour only for laying existing burnt bricks sub class "B" old size laid in trenches with width equal to length of bricks across the cable for cable protection complete all as specified and as directed. (Note:- (i) Old serviceable bricks obtained during excavation shall be reused. (ii) Old unserviceable bricks/bricks bats shall be stacked at site and taken on charge under demolition / salvage register.)
29Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 metre depth and getting out in any type of soil for taking out/laying cables complete all as specified and as directed
30Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed
31Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed
32Supply filling and spreading, levelling of clean dry Yamuna river sand to required width at bottom and top for cable cushioning complete all asspecified and as directed. (Note:- Punned depth of sand cushioning shall be measured and paid.)
33Supply & laying of kiln brunt bricks sub class "B" old size laid in trenches with width equal to length of bricks across the cable for cable protection complete all as specified and as directed
34Supply and fixing in replacement ofdecorative gate light MASHROOM (PRISMATIC) including 20W LED lamp made up of high grade breakable polycarbonate material for retrofitcomplete all as specified and directed. (Note:- Old unserviceable light shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
35Supply and fixing in replacement of 20W surface/wall mounted 4 feet LED batten light with all fitting, extruded aluminium housing provided complete all as specified and directed. (Note:- Old unserviceable wall mounted shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
36Material and labour for copper/aluminium point wiring (light, fan, bell, independent or power) including complete fittings such as switches, ceiling roses, pendents, regulators, sockets etc and making good disturbed surfaces of wall, floor & ceiling etc. 1.5 Sqmm FRLS type PVC insulated and sheathed cable with copper conductor 1100 Volts grade, multistranded alongwith earth wire 1.5sqmm PVC insulated and sheathed copper wire FRLS type in 25mm dia PVC conduits with PVC fittings such as tee, bend & socket etc including M.S. sunken box dolly earth connected including taking down worn out wires etc complete all as specified and directed. (Note :- Old unserviceable point wiring alongwith all accessories such as sunken box, earth wire & wire, switch socket etc shall be taken on charge under demolition/salvage register of iron & copper scrap in "KG" and attach the same page with each RAR.)
37All as per srl item No-12- here-in-before but 2.5 Sqmm
38Taking down old UNSV of any description any type changeover switch and S&F new changeover switches in sheet metal encloser 415V, 50 Hz 200Amps 4 Pole "front handle operated" on existing pole/wall complete all as specified and directed.
39Taking down old UNSV any type changeover switch and S&F new changeover switches in sheet metal encloser 415V, 50 Hz 250 Amps 4 Pole "front handle operated" on existing pole/wall complete all as specified and directed.
40Taking down old UNSV of any description any type changeover switch and S&F new changeover switches in sheet metal encloser 415V, 50 Hz 400Amps 4 Pole "front handle operated" on existing pole/wall complete all as specified and directed. (Note for ser item No 14 to 16 : Old unserviceable change over switch shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
41Taking down the unserviceable power contactor ofany size and in replacement S&F of new power contactor ML 1.5 in existing starter panel complete all as specified and directed
42Taking down the unserviceable power contactor ofany size and in replacement S&F of new power contactor ML 2 in existing starter panel complete all as specified and directed
43Taking down the unserviceable power contactor of any size and in replacement S&F of new power contactor ML 3 in existing starter panel complete all as specified and directed
44Taking down the unserviceable power contactor of any size and in replacement S&F ofnew power contactor ML 4 in existing starter panel complete all as specified and directed
45Taking down the unserviceable power contactor or any size and supply and fixing new power contactor MNX 18 in existing starter panel complete all as specified and directed
46Taking down the unserviceable power contactor or any size and supply and fixing new power contactor MNX 32 in existing starter panel complete all as specified and directed
47Taking down the unserviceable power contactor or any size and supply and fixing new power contactor MNX 40 in existing starter panel complete all as specified and directed
48Taking down the unserviceable power contactoror any size and supply and fixing new power contactor MNX 70 in existing starter panel complete all as specified and directed
49Taking down the unserviceable power contactor or any size and supply and fixing new power contactor MNX 95 in existing starter panel complete all as specified and directed
50Taking down the unserviceable power contactor or any size and supply and fixing new power contactor MNX 110 in existing starter panel complete all as specified and directed. (Note for ser item No 17 to 26:- Old U/s material power contactor obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
51Taking down the unserviceable FASD ML 1.5 (with MU relay) ofany size and in replacement S&F of new FASD ML 1.5 (with MU relay) including stainless steel box existing starter panel complete all as specified and directed
52Taking down the unserviceable FASD ML 2 (with MU relay) ofany size and in replacement S&F of new FASD ML 2 (with MU relay) including stainless steel box existing starter panel complete all as specified and directed
53Taking down the unserviceable FASD ML3 (with MU relay) of any size and in replacement S&F of new FASD ML3 (with MU relay) including stainless steel box existing starter panel complete all as specified and directed
54Taking down the unserviceable FASD ML 4 (with MU relay) any size and in replacement S&F of new FASD ML4 (with MU relay) including stainless steel box existing starter panel complete all as specified and directed. (Note for ser item No 27 to 30:-Old U/s FASD obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV Iron Scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
55Taking down SVL / MVL/ MH/CFL/LED llight fittings 30/48/60/70 /100/120/150 /250 /400 watts from existing pole/buildings/plant of any height/type complete all as specified and directed. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
56Taking down un-serviceable street light fitting 45W/60W/90W any make and over handling of light fitting by replacement of unserviceable parts and S&F new driver/LED lamp to existing light of suitable make and model and light fitting make fully funcionalcomplete all as specified and directed. (Note:- Old unserviceable parts shall be taken on charge in iron scrap in "KG" and submit testing & calliberation report to Engr-in-Charge before payment).
57S&F in replacement of 100W LED street light made up of die cast aluminium housing with hight efficient LED as lightning source with toughened glass having IP66 protection and impact resistance of IK 07 with including all fitting such as suitable cable/GI pipe bracket/MCB for fixing on wall complete all as specified and directed. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
58S&F street light fitting 45/48 watt LED, energy saving and environmental friendly long life led street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening seperate driver compartment with IP66 protection and impact resistance of IK07 including taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
59S&F street light fitting 60 watt LED, energy saving and environmental friendly long life led street light made up of pressure die cast aluminium housing with high power led as lighting source and lens embedded PC cover having top opening seperate driver compartment with IP66 protection and impact resistance of IK07 including taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
60S&F LED Flood light fitting 100 wattenergy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting etc complete fixed bracket & suitable size and MS clamp and nut bolts washers etc complete and connected with twin core cable 1.5 sqmm from flood light to fittings connector including taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
61S&F LED Flood light fitting 150 wattenergy saving, environmental friendly, long life, exclusive innovative die cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade high mast and general purpose lightingincluding taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
62S&F LED Flood light fitting 120 wattenergy saving environmental friendly, long life, exclusive innovative die cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade high mast and general purpose lighting including taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
63S&F Energy saving flood light 30 Watt environmental friendly, long life, exclusive innovative die cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade high mast and general purpose lighting including taking down of existing light fitting complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
64M & L for Painting topoles (9 mtr long) including cross arms, brackets, "D" clamps, nuts, bolts,complete including painting with five strips of 30cm each black and white paint in alternate strips from the base of pole upto 1.5mtr height, writing of pole identyfication No. complete painting with two coat of synthetic enamel paint of first quality silver paint over a coat of red oxide primer after and including complete removal of old paint by scratching, rubbing complete all as specified and directed by Engr-in-Charge.
