| 1 | Building workSCHEDULE \"A\" PART-IConstruction of block of DG Set Room Single Storey including Duty Room, Complete all as Specified and shown on drawings(Refer Srl Page No 17 of Sch A Part-I ) |
| 2 | Internal Water SupplySCHEDULE \"A\" PART-II Lump sum price worked out by the Contractor for “Internal Water Supply”as listed in Schedule ‘A’Part- II |
| 3 | Internal ElectrificationSCHEDULE \"A\" PART-III Sec-I Lump sum price worked out by the Contractor for “Internal Electrification”as listed in Schedule ‘A’Part- III Sec-I |
| 4 | Internal ElectrificationSCHEDULE \"A\" PART-III Sec-II SCHEDULE \"A\" PART-III Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 5 | Supply & Fix CFL 1x18 W having PF not less than 0.8 |
| 6 | Supply & Fix MCB SP 240 V 50 Hz 10 KA of rating (6-32A) of make havells cat Part No DHMCCSNF006-032 or equivalent make as mentioned in Appx \"E\" |
| 7 | Supply & Fix MCB SP 240 V 50 Hz 10 KA of rating (6-32A) of make havells cat Part No DHMCCSP06-32 or equivalent make as mentioned in Appx E |
| 8 | Street light luminarie in single PC deep drawn aluminium housing with side reflector and acrylic cover suitable for 85W CFL retrofit type incl 85 W CFL complete with all accessories prewired incl provn of bracket of 40 MM bore GI light grade pipe made to shape overall length 1.5 Mtr with clamp of FI 40x6 MM for fixing street llight fittings and providing PVC insulated copper conductor of size 2.5 Sq mm for making connnection to light fittings from junction box complete all as directed. Make havells Cat Part No. LHRC 13185099 or equivalent make as mentioned in Appx E |
| 9 | Point wiring with 1.5 Sq mm copper conductor FRLS (Multi strand) PVC ISI Mark unsheathed cable in and incl concealed PVC conduits, medium grade, ISI mark not less than 20 MM dia with all fittings/ accessories incl PVC insulated ISI mark unsheathed 1.5 Sq mm copper multi stranded conductor FRLS as earth wire connected to common earth dolly and incl sunken box cast iron/ pressed steel turminal boxes from 2 mm thick sheet of suitable sizes for mounting of switches, sockets, fan regulator, light fittings etc covered with 3 mm thick plastic laminated sheet (Make Hylum or equivalent ISI marked) complete all as specified and directed.Note :- Proper colour coding should be adopted for phase, neutral, earth and halves. |
| 10 | (a)One light point or fan point independent controlled by one way switch |
| 11 | (b) One three pin socket outlet, 5Amps independent |
| 12 | Point wiring with 2.5 Sq mm copper conductor FRLS (Multi strand) PVC ISI Mark unsheathed cable in and incl concealed PVC conduits, medium grade, ISI mark not less than 20 MM dia with all fittings/ accessories incl PVC insulated ISI mark unsheathed 2.5 Sq mm copper multi stranded conductor FRLS as earth wire connected to common earth dolly and incl sunken box cast iron/ pressed steel turminal boxes from 2 mm thick sheet of suitable sizes for mounting of switches, sockets, fan regulator, light fittings etc covered with 3 mm thick plastic laminatedfor one multi purpose two in one 5 and 15 amp socket on independent board complete all as specified and directed.Note :- Proper colour coding should be adopted for phase, neutral and earth and halves. |
| 13 | Socket outlet two in one, 3 pin and 2 pin 5 amp flush type all as specified |
| 14 | Socket outlet two in one, 6 pin and 5& 15 amp flush type all as specified |
| 15 | Sub Total |
| 16 | External ElectrificationSCHEDULE \"A\" PART-IV Sec-ILump sum price worked out by the Contractor for “External Electrification”as listed in Schedule ‘A’Part- IV Sec- I(Refer Srl Page No 26) |
| 17 | External ElectrificationSCHEDULE \"A\" PART-IV Sec-IISCHEDULE \"A\" PART-IV (Sec-II) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 18 | Laying, jointing and testing cable XLPE insulated, armoured heavy duty electric cable with aluminum conductor, 1100 volts grade laid in trenches, ducts, drawn through GI pipe, across the road/path/ drains/along poles/ walls/ floors/ equipment etc of following sizes (Cable will be issued under Schedule \"B\" free for fixing :- |
| 19 | (a) Cross section area 25 Sqmm 3 1/2 Core |
| 20 | (b) Cross section area 35 Sqmm 3 1/2 Core |
| 21 | (c) Cross section area 50 Sqmm 3 1/2 Core |
| 22 | (d) Cross section area 70 Sqmm 3 1/2 Core |
| 23 | (e) Cross section area 95 Sqmm 3 1/2 Core |
| 24 | (f) Cross section area 120 Sqmm 3 1/2 Core |
| 25 | (g) Cross section area 240 Sqmm 3 1/2 Core |
| 26 | (h) ditto but PVC insulated 16 Sqmm, 2 Core |
| 27 | Note :-Excavation and Earth work for above items shall be measured and paid under item Schedule A Part-V |
| 28 | Fixing only non integral asymmetric flood light 400 watt luminarie type including cast aluminium housing complete with external CC box (IP65) and lamp complete all as specified.Make Philips Cat Part No RVP50172XSONT400W or equivalent make as mentioned in Appx E. |
| 29 | Fixing, installation, testing and commissioning LT feeder pillar box type factory made, dust and vermin proof, out door type mounted on frame of MS angle iron 40 mm x 40 mm x6 mm, 45 cm above the ground level duly supported with MS angle iron 50 mm x50 mm x 6mm thick in PCC foundation of PCC 1:2:3, type B-1 using 20 mm graded stone aggregate, with openable shutter in front having, powdercoated including aluminium bus bar (4Nos) of size 200 A of suitable length with coloured insulated hot tape (cable connection with through cable gland of suitable size) mounted on porcelain insulators in including wiring to panel with suitable size PVC insulated and sheathed copper cable and comprising of the following :-(a) MCCB 100 Amps, 4 pole, 25KA-01 (Incoming).(b) MCB, SPN, 32 Amps - 06 (for outgoing)(c) MCB TPN, 32 Amps, 03 Nos (outgoing)(d) RYB neon indicatinglamp-01 Nos(e) Voltmeter digital type with inbuilt selector switch 0-500 V-01 Nos(f) Ammeter digital type with inbuilt selector switch 0-100 Amp flush mounted square pattern and set of threee CTs of suitable rating with all the outgoing feeders. |
| 30 | Fixing , installations, testing and commissioning LT feeder pillar box type factory made, dust and vermin proof, out door type mounted on frame of MS angle iron 40mm x 40 mm x 6 mm, 45 cm above the ground level duly supported with MS angle iron 50mm x 50 mm x 6 mm thick in PCC foundation of PCC 1:2:3, type B-1 using 20 mm graded stone agrregate, with openable shutter in front having, powder coated including aluminium bus bar (4Nos) of size 200 A of suitable length with coloured insulated hot tape (calbe connection with through cable gland of suitable size) mounted on procelain insulators in including wiring to panel with suitable size PVC insulated and sheathed copper cable and comprising of the following :-(a) MCCB 200 Amps, 4 pole 25 KA-01 (Incoming)(b) MCCB, 4 P , 63 Amps, 15 KA-04 Nos (for Outgoing)(c) RYB neon indicating lamp-01 No.(d) Voltmeter digital type with inbuilt selector switch 0-500 V-01 Nos 415V, 50 Htz fiush mounted square pattern.(e) Ammeter digital type with inbuilt selector switch 0-200 Amp flsh mounted square pattern and set of three CTs of suitable rating with all the outgoing feeders. |
| 31 | Fixing, installation testing and commissioning factory made LT panel,dust and vermin proof,indoor type floor mounted fabricated with 2.00 mm thick CRCA sheet on angle iron (50 mm X 50 mm X 6 mm) frame complete with open able shutters in front having proper locking arrangement, powder coated including aluminium bus bar (4 Nos) of size 200 A of suitable length with coloured insulated hot tape (cable connection with through cable gland of suitable size ) mounted on porcelain insulators in inclding wiring to penel with suitable size PVC insutated and sheathed copper cable and comprising of the following:-(a) MCCB 400 Amps, 4 pole, 35 KA-01 (Incoming) (b) MCCB, 4P, 200 Amps, 25 KA-02 Nos (for outgoing)(c) MCCB, 4 P, 100 Amps, 25 KA-04 Nos (for outgoing)(d) RYB neon indicating lamp - 01 No.(e) Voltmeter digital type iwth inbuilt selector switch 0-500 V V-01 Nos 415V, 50 Htz flush mounted square pattern.(f) Ammeter digital type with inbuilt selector switch 0-400 Amp flsh mounted square pattern and set of three CTs of suitable rating with all the outgoing feeders.(g) Online change over switch of rating 400 A. |
| 32 | Earthing complete with galvanished steel earth plate electrode 600 mm x 600 mm thickness not less than 6 mm burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl galvanished earth lead using galvanised iron strip 32mmx6mm size by means of nuts and bolts, check nuts and washers of galvanished incl PCC pit of 1:2:4 tope B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6 mm dia bar handle, excavation and earth work in any type or soil, charcoal dust, salt, light grade GI watering pipe 20 mm dia with funnel and wire mesh and medium grade GI protection pipe of 40 mm bore from top edge of earth plate upto main distribution board max 7.5 metre) complete all to as shown in electrical plate no 5 of MES sch 1991(Part I) connected main switch board all as specified and testing on completion. |
| 33 | Earthing complete with galvanished steel earth plate electrode 600 mm x 600 mm thickness not less than 6 mm burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl galvanished earth wire of size 4 mm by means of nuts & bolts check nuts and washers of galvanished incl PCC pit of 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6 mm dia bar handle excavation and earth work in any type of soil charcol dust, salt light grade GI watering pipe 20 mm dia with funnel and wire mesh and medium grade GI protection pipe of 15 mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate no 5 of MES sch 1991 (Part1) connected main switch board all as specified and testing on completion. |
| 34 | Supply, installation, testing and commissioning of diesel engine/driven generating set of capacity 320 KVA/256 KW, 0.8 power factor at NTP, mounted on common base frame alongwith sound proof enclosure (acoustic enclosure ), 1500 RPM, with silencer pipe independently supported from engine to outside upto 1 mtr, AVM padded foundation as per manufacture\"s design, cold starting kit, battery start with suitable size cable for connection from DG set to panel board (DG Set shall be capable of operating in temperature range of (-35) degree centigrade to (+35) degree centigrade) complete with and incl the following :-(A) PRIME MOVER :- Vertical diesel engine of suitable capacity water cooled (Radiator mounted) closed circuit as per BS 649 or IS-10002 direct injection type turbo charged electric starting system having rated speed 1500 RPM. The DG set shall be capable of running 24 hours continuosly with 10% over loading for one hour in every 12 hours as per BS 5514/- BS 649. Engine shall be equipped with all standard fittings as per manufacturer recommedation and mounted on common base frame with following accessories as per manufacturer design:-(i) RPM cum Hrs meter(ii) Battery charging ammeter(iii) Ignition key/ starting with push button switch(iv) Lubricating oil pressure gauge(v) A-1 governor controlling(vi) Oil temperature gauge(vii) Water temperature gauge(viii) Lubricating oil coolant heater to avoid freezing (ix) 24V-02 Nos (01 for standby) by starting equipment comprising with the following:- |
| 35 | (aa) Two Nos 24V 180AH maintenance free batteries. Make: Exide/Standard(ab) Battery charging alternator with inbuilt regulator(ac) Starter motor of suitable capacity(ad) Battery leads (copper cable) of suitable size with brass thimbles and terminal(B) ALTERNATOR:- Alternator rating 320KVA/256KW 03 phase 50 cycles, 415 Volts 04 wires supply at NTP 0.8 power factor @ 1500 RPM, self-excited, self-regulated mounted on a strong fabricated steel frame suitable for mouting on permanent foundation to be coupled with the above engine. The alternator shall be confirming to BS-2613 or IS-4722 (C) ACCOUSTIC ENCLOSURE:- Set shall be fitted with acoustic enclousure suitable for 320 KVA as per manufacturer instruction and confiming to CP CB norms acoustic enclosure shall comply with revised noise limit for DG set vide GSR-371 (E) dt 17 May 2002 and its amendments under environment (protection) act 1996 issued by Min of Environment and forest.(D) CONTROL PANEL: Alternator control panel alongwith self regulated AVR system inbuilt, cubical type with internal copper wiring for 320 KVA alternator, 415 V 3 phases, 04 wire, 50 Hz, fabricated out of 2 mm thick CRCA sheet painted internally and externally with 02 coats of synthetic enamel paint over 01 coat of primer including following accessories as per manufacturer design:-(i) Digital Voltmeter 0-500 amp of size 96 mm x 96 mm AC with flush type selector switch, Make:- AE/ Legrand(ii) Digital ammeter 0-500 amp of size 96 mm x 96 mm (3 phase/ 1 phase) AX with flush type selector switch(iii) Frequency meter digital type built in |
| 36 | (iv) MCCB 400 Amps, 4 pole 36 KA-01 (for incoming) as recommended by manufacturer(v) Set of copper bus bar for suitable capacity(vi) Set of indicator lamps LED type (Red, Yellow, Blue)(vii) Set of instrument fuses(viii) Digital energy meter having facility to show KWH, KW, KVA, power factor reading etc(ix) Running hour meter(E) OTHER FITTINGS:-(i) Battery charger having electric circuit consisting of triodes, rectifier, capacitor and resistor etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to the battery charger through control panel are electric power point(F) FUEL TANK: of suitable capacity as per manufacturer instructions capable to store 12 hrs running of DG set, as per manufacturer design, with all pipes conecting upto fuel pumps including oil level indicating gauge in ltrs, drain and air vent plug etc.(iii) The contractor shall supply 02 yrs maint spare for the above Genr set :-(aa) Fuel filter - 12 Nos(ab) Lub Oil filter- 12 Nos(ac) Element air cleaner outer- 06 Nos(ad) Element air cleaner Inner- 06 Nos(ae) V-Belt - 02 Sets(af)Filter lubricant oil by pass- 02 Nos |
| 37 | Fixing only Junction Box of size 30cm x 25 cm on the pole or wall fabricated out of MS sheet of 3.4 mm thick on angle iron (50x50x6mm) frame complete with open able shutters in front and rear having proper locking arrangement and bolted,spray painted internally and externally with two coats of syntheric enamel paint over a coat of red oxide primer including copper bus bar (02 Nos) of size 25x3 mm of suitable length mounted on suitable insulator indluding one No of MCB SPN 6 Amps complete all as directed. |
| 38 | Junction Box of size 30cm x 25 cm on the pole or wall fabricated out of MS sheet of 3.4 mm thick on angle iron (50x50x6mm) frame complete with open able shutters in front and rear having proper locking arrangement and bolted,spray painted internally and externally with two coats of syntheric enamel paint over a coat of red oxide primer including copper bus bar (02 Nos) of size 25x3 mm of suitable length mounted on suitable insulator indluding one No of MCB SPN 6 Amps complete all as directed. |
| 39 | Street light fitting HPSV 70 watts, single piece cast aluminium housing (IP 65) with POT optics reflector including sodium vapour lamp 70 watt complete with all accessories prewired indluding provision of bracket of 40 mm bore GI light grade pipe made to shape over all length 1.50 meter with clamps of FI 40x6 mm for fixing street light fittings and providing PVC insulated conductor cable of suitable size of making connection to light fittings from junction box complete all as directed.Cat Part No LHRY 28170D99 of Havels or equivalent make as mentioned in Appx \"E\" |
| 40 | Supply, install testing and commisioning electric siren horizontal double munting 3 phase 440/400 volts 286 RPM, 50 Hz, AO supplied along with 1 HP motor suitable for audible range of 1.5 KM and PVC insulated ISI marked copper cable from siren to starter including suitable manual operated starter etc as sepcified. |
| 41 | Sub Total |
| 42 | Excavation and Earth work for Sch A Part-IV and Site ClearanceSCHEDULE \"A\" PART-V)Lump sum price worked out by the Contractor for “Excavation and Earth work for Sch A Part-IV and Site Clearance”as listed in Schedule ‘A’Part-V |
| 43 | Defective WorkSCHEDULE \"A\" PART-VI)SCHEDULE \"A\" PART-VI) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 44 | Demolition of Unreinforced cement Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level), complete all as specified and as directed by Engineer-in-charge. |
| 45 | M&L 50 mm thick plain Cement concrete type B-1, 1:2:4 (using 20mm graded crushed stone aggregate) finished even and smooth without using extra cement, complete all as specified and as directed by Engineer-in-charge. |
| 46 | Dismantling wall and ceiling board of any description including cover fillets, complete all as specified and as directed by Engineer-in-charge. |
| 47 | M&L 12mm thick prelaminated particle board interior grade both side backing, complete all as specified and as directed by Engineer-in-charge. |
| 48 | M&L 50 mm thick plain Cement concrete type C-1, 1:3:6 (using 20mm graded crushed stone aggregate) finished even and smooth without using extra cement, complete all as specified and as directed by Engineer-in-charge. |
| 49 | Dismantling floor hearth wall tiling including cement mortor bedding (but not backing), complete all as specified and as directed by Engineer-in-charge. |
| 50 | M&L 7mm thick non skid ceramic tiles 300mmx300mm over 15mm thick cement mortor bed in CM 1:4, complete all as specified and directed by Engineer-in-charge. |
| 51 | Taking down cement plaster on brick or concrete wall including racking out joints hacking for key scrubbing down with water,complete all as specified and directed by Engineer-in-charge. |
| 52 | M & L 10mm thick cement plaster in cement mortar 1:6 finished even and smooth without using extra cement,complete all as specified and directed by Engineer-in-charge. |
| 53 | Fixing only in repaircable XLPE insulated, armoured heavy duty electric cable with aluminum conductor, 1100 volts grade laid in trenches, ducts, drawn through GI pipe, across the road/path/ drains/along poles/ walls/ floors/ equipment etc ofsize Cross section area 50 Sqmm 3 1/2 Core Note :- Cable shall be issued under Sch BOld cable to be taken on charge by GE |
| 54 | Fixing only in repair cable PVC insulated, armoured heavy duty electric cable with aluminum conductor, 1100 volts grade laid in trenches, ducts, drawn through GI pipe, across the road/path/ drains/along poles/ walls/ floors/ equipment etc ofsize Cross section area 16 Sqmm 2 Core Note :- Cable shall be issued under Sch BOld cable to be taken on charge by GE |
| 55 | Supply and fixingLED street light fitting 70 watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66/65 protection com plete. |
| 56 | Excavation in trenchesnot exceeding 1.5m in depthdeep for laying of pipe, cable, foundation of electric pole etc and getting out in hard soil, complete all as specified. |
| 57 | Returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed.(Surplus soil if any shall not be removed but left over the trench) |
| 58 | Removing surplus soil to a distance not exc. 50 M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed. |
| 59 | Sandcushioningwith clean dry sandto cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cablecomplete all as specified.Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I. |
| 60 | M & L for providing PCC cable cover class LV type-I of size 250x150x40mm laid in perpendicular to the cable abutting each other all as specified and directed at site. |
| 61 | Sub Total |
| 62 | Schedule Of CreditSCHEDULE \"A\" PART-VII)SCHEDULE \"A\" PART-VII, Schedule of Credit ( Old Contractors Store For Incorporation in the Work) The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 603555.90 and any other reduction if any from quoted amount. |
| 63 | Schedule Of CreditSCHEDULE \"A\" PART-VIII)SCHEDULE \"A\" PART-VIII, Schedule of Credit ( Old Contractors Store and T&P Not For Incorporation in the Work) The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 29900.00 and any other reduction if any from quoted amount. |