Tender For Electrification Work Of 4 New Trades Under C.I.T.S. Training And Workshop Building Under Tata Technology Ltd In State Staff Training And Research Center, Aliganj, Lucknow, aliganj-Uttar Pradesh

Uttar Pradesh Housing And Development Board-UPAVP has published Tender For Electrification Work Of 4 New Trades Under C.I.T.S. Training And Workshop Building Under Tata Technology Ltd In State Staff Training And Research Center, Aliganj, Lucknow. Submission Date for this Tender is 10-06-2024. Electrification Work Tenders in aliganj Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43001296
Corrigendum : Tender For Electrification Work Of 4 New Trades Under C.I.T.S. Training And Workshop Building Under Tata Technology Ltd In State Staff Training And Research Center, Aliganj, Lucknow
Open Tender
Indian
Uttar Pradesh
aliganj
10-06-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Electrification Work Of 4 New Trades Under C.I.T.S. Training And Workshop Building Under Tata Technology Ltd In State Staff Training And Research Center, Aliganj, Lucknow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Mar-2024 Corrigendum no. 333 Date 10-06-2024

Key Value

Document Fees
INR 1770 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

Attachment

FileName File Description File Size
0fc4eb01-22d1-45f4-918f-07f32f382e60.html Tender Notice 0 KB
BIDDOCUMENTS.pdf Tender Document 0 KB
BOQ_1588439.xls Tender Document 0 KB
GPW9.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: Electrification work of 4 New Trades under C.I.T.S. Training and workshop Building under Tata Technology Ltd in State Staff Training and Research Center, Aliganj, Lucknow.
Sl. No. Item Description
1Supply, erection, testing and commissioning of 11 KV Double pole structure for providing 1 No. 11KV,200A GOS in accordance with IE rules, & local authority specification and drawings and comprising of the following.- 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc with 2 Nos. 3m GI Pipe for vertical cable., 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection., 1 set 11KV Insulator complete with spindles & hardware complete as required., 1 No. 11KV 400A TP Gang operated Air break switches complete with 25mm dia GI pipe operating machanism, handle & locking arrangement.1 set of 3 nos.11KV single pole drop out fuse complete with barrel fuses, and mounting arrangement., 1 set (3 nos.) 11KV lightning arrestor and connecting to all phases., 1 No. 150 mm dia GI pipe class "B" (for XLPE cable protection) as required., 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required (for GO & DO & LA), 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices.
2Supply and laying of3 core standered aluminium conductor XLPE(Cross linked polyethylene)insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connectedwith earth conductor by clamps etc. 70 sqmm 3 core Make : Havells/KEI/Polycab/Gloster
3Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 70Sqmm 3 core Make : Raychem/3M
4Providing, erecting, testing & commissioning approved make oil immersed naturally ONAN cooled, double wound, core type outdoor copper wound 11 kV/ 433 Volts Step Down Transformer of following capacities operating on 3 phase, 50 Hz 4 wire & neutral earthed system continuously rated for a full temperature rise in oil following capacities operating on 3 phase, 50 Hz 4 wire & neutral earthed and Off Load Tap Changer continuously rated for a full temperature rise in oil not exceeding 40 deg. C at maximum ambient temp. Of 50 deg. C complete with necessary radiator first filling of new transformer oil & standard fitting as below complying with I.S. 1180 LEVEL 2 standards OFF load tap changing range steps -10% to 5% on H.V in steps of 2.50% .and L.V. for variation should be provided The H.V. shall be connected delta & secondary with star connection. The transformer should have cable-end boxes on H.T. side & on L.T. side suitable for cables and outdoor type end termination as per requirement complete with test certificates from manufacturers. Losses As per IS 1180 LEVEL-2.
5Conservator with plain oil level gauge and oil drain plug 1nos., Top filter valve 1 Nos., Bottom filter-Cum-drain valve 1Nos.., Rating and diagram plate 1nos., Earthing Terminals 2Nos., ThermoM pockets 1Nos., Lifting Lugs 2/4 Nos., Air release plug 2/4 Nos., Bi-directional rollers 4Nos., Jacking pads 1Nos., Pressure release valve 1Nos., Separate Bare LV neutral 433V ,Detachable/Fixed type radiators 1Nos.,Magnet Oil levelgauge, Oil temperature indicator 1Nos., Winding temperature indicator 1Nos., Marshaling Box single window 1No., Double flot buchholz"s relay with alarm and trip contact. Copper Wound 250KVA 11/0.433KVMake : Siemens/ Kirloskar/Schmeider/Voltamp/Areva
6Design, Manufacturing, Supply, Commissioning & Testing of Main LT Panel. The panel will be totally enclosed type with, free standing, floor mounted, indoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multiM, indication lamps, CT"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness. The Main LT Panel shall use all breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. All having following incomming and outgoing Air Circuit Breakers, FSU"s as per the drawing and specification. No. incoming breaker will have microprocessor based releases and all outgoing breaker will have minimum electrostatic releases over 250A & thermal magnetic release below 250A. The Panel will be made as per detailed specifications & drawings forming part of this document. Fault level of panel shall be 35 MVA. INCOMMER : 500Amp. 25KA FP With S/C, U/V, E/F Protection MCCB 2no. (From Transformer) BUSCOUPLER : 500Amp. 25KA FP With S/C, U/V, E/F Protection MCCB 1no. (From Transformer)BUSBARS : 2 Nos. 630 Amp FP busbars of aluminium alloy as per SLD. OUTGOING : 200Amp. 25KA TP MCCB 2 No. (APFC Panel) OUTGOING : 250Amp. 25KA FP MCCB 4 No. (TATA+Conference Hall+Girls Hostel+Spare)OUTGOING : 63Amp. 16KA FP MCCB5 No. (Ex. Light+Pl+Spare) INSTRUMENTS : 1 sets of multifunction M with paraM current,voltage,KWH,KVAH,Power factor on incoming from transformers.1 Sets of phase indicating lights (RYB) with protection fuses (one set for No. incoming breaker).1 Sets breaker "ON" & "OFF" indicating lamp (one set for No. incoming breaker).2 Sets auto trip indicating lamp . Make : L&T/ABB/Schneider/Siemens
7100KVAR CAPACITOR PANEL INCOMING : 1 Nos. 200 Amp TP MCCB 25KA BUSBARS : 1 Nos. 250 Amp TPN busbars of aluminium alloy as per SLD. OUTGOING 12 stepped Automatic Power Factor Correction relay (APFC relay).,,4 Nos. 32 Amp TP MCB. 4 Nos. 25 Amp TP MCB.,4 Nos. capacitor duty contactor (one for No. 15KVARcapacitor unit)., 4 Nos. capacitor duty contactor (one for No. 10KVARcapacitor unit).,4 Nos. 15 KVARsuper heavy duty mix dielectric low loss Capacitor suitable for non leniar loads upto 20% ,4 Nos. 10 KVARsuper heavy duty mix dielectric low loss Capacitor suitable for non leniar loads upto 20% , 8 sets of push button stations Red and Green for manual operation of capacitor units with auto/manual selector switches., 1 No. Indicating lamp for No. capacitor unit to indicate that the unit is "ON"., 1 No. Toggle switch for changing automatic to manual operation of capacitor units., Power factor M., 1 No. 0 to 200 Amp amM with selector switch & C.T"s., 1 No. 0 to 500 Volts voltMwith selector switch. Make : L&T/ABB/ Schneider/ Siemens
8Supplyandlayingof aluminiumconductorPVCinsulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Make : KEI/Polycab/Havells/Gloster
93.5 core 150 Sqmm Cable
103.5 core 300 Sqmm Cable
11Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Make : Dowells/Gripwell/Camel/Hex
123.5 core 150 Sqmm Cable
133.5 core 300 Sqmm Cable
14Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
15Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
16Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
17Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
18Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
19Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 300mm Dia
20S/F of cable root marker
21Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work.
22Supply and fixing danger board fabricated from 10 gauge M.S. Sheet as per I.E. Rules.
23Supply and fixing of 2 metres high cage fabricated with 3mm thick expanded metal fixed on 50mm x 50mm x 6mm angle iron frame having vertical members spaced at 1 to 1.25 mts and horizontal members spaced at 1 mt. The vertical members shall be grouted in floor and horizontal members in the wall to a depth of 300mm with ends forked.The cage shall have 2000mm x 1000mm size one leaf door with locking device having door frame fabricated with 35mm x 35mm x 6mm angle iron and 3mm expanded metal duly fixed with the cage member with hinges etc. The cage shall be painted with red oxide primer and synthetic enamel paint. The job includes all materials, labour, T&P etc. for proper completion ofwork.
2411KV Pole mounted CT/PT CTR 10/5
253PH 4WStatic TVM 11KV