65Supply and fix in replacement of MS clamp (suitable for holding street light bracket on steel pole)made out of 40 mm wide 6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia-3 Nos with flat washer (3mm thick) -02 No for each including painting with aluminium paint over one coat of red oxide to the M.S clamps complete all as specified and directed. (Note :- Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill)
66S&F in repair sheet steel looping boxes of size 300 x200x150mm,factory made, consisting of 3.15 mm thickMS sheet and aluminium bus bar 3 phase, 4 wire system of capacity 200 Amp, MCB of capacity 10 Amp, 10 KA breaking capacity and proper locking arrangement and opening forincoming and outgoing cable including taking down of existing looping box complete all as specified and directed by EIC. (Note:-Old unserviceable material shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
67Supply and fix in replacement oflight gradeGalvanised mild steel pipe 80mm bore complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitablemild steel clamps , bolts , nuts and washers for cable protection complete all as specified and directed. (Note for ser item No 43 to 45:- (i) Excavation & earth work shall be measured and paidfor separately under appropriate item of this schedule. (ii) Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in length (RM) shall be taken into account and attach with RAR/F Bill)
68All as per above Item No 43 here-in-before but of size 50 mm bore
69All as per above Item No 43 here-in-before but of size 40 mm bore
70Supply and fix inreplacementof old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugsincluding crimping with crimping tools in the existing LT cable 25 Sqmmupto 120 Sqmm 3.5/4 core including necessary connection complete all as specified and directed. (Note :- Old U/s aluminium lugs from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of aluminium scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
71Supply and fix in replacement, errecting of steel tubular poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long)including painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellowpaint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide complete all as specified and directed. (Note: (i) Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule. (ii) Old unserviceable steel pole shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
72M&L For casting of foundation for steel tubular poles of concrete 15 cm Depth in bottom of Pit for bed concrete(1:4:8) Type D-2 using 40 mm graded aggregate for foundation of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete allas specified and directed at site.
73M&L For casting of Foundation for steel tubular poles of PCC 1:3:6 (nominal mix) type C-2(using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
74M&L For casting of foundation Coping for, steel tubular poles new and old with PCC(1:2:4) Type B-1 using 20 mm graded aggregate for coping of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete allas specified and directed at site.
75Supply and fix in replacement of Mild steel work in framed work such as gates,grills, framed guard bars, gratings, ladders, MS clamp for supporting of cable etc., with ends of bars shouldered and/ or riveted, or forged into spikes, and similar work complete all as specified and directed. (Note :- Old U/s frame work from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill)
76Supply and fix in replacement of aluminium strip 25 x 3.15mm with saddles and fixing screws, insulators rawal plugs etc forconductor for roof and fixed on wall upto test point complete all as specified and directed. (Note :- Old U/s aluminium strip demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of aluminium scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
77Supply and fix in replacement of galvanized iron strip 32 x 6 mm fixed with saddles & fixing screws, PVC dash fastners, insulators fixed from test point to earth on walls or burried in ground /drawn into hume pipe complete all as specified and directed. (NOTE : (i) Excavation & earth work shall be measured and paid for seperately under relevant item of schedule. complete all as specified and directed. (ii) Old U/s GI strip demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
78Supplying and laying in repacement ,synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed. (Note :- Old U/s rubber insulated mats demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of rubber scrapin weight (KG) shall be taken into account and attach with RAR/F Bill)
79Supply and fix inreplacement of 1100 Volts grade heavy duty cable PVC insulated aluminum conductor , served with inner sheathing of PVC tape and overall PVC sheathed twin core cable flat or circular of size of aluminum conductor 6 sq mm stranded conductor including taking down old UNSV cable complete all as specified and directed. (Note:- Old U/s aluminium conductor demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of aluminium scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
80S&F of cable joint kit of size 4 core 16 sqmm for heat shrinkable straight through joint complete all as specified and directed
81S&F of cable joint kit of size 4 core 25 sqmm for heat shrinkable straight through joint complete all as specified and directed
82S&F of cable joint kit of size 3.5 core 35 sqmm for heat shrinkable straight through joint complete all as specified and directed
83S&F of cable joint kit of size 3.5 core 50 sqmm for heat shrinkable straight through joint complete all as specified and directed
84S&F of cable joint kit of size 3.5 core 70 sqmm for heat shrinkable straight through joint complete all as specified and directed
85S&F of cable joint kit of size 3.5 core 95 sqmm for heat shrinkable straight through joint complete all as specified and directed
86S&F of cable joint kit of size 3.5 core 120 sqmm for heat shrinkable straight through joint complete all as specified and directed. (Note for ser item No 56 to 62 :-Old unserviceable joints shall be taken on charge and enter in demolition / salvage register in "EACH" and attach the same page of salvage register with each RAR.)
87Material and labour for pin point the fault by arranging fault locating machine in any size of LT UG cable from any location/position/situtation, taking down/out the faulty portion of cable, of any length from trenches, jointing with cable jointing kit & testing for satisfactorily serviceable with & including necessary excavation and earth work, sand cushioning and making necessary connections to make it functional complete all as specified and as directed. Note :- (i) Cable jointing kit shall be measured and paid seperetely. (ii) Old retrieved bricks/cable cover shall be reused (iii) The rates quoted includes excavation & earth work with sand cushioning.
88M&L for repair / maintenance of LT panel board having 2-4 starters at pump house, complete overhauling by dismentling all cable terminals, taking out star-delta starters, busbars, MCCBs in replacement of following points:-
89unsv copper / aluminium cable end terminals,
90unsv nuts, bolts & washers,
91unsv copper/aluminium wires from busbar MCCB & MCCB ,star-delta starters
92unsv CTs
93unsv Ampmeters/voltmeters
94unsv selector switches
95unsv ON/OFF Push buttons
96unsv LED indicator with lamps
97unsv star-delta staters,
98unsv SPP,
99unsv door panel fixing screws,
100unsv panel wiring and complete assembling of LT panel board with serviceable items as dismentled and new items as replaced, spray painting with one coat of synthetic enamel paint to external surface of panel board, testing after completion all as specified and directed. (Note for ser item No 64 to 65:- (i) MCCBs, Ampmeter, voltmeter, selector switches, push buttons, LED indicators, CTs, Star-delta starters, relay, timer, SPPs required for replacement will be measures in relevent item. (ii) Old U/s material demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrapin weight (KG) shall be taken into account and attach with RAR/F Bill)
101All as per item No 64 above but LT panel board having 01 Starter
102S&F in replacement DOL starter 5 HP relay range 7-10Ampin existing starter panel complete all as specified and directed
103S&F in replacement DOL starter 7.5 HP relay range 10-13Amp in existing starter panel complete all as specified and directed
104S&F in replacementDOL starter 10 HP relay range 13-18 Ampin existing starter panel complete all as specified and directed. (Note for item No 66 to 68 :- Old U/s DOL Starter demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrapin weight (KG) shall be taken into account and attach with RAR/F Bill)
105S&F in replacementDirect mounting on ML 1.5 contractor Thermal over load relay,relay range 6-10 Amps suitable for fixing in existing panel complete all as specified and directed.
106Supply and fixing in replacement Direct mounting on ML 1.5 contractor Thermal over load relay,relay range 10-16 Amps suitable for fixing in existing panel complete all as specified and directed.
107Supply and fixing in replacementDirect mounting on ML 2/3contractor Thermal over load relay, relay range 13-21 Amps suitable for fixing in existing panel complete all as specified and directed.
108Supply and fixing in replacementDirect mounting on ML 2/3 contractor Thermal over load relay, relayrange 20-32 Amps suitable for fixing in existing panel complete all as specified and directed.
109Supply and fixing in replacementDirect mounting on ML 2/3contractor Thermal over load relay, relay range 28-42 Amps suitable for fixing in existing panel complete all as specified and directed. (Note for item No 69 to 73:-Old U/s material demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrapin weight (KG) shall be taken into account and attach with RAR/F Bill)
110Supply only Electronic overload relay (Manual reset) relayrange 45-75amp suitable for direct mounting complete all as specified and directed.
111Supply only Electronic overload relay (Manual reset) relayrange 66-110 amp suitable for direct mounting complete all as specified and directed.
112Supply & Fix in replacement amp meter 96mmx96mm CT operated of range 0-100 as required complete all as specified and directed.
113Supply & Fix in replacement voltmeter 96mmx96mm 0-500 complete all as specified and directed.
114Supply & Fix in replacement voltmeter selector switch complete all as specified and directed.
115Supply & Fix in replacement ampmeter selector switch complete all as specified and directed. (Note for ser item No 74 to 79 : Old U/s material demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrapin weight (KG) shall be taken into account and attach with RAR/F Bill)
116Supply & FixLED indicator lamp in replacement complete all as specified and directed.
117Supply & Fix panel mounted ON/OFF push button with contact block in replacement complete all as specified and directed.
118Supply & Fix of CT 30/5Aor 50/5 or 100/5 in replacement complete all specified and directed.
119S&F in replacement copper bus bar rating 200 Amps 25/3mm including makingwhole suitable for panel with tape insulation of suitable colour in Phase RYB & neutral in Black colour complete all as specified and as directed. (Note for ser item No 83 & 84 : Old U/s aluminium & copper bus bar demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill)
120S&F in replacement aluminium bus bar rating 200 Amps 25/6 mm including makingwhole suitable for panel with tape insulation of suitable colour in Phase RYB & neutral in Black colour complete all as specified and as directed
121Supply & fixing LED bulb 9 Watt B 22 luman efficiency 90Im/w,white cool day lightcomplete all as specified and directed
122Material & labour for repair to existing earthing pit by dismentling unserviceable brick work after necessary excavation & earth work and construction of pit with new brick work using sub class B brick and plaster as required,replacing alternate layer of charcoal & salt as per electrical plate No-03 providing & connected earthing lead wire 4 mm dia of length as required by means of bolt,nuts and check nuts to make earthing funcional after testing complete all as specified and directed. (Note : Old U/s brick /bricks bat obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in volume in (CUM) shall be taken into account and attach with RAR/F Bill)
123Supply & Fixing of 1.5 Sqmm PVC insulated copper conductor, 3 core cable in surface/ recessed as required in replacement complete all as specified and directed
124Supply & Fixing of 25 Sqmm PVC insulated copper conductor, single core cable in surface/ recessed as required in replacement complete all as specified and directed
125Supply & Fixing of 35 Sqmm PVC insulated copper conductor, single core cable in surface/ recessed as required in replacement complete all as specified and directed. (Note for ser item No 87 to 89:- Old U/s copper conductor shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill)
126Supply and fixing in replacementelecrtonic timer type ST 100 for fixing in panel complete all as specified and as directed
127Supply and fixing in replacement single phase preventor VSP 2complete all as specified and directed
128Supply and fixing in replacement Switch piano,flush type,single pole one way for5 amps complete all as specified and directed
129Supply and fixing in replacement Switch piano,flush type,single pole one wayfor 15 amps complete all as specified and directed
130Supply and fixing in replacementswitch socket combination of rating 5 Amp flush type complete all as specified and directed
131Supply and fixing in replacementswitch socket combination of rating 16 Amp flush type complete all as specified and directed
132Supply and fixing in replacement socket outlet 2 in 1,3 pin of rating 5 Amp complete all as specified and directed
133Supply and fixing in replacement socket outlet 2 in 1,3 pin of rating 15 Amp complete all as specified and directed. (Note for item No 90 to 97:- Old U/s copper conductor shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV in weight (KG) shall be taken into account and attach with RAR/F Bill)
134Supply and fixing in replacement of MCCB 3 pole 415 volt adjustable type 63Amp with breaking capacity 25KA complete all as specified and directed
135Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 63Amp with breaking capacity 35KA complete all as specified and directed
136Supply and fixing in replacement of MCCB 3 pole 415 volt adjustable type 100Amp with breaking capacity 27KA complete all as specified and directed
137Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 100Amp with breaking capacity 25KA complete all as specified and directed
138Supply and fixing in replacement of MCCB 3 pole 415 volt adjustable type 200Amp with breaking capacity 36KA complete all as specified and directed
139Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 160 Amp with breaking capacity 36KA complete all as specified and directed
140Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 200 Amp with breaking capacity 36KA complete all as specified and directed
141Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 250 Amp with breaking capacity 36KA complete all as specified and directed
142Supply and fixing in replacement of MCCB 4 pole 415 volt adjustable type 320 Amp with breaking capacity 36 KA complete all as specified and directed
143Supply and fixing in replacement of MCCB 3 pole 415 volt adjustable type 400 Amp with breaking capacity 36 KA complete all as specified and directed
144Supply and fixing in replacement of MCCB 3 pole 415 volt adjustable type 630 Amp with breaking capacity 36 KA complete all as specified and directed. (Note for item No 98 to 108:- Old U/s MCCB shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
145Supply and fixing in replacement of MCB single pole adjustable type 6 Amp complete all as specified and directed
146Supply and fixing in replacement of MCB single pole adjustable type 10 Ampcomplete all as specified and directed
147Supply and fixing in replacement of MCB single pole adjustable type 16 Amp capacity 10 KA complete all as specified and directed
148Supply and fixing in replacement of MCB Double pole adjustable type 32 Amp capacity 10 KA complete all as specified and directed
149Supply and fixing in replacement of MCB Double pole adjustable type 40 Amp capacity 15 KA complete all as specified and directed
150Supply and fixing in replacement of MCB Three pole adjustable type 63 Amp capacity 15 KA complete all as specified and directed. (Note for item No 109 to 114:- Old U/s MCB shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
151Taking out existing rusted panel including all accessories compllete all as specified and directed. (Note :- Old unserviceable pannel with all accessories will be deposited in MES store Yrad and taken on charge as "EACH".
152Supply & fixing , install testing and commissioning of feeder pillar box ,outdoor type cubical shape,three phase, 4 wire, Al bus bar for phases and neutral made out of CRCA sheet 3.15 mm thick ,factory fabricated , CPRI approved , powder coated ,dust and vermin proof , provn for ventilation , angle iron frameand four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level , grouting properly ,and of suitable size to accomodate the items mentioned belowand having seperate compartment /chambers for cable gallery busbar, switch gear etc complete all as specified and directed comprising of following including necessary cable connections to the MCCBs, voltmeter, Ammeter and cable lugs etc and providing danger notice plate of size 300x200mmx3mm thick duly marked skull & bones with night glow highlighter fluorescent paint complete:-
153(a) Incoming : MCCB63 Amp 3 pole 18 KA with adjustable thermal and fixed magnetic release -01 No
154(b) Outgoing : MCCB40 Amp 3 pole 18 KA with adjustable thermal and fixed magnetic release -01 No
155(c) FASD StarterML 1.5 FASD with MS sheet enclosure-01 Nos
156(d) Analog time switch -01 No
157(e) Single phase preventer-01 No
158(f) Albus bar with PVC sleev suitable for 200 amps for phase & 200 Amp for neutral- 01Set.
159(g) Voltmeter,digital type 0- 500 volt,with selector switch - 01 set
160(h) Ammeter Digital type 0-100Amps, with selector switch and CT"-1set
161(j) Phase indicating lamps LED type ( red, yellow, blue) 01 set
162(Note:- (i) Contractor will be taken up approval of Accepting Officer for panel drawings before fabrication of Panel. (ii) Foundation & PCC work of LT panel will be executed in PCC (1:4:8) type D-2 using 40mm graded stone aggregate size as per site requirement and cost deemed included in quoted unit rate. (iii) Excavation and earth work shall be measured and paid seprately under respective items.
163Supply, install, commissioning and testing of LT panel board indoor type floor mounted of factory made powder coated made out of outside body of 3.15mm thick steel sheet and inside body 14 gauge steel sheet, locking arrangement, front side and rear side opening arrangement of suitable size, Incl mounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted or welded on floor. Aluminium bus bar TPN of 600 A for MCCB to all feeders to accommodate following items and providing danger notice plate of size 300x200mmx3mm thick duly marked skull & bones with night glow highlighter fluorescent paint complete:-
164(a) Incoming :- MCCB 250 Amp 50 KA 4 pole-01 no
165(b) Outgoing :- MCCB 100 amp 35/36 KA 3pole -03 nos
166(c) RYB indication for each incoming & outgoing supplies-01 set
167(d) Voltmeter, amp meter, with CT’s &selector switch-01 set
168(e) Termination of all cables with suitable size thimble and gland-1job
169(f) Fully Automatic star delta motor starter 50 hp (37.5KW) ,with single phase protuction , timer stardelta, relay AC-3, 415V,50 Hz, 3 Phase , relay range 30 to 50 AMP
170(g) Termination of all cables with suitable size thimble and gland-1 job
171(Note:- (i) Contractor will be taken up approval of Accepting Officer for panel drawings before fabrication of Panel. (ii) Foundation & PCC work of LT panelwill be execution PCC (1:4:8) type D-2 using 40mm graded stone aggregate size as per site requirement and cost deemed included in quoted unit rate. (iii) Excavation and earth work shall be measured and paid seprately under respective items.
172Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopysloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3.15mm thick CRCA sheet, factory made (CPRI approved manufacturer) powder coated painted as approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 350 Amps capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lampRYB, complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes,PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to in and including accomodate the following items and all as specified and directed by dismantling exisiting unserviceable LT panel and including providing danger notice plate of size 300x200mmx3mm thick duly marked skull & bones with night glow highlighter fluorescent paint complete:-
173(a) Incoming MCCB 200Amp rupturing capacity 36 KA, 4 Pole, 415volts, 50Hz - 01No (b) Outgoing MCCB"s100Amp rupturing capacity 25 KA 4 Pole, 415volts, 50Hz - 03 Nos (c) ML2 FASD (Heavy duty 35 HP relay range 13-21 Amp - 03 Nos (Note:- (i) Contractor will be taken up approval of Accepting Officer for panel drawing before fabrication of Panel. (ii) Foundation & PCC work of LT panel will be executed in PCC (1:4:8) type D-2 using 40mm graded stone aggregate, size as per site requirement and cost deemed included in quoted unit rate. (iii) Excavation and earth work shall be measured and paid seprately under respective items.
174Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopysloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3.15mm thick CRCA sheet, factory made (CPRI approved manufacturer) powder coated painted as approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 350 Amps capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lampRYB, complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes,PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to in and including accomodate the following items and all as specified and directed by dismantling exisiting unserviceable LT panel and including providing danger notice plate of size 300x200mmx3mm thick duly marked skull & bones with night glow highlighter fluorescent paint complete:-
175(a) Incoming MCCB 200Amp ruputuring capacity 35KA, 4Pole, 415Volts, 50Hz - 01 No (b) Outgoing MCCB"s 100Amp ruputuring capacity 25 KA 3 Pole, 415Volts, 50Hz - 02 Nos (c) ML2 FASD (Heavy duty 35 HP relay range 09-14 A - 01 No (d)ML4 FASD (Heavy duty 75 HP relay range 45-75A) - 01 No (Note:- (i) Contractor will be taken up approval of Accepting Officer for panel drawing before fabrication of Panel. (ii) Foundation & PCC work of LT panel will be executed in PCC (1:4:8) type D-2 using 40mm graded stone aggregate, size as per site requirement and cost deemed included in quoted unit rate. (iii) Excavation and earth work shall be measured and paid seprately under respective items.
176M&L for cutting of Hardstanding/road by mannual method upto 100mm deep for inserting GI pipefor cable protection complete including ready mix concreate and making good distrubed surface completeall as specified and as directed
177M&L complete for drilling hole underhard standing /road for laying ofpipe for protection of cable etc by means of mannual booky upto 200 mm and without disturbing the top surfaceand making good the disturbed surface if any complete all as specified and directed.
178M&L for painting to electrical equipments steel sections, rolling shutters etcwith two coat of synthetic enamel high glow paintIst gradeincluding preparation/cleaningof steel surfaces complete all as specified and directed.
179M&L for painting to electrical equipments steel sections, rolling shutters etcwith one coat of synthetic enamel high glow paintIst gradeincluding preparation/cleaningof steel surfaces complete all as specified and as directed.
180Supply & fixing in replacement Automatic Phase Sequence Correctorsuitable for 15 HP with sheet metal encloser including copper lugs etc complete all as specified and as directed
181Supply & fixing in replacement automatic Phase Sequence Correctorsuitable for 7.5 HP with sheet metal encloser including copper lugs etc complete all as specified and as directed. (Note for ser item No 124 & 125 :-Old U/s utomatic phase Sequence Corrector shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RV of iron scrap in weight (KG) shall be taken into account and attach with RAR/F Bill)
182Supply and fixing in replacement of Earthing complete with galvanised iron earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, connected to galvanised iron strip 32 x 6mm as earth continuityconductor connected to earth plate by means of GI light bolt nuts, check nuts and washers ofincluding providing earth wire protection pipe GI light grade 40mm bore from earth plate to main switch board/panel, watering pipe 40mm bore GI pipe medium grade with wire mesh and funnel at top, earth pit of PCC in 1:2:4 type B-1, with RCC cover 1:2:4 type B-0using MS TMT 8mm dia @ 150 c/c both way with suitable handle, angle iron frame made out of angle iron of size 40 x 40 x 4mm, including adequate quantity of charcoal dust and salt in alternate layers all around the earth plate, including excavation and earth work in any type of soil complete all as per electrical plate No 3 of SSR Part-I (2009) connected to earthing test point including test point made out of 40 x 3mm GI flat iron, all as specified and indicated including testing on completion, including taking down old unserviceable earthing, for machinery/ equipment installed at power house/sub station complete all as specified and directed.
183(Note:- (i) GI strip upto 7.5RM from earth point shall be deemed included in quoted unit rate. (ii) Old unserviceable material like steel plate & brick, angle shall be taken on charge iron scrap in "KG". (iii) Testing report of earthing will be passed by EIC and submitted alongwith RAR before payment.
184M & L for earthing in replacement GI plate60×60cm ×3.15mm thick electrode and 32x6mm galvanised strip as earthing leadthick buried directly in ground vertically to a depth not less than 2.25 mtr below normal ground level, connected to copper strip of size 25x4mm as earth lead by means of bolts, nuts and washers madeout of copper or tinned brass and protection GI pipe of 40mm dia all as specified and testing complete including earthwork, PCC chamber, RCC chamber cover with handle GI watering pipe 20mm dia, GI funnel with wire mesh, magnesium sulphate, salt, charcoal, lugs etc and method of earthing shall be as per plate No :3 of SSR part -I complete all as specified and directed. (Note:- (i) GI strip upto 7.5RM from earth point shall be deemed included in quoted unit rate. (ii) Old unserviceable material like steel plate & brick, angle shall be taken on charge iron scrap in "KG". (iii) Testing report of earthing will be passed by EIC and submitted alongwith RAR before payment.
185M & L for preparation of old painted surface of F/P box / LT Panel by removing all dirt, dust,etc with the help of blower and spray painting complete surface incl angle iron with one coat of synthetic enamel paint of approved colour over a coat of red oxide including writing of identificationetc all as directed by Engineer-in-Charge
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail