Tender For Repair/ Maint Of Water Supply Pumping And Distribution Pipe Lines Starter Panel Pump Motor Cleaning Of Water Storage Tank And Allied Works Under Age (I) Lansdowne, Dehradun-Uttarakhand

Military Engineer Services-MES has published Tender For Repair/ Maint Of Water Supply Pumping And Distribution Pipe Lines Starter Panel Pump Motor Cleaning Of Water Storage Tank And Allied Works Under Age (I) Lansdowne. Submission Date for this Tender is 22-04-2024. Tanks and Cylinders Tenders in Dehradun Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

43006932
Corrigendum : Tender For Repair/ Maint Of Water Supply Pumping And Distribution Pipe Lines Starter Panel Pump Motor Cleaning Of Water Storage Tank And Allied Works Under Age (I) Lansdowne
Open Tender
Indian
Uttarakhand
Dehradun
22-04-2024

Tender Details

Repair / Maint Of Water Supply Pumping And Distribution Pipe Lines Starter Panel Pump Motor Cleaning Of Water Storage Tank And Allied Works Under Age ( I ) Lansdowne

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-04-2024
2 17-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 22-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 42000.0 /-
Tender Value
INR 21 Lakhs /-

BOQ Items

Name of Work: REPAIR/ MAINT OF WATER SUPPLY PUMPING AND DISTRIBUTION PIPE LINES, STARTER PANEL, PUMP MOTOR, CLEANING OF WATER STORAGE TANK AND ALLIED WORKS UNDER AGE (I) LANSDOWNE.
Sl. No. Item Description
1Excavation in trenches in any type of soil n.exc 1.5 M wide and n.exc 1.5 M in depth for foundation laying of pipe etc n.exc 10 sqm on plan and n.exc 1.5 M in depth and getting out in any type of soil complete all as specified and as directed.
2Returning filling in including spreading levelling watering and well ramming in layers not.exc 25cm each layers complete all as specified and as directed.
3Removal of excavated material & surplus soil to a distance n.exc 50 M and depositing where directed at a level not exc 1.5 M above the starting point complete all as specified and as directed.
4Taking up or down existing GI pipe of following sizes from trenches / walls / roof / floor etc including connection and cleaning for refixing or removal from site and making good to distrubed area (surface of walls / floor etc) complete all as specified and as directed.
5GI Pipe 150 mm dia
6GI Pipe 100 mm dia
7GI Pipe 80 mm dia
8GI Pipe 40/50 mm dia
9GI Pipe25 mm dia
10GI Pipe 20 mm dia
11GI Pipe 15 mm dia
12S & FGI tubing, "medium grade" (ISI Marked)with screwed joints or welded joints all as per site requirement incl all fittings complete laid in trenches / on walls / on ceiling / roof etc incl necessary suitable size of MS clamps / saddling on walls / ceiling etc complete all as specified and directed at water supply distribution/pumping system Lansdowne of following bore of GI pipes :-
13GI Pipe 150 mm dia
14GI Pipe 100 mm dia
15GI Pipe 80 mm dia
16GI Pipe50 mm dia
17GI Pipe40 mm dia
18GI Pipe25 mm dia
19GI Pipe20 mm dia
20GI Pipe 15 mm dia
21S & FGI tubing, "Heavy duty" (ISI Marked)with screwed joints or welded joints all as per site requirement incl all fittings heavy duty complete laid in trenches / on walls / on ceiling / roof etc incl necessary suitable size of MS clamps / saddling on walls / ceiling etc complete all as specified and directed at water supply distribution/pumping system Lansdowne of following bore of GI pipes :-
22GI Pipe100 mm dia
23S & F in replacement GI fitting Bends, Socket , Union, Flange, Nipple etc (Heavy duty) of size 80 mm to 150 mm dia complete all as specified and directed. Note :- Site of fixing may be in any pumping installation/distribution system at Lansdowne.
24Disconnecting and taking down the existing unserviceable sluice valve 150 mm dia installed in position and removed from site and Supply, Fixing, testing and connecting cast iron sluice valve heavy duty double flanged, 150 mm dia PN 1.6 confirming to IS 14846: 2000 ISI marked with Stainless steel spindle and two nos of MS flange of 16mm thick, 8 holes with nuts and bolts packing materials complete including cutting the existing watermain for fixing cast iron sluice valve and jointing welding complete required at site of water supply installations/distribution system complete all as specified and directed.
25All as per Item No. 08 above but 100 mm dia complete all as specified and directed.
26All as per Item No. 08 above but 80 mm dia complete all as specified and directed.
27Disconnecting and taking down the existing unserviceable non return valves of cast iron and supply installing and testing of heavy duty cast iron non return valve PN 1.6 confirming IS 5312-1 (2004) ISI marked along with two Nos of heavy duty flange 16 mm thick, 8 hole suitable for 100 mm dia with all fixing accessories such as suitable size nut and bolts of 16 Nos, packing material of leather buffalo including cutting the existing water main of 100 mm dia for fixing the non return valve, welding jointing complete as per site requirement atwater supply installations/distribution system complete all as specified and directed.
28All as per Item No 11 above but 80 mm dia as per site requirement atwater supply installations complete all as specified and directed.
29Disconnecting and taking down the unserviceable gun metal gate valve 50 mm dia from installed position and removed from site and Supply, fixing and connecting Gun metal gate valves of size 50mm ISI marked confirmming to IS 778-1984with iron wheel head, screwed both ends for GI pipe complete all as specified and directed.
30All as per Ser No. 13 abovebut 40 mm diacomplete all as specified and directed .
31All as per Ser No. 13 above but 25 mm diacomplete all as specified and directed.
32All as per Ser No. 13 above but 20 mm diacomplete all as specified and directed.
33All as per Ser No. 13 above but 15 mm diacomplete all as specified and directed.
34M&L Construction of brick masonry valve chamber (as per standard drawing) of internal size 900x900x900mm with sub class "B" bricks in cement mortar 1:6 with 2mm thick MS sheet cover and angle iron frame made out of 40x40x6mm angle with locking arrangement duly painted with two coat of bitumen paint over a coat of red oxideprimer incl necessary earth work and excavating in any type of soil, returning filling in, removal of surplus soil complete incl 100 mm thick PCC 1:4:8 type B-2 (using 40 mm graded stone aggregate)in base concrete and 50 mm thick coping PCC 1:2:4 type B-0 (using 12.50 mm graded stone aggregate) over brick wall topincluding.two coats of snowcem rendering plastering work complete all as specified and directed.
35S&F in repair valve pit chamber top cover of size 900x900 mm made with 2mm thick MS sheet with supportingMS angle iron frame made out of 40x40x6mm and painting with two coats of bitumen paint over a coat of red oxidprimer and locking arrangment complete all as specified and directed.
36S&F in repairGI elbows/bend/unions/sockets/ tees/nipple with welding joint of 150mm water mains both ends for making leak proofbetween IInd lift to Stn HQ/SMT tank and any site of water supply installation all as specified and directed.Note:- The cost of fittings such as elbows/bend/unions/sockets/ tees/nipple etc shall be included in the unit rate quoted by the contractor.
37S&F in repair GI elbows/bend/unions/sockets/ tees/nipple with welding joint of 100mm/80mm water mains both endsfor making leak prooffrom Zero to IInd liftand oras per site requirement of water supply installation all as specified and directed. Note:- The cost of fittings such as elbows/bend/unions/sockets/ tees/nipple etc shall be included in the unit rate quoted by the contractor.
38S&F angle iron work for support of water pipeline by welding at scattered location complete all as specified and directed.
39M&L for walling of square rubble uncoursed well bonded, bedded and solidity hearted built in cement motor 1:6 for support for pipe line complete all as specified and directed.Note: Site of work is in hilly terrain which is not approachable by road
40M&L for cement concrete (1:4:8), type D2 ( using 40 mm graded stone aggregate) asin foundation, filling or mass concretecomplete all as specified and directed Note: Site of work is in hilly terrain which is not approachable by road
41Cutting the existing floor/ roads for laying of GI pipe line and making good the distrubed surface with PCC (1:2:4),type B1 (using 20 mm stone aggregate)complete all as specified and directed.
42S&F and fixing U-PVC pipe of size 75 mm bore SCH-40 including all pipe line fittings like elbow, socket plug hose clip adaptors cutting through walls floors and making good or laying in treches complete all as specified and directed.Note: Site of work is in hilly terrain which is not approachable by road
43S&F in repair cast iron foot valve, flanged end type confirming to IS-4038, ISI marked alongwith fixing accessories such as suitable size nut, bolts, washer & rubber gasket of following size complete all as per site requirement all as specified and directed :-
44100 mm dia
4580 mm dia
46Taking down non functional electric induction motor of any size andcapacity from water supply installation at zero/ Ist/ IInd stage pump house which are not approachable by road and 3rd stage/ Jharapani/ 2nd lift/ 15 LGLN pump house, decoupling motor from pump and cutting, removing burnt out copper winding and re-winding with super enamelled copper wire of suitable gauge conforming to IS 13730-0-6 (2012)and reassembling/couple back complete and transporting back to its original location and making necessary allingnment and electric connection all as directed at site.. Note :- Any other spare parts, if needed to be replaced shall be measured & paid as supply only separately under respective item of Sch "A"/ BOQ.
47Supply only following spare parts suitable for above mentioned items complete all as specified and directed.
48Stainless steel bush/shaft sleeve for suction/delivery for 75 HP centrifugal multistage horizontal pump with bore as per sample.
49Stainless steel bush/shaft sleeve for suction/delivery for 100 HP centrifugal multistage horizontal pump with bore as per sample.
50Cast steel bearing lock nut with washer as per sample for 100HP Pump.
51Roller bearing NU-207 for 100HP Pump.
52Bush type flexible cast iron flanged couplingwith finished bore and keyway as per sample for centrifugal Pump set.
53Rubber bush along with pin (high tensile nut bolt) as per sample for flexible coupling.
54S&F in repair water pressure guage of pressure 0-40 kg/sqcm with dial size of 100 mm dia along with ball valve of suitable size complete all as specified and directed.
55M&L in repair for fabrication and fixing of mild steel, plain, black sheet of thickness 1 mm for making coupling guard, cut to size, holes punched, including round headed screws, clout nails or rivets, bending or turning up, mitred angles, etc. as required complete all as specified and directed.
56Taking downCentrifugal Pump of capacity 100 HP from foundation of Pump set base frame of 3rd Stage Pump House water supply installation and Shifting to 2nd stage pump house water supply installtion and including refixing on new PCC (1:2:4) type B1 platform including new MS channel frame with inlet, outlet pipe connection, bush type flexible coupling for motor and pump complete all as specified and directed. Note: The work will be carried out at 2nd Stage and 3rd stage Pump House which is not connected by road.
57Taking down of Centrifugal Pump Set including electric induction motor of capacity 75 HP from foundation of Pump set base frame of Jharapani Pump House water supply installation and Shifting to 3rd stage pump house water supply installtion and including refixing on new PCC (1:2:4), type B1 platform including new MS channel frame with inlet, outlet pipe connection, bush type coupling for motor and pump, electric motor fan with fan blade of MS as per OEM recommendation complete all as specified and directed.
58Supply, laying & testing in repair of PVC insulated unarmoured and unsheathed Single core copper conductor flexible cable of following size complete all as specifiedand directed :-
5925 Sqmm Cable
6035 Sqmm Cable
61S&F in repair electronic star delta timer 3-30 seconds type ST100,160-500Volts, 50Hz complete all as specified and directed.
62S&F in repair Power Contactor 95 Amps complete all as specified and directed.
63S&F in repair auxiliary contact block side mounting with 1 No + 1 NC commplete all as speciffied and directed.
64S&F in repair motor protection relay D2MPR commplete all as speciffied and directed.
65S&F in repair Phase failure relay with under and over voltage settings complete all as specified and directed.
66M&L for cleaning of semi UG Sump of following capacity after emptying the sump with help of Pump, removing all mud, waste etc complete, scrubbing the entire sump inside with wire brush, washing the entire sump from inside with water and subsequently with bleaching powder solution and painting inside with two coats of lime washand writing date of cleaning complete all as specfied & directed :- Note : Date of cleaning shall be painted with white synthetic enamel paint after making a block of black paint on sump all as directed.
6716 Lakh gallon capacity
687.5lakhs gallon capacity
694.5lakhs gallon capacity
703 Lakh/2.5lakhs gallon capacity
712 Lakh/ 1.5Lakh/ 1.4 Lakhs gallon capacity
721 Lakhs gallon capacity
7350000 /45000/40000 gallon capacity water storage tank
7410000 gallon capacity water storage tank
75M&L for Collecting water sample fromwater supply installation of lansdowne and carry out water quality test (pH, TDS, Turbidity, Alkalinity, Total hardness, Fluoride, nitrate, Sulfate, RFC, Colour, Conductivity, Chloride, odour, Total coliform, E.Coli) from recognised government organisation complete all as specified and directed.
76M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground. (earth pit not less than 2.25 mtr depth below ground levelat any type of strata ) with top edge of the earth plate not less than 1.5mtr below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all around the plate. connected by 32x6 mm GI strip as earth lead by means of brass nuts and bolt,thimbles check nuts, washers including concrete chamber of PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320x320x80mm size (1:2:4) Type B1 using 20mm graded stone aggregate rainforced with XPM all as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified including and provision of GI strip upto 7.5 mtrs long with 40 mm dia medium grade Gi pipe protection and watering pipe of GI 20 mm bore, medium grade, including all exavation and earth work and connecting the earthing strip to panel, including testing on completion complete all as specified and directed.. Note:- (i) RCC pit cover shall be precast of RCC(1:2:4) type B1, 80mm thick rainforced with XPM weighting not less than 4kg/sqm in lieu of CI cover. (ii) Cost of additional GI strip more than 7.5 mtrs will be measured and paid seperately under relevant items.
77M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required but 32x06mm galvanised iron strip incl taking down old strip complete all as specifed and directed.
78M&L for brick work with sub class "B" old size bricks straight or curved on plan exc 6.00 M mean radius built in cement mortar 1:6 for Pipe Line Support complete all as specified and directed.
79M&L for rendering 10 mm thick cement plaster (1:6) on external surfaces of brick wall/concrete surface complete all as specified and directed.
80Supply, installing, testing and commissioning in replacement factory made and tested Indoor type Phase Sequence Corrector of capacity 200 Amps , 3 Phase 4 Wire, 415 volts, 50 Hz, wall mounted. The Phase Sequence Corrector shall be dust and vermin proof, protection class (IP-42) and made of 2.00 mm thick CRCA mild steel sheet, front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 Sqmm complete all as specified and directed.Note:All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
811. Motor Protection Automation Phase Sequence Corrector single phase preventer with facility to change over from automatic to manual with Over Load protection for contactors upto 200 Amps motor etc Protection:-Avoid damages during Phase sequence changes or reversal. • The Sequence Corrector will switch off, during the Single Phasing or Imbalance voltage occur & later, Auto-reset after restoration. • Quartz Timer One dial daily for automatic operation of motor. • No break downs of Three phase system due to the change in sequence. • Bye Pass Selector switch in case of controller Faulty. • Surge Protection Device 3 Phase 40kA 240/415 V AC= 01 No.
82The panel manufacturer should have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-42 2. CPRI Certification Short Circuit withstand strenght should be 50kArms for 1.0 Sec 3. CPRI Certification Rated current for short circuit not less than 4000A with rated insulation voltage 660V 4. ISO 9001 CERTIFIED
83Supply, installing, testing and commissioning in replcement factory made and tested Indoor type Phase Sequence Corrector of capacity 400 Amps , 3 Phase 4 Wire, 415 volts, 50 Hz, wall mounted. The Phase Sequence Corrector shall be dust and vermin proof, protection class (IP-42) and made of 2.00 mm thick CRCA mild steel sheet, front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete all as specified and directed.Note::All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
841. Motor Protection Automation Phase Sequence Corrector single phase preventer with facility to change over from automatic to manual with Over Load protection for contactors upto 400 Amps motor etc Protection:-Avoid damages during Phase sequence changes or reversal. • The Sequence Corrector will switch off, during the Single Phasing or Imbalance voltage occur & later, Auto-reset after restoration. • Quartz Timer One dial daily for automatic operation of motor. • No break downs of Three phase system due to the change in sequence. • Bye Pass Selector switch in case of controller Faulty. • Surge Protection Device 3 Phase 40kA 240/415 V AC= 01 No.
85The panel manufacturer should have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-42 2. CPRI Certification Short Circuit withstand strenght should be 50kArms for 1.0 Sec 3. CPRI Certification Rated current for short circuit not less than 4000A with rated insulation voltage 660V 4. ISO 9001 CERTIFIED
86Disconnecting and taking down the existing unserviceable butterfly valves of cast iron and S&Ftesting and connecting cast iron butterfly valve lever operated heavy duty double flanged, 100 mm dia PN 1.0 confirming to IS 13095 ISI marked with Stainless steel stem and disc and two nos of MS flange of 16mm thick, 4 holes with nuts and bolts packing materials complete including cutting the existing watermain for fixing cast iron butterfly valve and jointing welding complete required at site of water supply installations complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy