Greater Noida Industrial Development Authority-GNIDA has published Supply, Installation , Testing, Commissioning Of Fire Detection , P.A. System And Fire Hydrant System, Sprinkler System, And Hand Appliances And Accessories Work Of Office Building For Gnida At Sector Kp-Iv, Greater Noida. (Tower-02 - 2Nd, 3Rd, 4Th And Co. Submission Date for this Tender is 26-03-2024. Irrigation System Tenders in noida Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | (A) Fire Hydrant System (For Second,Third and Fourth Floor) |
2 | Providing, laying, jointing and testing in trenches the following sizes of MS class `C" (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers and providing protection toembedded MS pipesandfittingsbyapplying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4 mm thick pyp kote (AW 4 mm) protection coating by thermo fusion process. Overlap shall be maintained at 15 mm. The application process shall be strictly according to manufacturer’s specification, inclusing necessary excavation trenches and refilling as required. |
3 | 80 mm dia |
4 | 100 mm dia |
5 | 150 mm dia |
6 | Providing & fixing Stainless Steel fire hydrant single landing valve with 80 mm NB flangedinlet ( Table-EFlange) , SS spindle controlled 63 mm dia femaleinstantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS standards.Includingflanged tappingfromwet rise complete as required. |
7 | Twin Landing Valve (For Internal Hydrants) |
8 | Providing and fixing first aidfire hose reel wall mounting swinging type fitted with 20 mm dia 36.5 m long high pressure ( 10 Kg/cm2) themo plastic hose tube conforming to IS: 12585 Type II with 5 mm outlet gun metal nozzle with shut off valve (I.S. 884-1969). |
9 | Providing and fixing of Non-percolating flexible hose (RRL type-"B" with EPDM Lined) ISI marked (IS:636) 63 mm dia x 15 M long complete with instantaneous type stainless steel 63 mm dia. IS marked Male and female couplings (IS:903)bound and riveted to hose pipe with copper rivets and 1.5 mm copper wire. |
10 | Providing and Fixing stainless steel 63 mm dia instantaneous pattern branchshort pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required. |
11 | Providing and fixing single acting air valve with screwed inlet 25 mm dia. |
12 | Providing and fixing forged brassball valve with forged brass ball suitable for test pressure ofnot less than 15 kg / sq.cm of thefollowingsize :Cost shall be inclusive of providing necessary union / flange connection). |
13 | Providing and fixing dial type pressure gauge with isolation cock and pipe at hydrant station. |
14 | Dial diameter 100 mm calibration |
15 | 0-15 kg |
16 | Providing& fixing butterfly valve tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, 2 nos. table-E flanges, nuts, bolts, washers & painting complete as required. |
17 | 150 mm dia |
18 | Providing & fixing dual plate CI wafer type check valve tested to a pressure of 15 Kg/sqcm. Including rubber gasket,2 nos. table-E flanges, union, nuts, bolts, washers & painting complete as required. |
19 | 150 mm dia |
20 | Providing and fixing MS partly glazed single/double hung lockable shutter fabricated from MS section as required with5 mm thick glass for fire station complete including stove enamelled painting of door and frame and words "Fire Hydrant" written on glass, suitable to accommodate 2 Hydrant landing valves, 1 fire hose reel, 2 nos.15m long 63 mm dia hose,1-branch pipe, 1no. fire man"s axe, fire extinguishers 2 nos, including suitably mounted on a raisedmasonry platform as required. (Approx. Size 0.90 m x 2.1m ) |
21 | Sprinkler System |
22 | Providing, laying, jointing, testing and commissioning of following sizes of pipes conforming to IS-1239 with all accessories like all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with clamps, hangers (using anchor fasteners) or angle iron, G.I. pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s / Consultants requirements including cutting holes and chases in brick and making good the same to original conditions complete in all respects. |
23 | All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwire and then supply of the same shall also be included for rates under this head. Including two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting oflegends both direction arrow as per the approval of the Project Manager. |
24 | Welding of any kind on the galvanized support / hanger shall not be permitted. |
25 | 25 mm dia |
26 | 32 mm dia |
27 | 40 mm dia |
28 | 50 mm dia |
29 | 65 mm dia |
30 | Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows : |
31 | Standard sprinkler Pendant / Upright Type (68 deg.C) |
32 | Semi Concealed Type with double rocette plate (68 deg.C) |
33 | Providing and fixing inspector"s test assembly complete with test value, sight glass sectional drain valve union with corrosion resistant orifice all complete |
34 | Providing& fixing butterfly valve tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, 2 nos. Table-E flanges, nuts, bolts, washers & painting complete as required. |
35 | 150 mm dia |
36 | Providing and fixing dial type pressure gauge with isolation cock and pipe at hydrant station. |
37 | Dial diameter 100 mm calibration 0-15 kg |
38 | Providing and fixing electrically operated flow indicating switches System Sensor in sprinkler branch line on each floor with necessary junction box installed in accessible place. (Wiring from switches to panel not included) |
39 | For 150 mm dia line |
40 | Providing and fixing single acting air valve with screwed inlet 25 mm dia. |
41 | Hand Appliances |
42 | Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylindricalbody, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. |
43 | Capacity 4.5 Kg. |
44 | Providing and fixing ABC Powder type fire extinguishers consisting of welded M.S. cylindricalbody, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. |
45 | Capacity 4.0 Kg. |
46 | S/ fixing of SS flexible sprinkler Pipe of 25 MM dia. |
47 | 1500MMLong |
48 | S/ fixing of SS Plate to above ceilling fan spinder. |
49 | (B) Fire Hydrant System (For Fifth Floor Commercial Court) |
50 | Providing, laying, jointing and testing in trenches the following sizes of MS class `C" (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers and providing protection toembedded MS pipesandfittingsbyapplying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4 mm thick pyp kote (AW 4 mm) protection coating by thermo fusion process. Overlap shall be maintained at 15 mm. The application process shall be strictly according to manufacturer’s specification, inclusing necessary excavation trenches and refilling as required. |
51 | 80 mm dia |
52 | 100 mm dia |
53 | 150 mm dia |
54 | Providing & fixing Stainless Steel fire hydrant single landing valve with 80 mm NB flangedinlet ( Table-EFlange) , SS spindle controlled 63 mm dia femaleinstantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS standards.Includingflanged tappingfromwet rise complete as required. |
55 | Twin Landing Valve (For Internal Hydrants) |
56 | Providing and fixing first aidfire hose reel wall mounting swinging type fitted with 20 mm dia 36.5 m long high pressure ( 10 Kg/cm2) themo plastic hose tube conforming to IS: 12585 Type II with 5 mm outlet gun metal nozzle with shut off valve (I.S. 884-1969). |
57 | Providing and fixing of Non-percolating flexible hose (RRL type-"B" with EPDM Lined) ISI marked (IS:636) 63 mm dia x 15 M long complete with instantaneous type stainless steel 63 mm dia. IS marked Male and female couplings (IS:903)bound and riveted to hose pipe with copper rivets and 1.5 mm copper wire. |
58 | Providing and Fixing stainless steel 63 mm dia instantaneous pattern branchshort pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required. |
59 | Providing and fixing single acting air valve with screwed inlet 25 mm dia. |
60 | Providing and fixing forged brassball valve with forged brass ball suitable for test pressure ofnot less than 15 kg / sq.cm of thefollowingsize :Cost shall be inclusive of providing necessary union / flange connection). |
61 | Providing and fixing dial type pressure gauge with isolation cock and pipe at hydrant station. |
62 | Dial diameter 100 mm calibration |
63 | 0-15 kg |
64 | Providing& fixing butterfly valve tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, 2 nos. table-E flanges, nuts, bolts, washers & painting complete as required. |
65 | 150 mm dia |
66 | Providing & fixing dual plate CI wafer type check valve tested to a pressure of 15 Kg/sqcm. Including rubber gasket,2 nos. table-E flanges, union, nuts, bolts, washers & painting complete as required. |
67 | 150 mm dia |
68 | Providing and fixing MS partly glazed single/double hung lockable shutter fabricated from MS section as required with5 mm thick glass for fire station complete including stove enamelled painting of door and frame and words "Fire Hydrant" written on glass, suitable to accommodate 2 Hydrant landing valves, 1 fire hose reel, 2 nos.15m long 63 mm dia hose,1-branch pipe, 1no. fire man"s axe, fire extinguishers 2 nos, including suitably mounted on a raisedmasonry platform as required. (Approx. Size 0.90 m x 2.1m ) |
69 | Sprinkler System |
70 | Providing, laying, jointing, testing and commissioning of following sizes of pipes conforming to IS-1239 with all accessories like all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with clamps, hangers (using anchor fasteners) or angle iron, G.I. pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s / Consultants requirements including cutting holes and chases in brick and making good the same to original conditions complete in all respects. |
71 | All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwire and then supply of the same shall also be included for rates under this head. Including two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting oflegends both direction arrow as per the approval of the Project Manager. |
72 | Welding of any kind on the galvanized support / hanger shall not be permitted. |
73 | 25 mm dia |
74 | 32 mm dia |
75 | 40 mm dia |
76 | 50 mm dia |
77 | 65 mm dia |
78 | Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows : |
79 | Standard sprinkler Pendant / Upright Type (68 deg.C) |
80 | Semi Concealed Type with double rocette plate (68 deg.C) |
81 | Providing and fixing inspector"s test assembly complete with test value, sight glass sectional drain valve union with corrosion resistant orifice all complete |
82 | Providing& fixing butterfly valve tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, 2 nos. Table-E flanges, nuts, bolts, washers & painting complete as required. |
83 | 150 mm dia |
84 | Providing and fixing dial type pressure gauge with isolation cock and pipe at hydrant station. |
85 | Dial diameter 100 mm calibration 0-15 kg |
86 | Providing and fixing electrically operated flow indicating switches System Sensor in sprinkler branch line on each floor with necessary junction box installed in accessible place. (Wiring from switches to panel not included) |
87 | For 150 mm dia line |
88 | Providing and fixing single acting air valve with screwed inlet 25 mm dia. |
89 | Hand Appliances |
90 | Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylindricalbody, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. |
91 | Capacity 4.5 Kg. |
92 | Providing and fixing ABC Powder type fire extinguishers consisting of welded M.S. cylindricalbody, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. |
93 | Capacity 4.0 Kg. |
94 | S/ fixing of SS flexible sprinkler Pipe of 25 MM dia. |
95 | 1500MMLong |
96 | S/ fixing of SS Plate to above ceilling fan spinder. |
97 | (C) FIRE ALARM SYSTEM (ADDRESSABLE TYPE) (For Second,Third and Fourth Floor) |
98 | Supply,Installation,Testing&CommisioningofFire GraphicsSoftwareWinmagtobeloadedon PCto monitor the Floor wise Fire Detection System. |
99 | Supply, Installation,Testing & Commisioning of Analog AddressableIntelligentmultisensor detectorwith two inbuilt optical smoke sensors with light angles as well asadditionalheatdetectorsensorwithdecentralise intelligence, soft addressablePhotothermal type with inbuilt fault isolatoras per NFPA style 7 wiring complete with base as required. |
100 | Supply Installation, Testing & Commissioning of Intelligent addressable photothermal detector with bluecolourLEDforveryearlywarningwithinbuilt isolator as per NFPA7 style 7 wiring & standard base complete as per specification. |
101 | Supply, Installation, Testing & Commisioning of Analogue AddressableIntelligent Heat Detector with fixed & rate of rise temperature function with decentralise intelligence , soft addressable type, with inbuilt fault isolatoras per NFPA style 7 wiring complete with base as required. |
102 | Supply Installation, Testing & Commissioning of Intelligent addressable Manual Call Point / Pull station complete as per specification. |
103 | Supply, installation, testing and commissioning of addressablecontrolmodulecompleteasper specification. |
104 | Supply, installation, testing and commissioning of addressablemonitormodulecompleteasper specification. |
105 | SupplyInstallation,Testing&Commissioningofwall mounting loop powered addressable type hooter with all accessories. |
106 | Supply Installation, Testing & Commissioning of Response Indicator single LED / 2 LED. |
107 | SupplyInstallation,Testing&CommissioningofFire fighters telephone handset. |
108 | SupplyInstallation,Testing&CommissioningofFire fighters telephone jack. |
109 | Supply, Installation, Testing & Commissioning of 2corex1.5sq.mmsizesof1.1KVgrademulticore copperconductor FRLSinsulatedandFRLS sheathed armoured cable conforming torelevant IS. Outer sheathing of cable shall be in red colour. (DSR- 1.17.2) |
110 | Supply Installation, Testing & Commissioning of Intelligent addressable photothermal detector with CO sensor to sense 50 ppm and 100 ppm carbon mono oxider for pre alarm and alarm with inbuilt isolator as per NFPA7style7 wiring & standardbase complete as per specification. (DSR-1.17.2) |
111 | Supply,installation,testing&commissioningofM.S. junctionbox(4""X4""RectangularOR4""Circularas per detector size.) etc. complete as required. |
112 | Supply,Erection,Testing&CommissiongofPanic Bar, Shall be with Local Scare alarm, with dedicated powersupplyunitwithbatterybackupandshallbe with magnetic contact.The same shall be as an input totheAccessControlleronthenetwork.EachPB shall be provided with sounder output at the Security controlroomforanyemerrgencydooralarmsand same to be intergrated with Fire Alarm Panel. |
113 | P.A. SYSTEM |
114 | SITCofIPbasedPAController cabableofhandling 50zones, expandableupto250Zoneswith required sizeofrack.DigitalaudiocontrollercomlyingtoIEC EN 60849 / VDE 0828 with built-in high and low pass filters and parametric equalizer capable of handling 24 loudspeakerlines.Supervisionofpoweramplifiers andhot-standbyprovisionforamplifierredundancy. Permenant,non-audiblesupervisionofloudspeaker linesalsoduringpowersavemode.4inputsfor Automatic Volume Control. 4 ethernet 100Mbps sockets with switching. Non volatile audio memory up to176seconds,freelyscalable1I2Cbus. including suitable size of rack for complete system. |
115 | Power Amplifier 2x500W/100V -Meets standards IED BS EN 60286-3, 55013, 55020 -Inrush restraint and softstart -Integrated electronic protection against thermal overload and short circuit. -Temperature controlled fans, airflow from front to rear.-Method of control: Class AB -Power output of amplifier: 2 x 500W sin. /100V -Output range: 50 Hz-22kHz; 0/-0,5 dB -Signal tonoise ratio (not valuated): > 105 dB -Channel separation: > 75 dB -THD (total harmonic distortion): < 0,08% -Input level at max. output voltage: 0 dBu -The amplifier has to be switched into Stand-by Mode in case of power loss by the control centre. -500W amplifier to work as a hot-standby in case any amplifier channel failure |
116 | Supply, Installation, Testing & Commissionig of Volume Controller for all the closed areas. |
117 | 6WmultitapvoicealarmspeakerwithFireDome complyingwithBS2839part8-linevoltage100V (Wall / Ceiling speaker) |
118 | NetworkableDigital Storage- |
119 | E2695onnected to the Ethernet -Compliant to EN60849 standard -Flash memory for critical messages -Hard disk memory for 150hours of audio playback -Unit should be able to log & record announcements |
120 | 8 port LAN switch |
121 | Wiring for PA system with the following sizes of PVC insulated copper conductor twisted cables in existing surface/recessed M.S. conduit etc. as complete as required. |
122 | 2 x 1.5 sq.mm twin twisted PVC wire (30/0.25mm) |
123 | (D) FIRE ALARM SYSTEM (ADDRESSABLE TYPE) (For Fifth Floor Commercial Court) |
124 | Supply,Installation,Testing&CommisioningofFire GraphicsSoftwareWinmagtobeloadedon PCto monitor the Floor wise Fire Detection System. |
125 | Supply, Installation,Testing & Commisioning of Analog AddressableIntelligentmultisensor detectorwith two inbuilt optical smoke sensors with light angles as well asadditionalheatdetectorsensorwithdecentralise intelligence, soft addressablePhotothermal type with inbuilt fault isolatoras per NFPA style 7 wiring complete with base as required. |
126 | Supply Installation, Testing & Commissioning of Intelligent addressable photothermal detector with bluecolourLEDforveryearlywarningwithinbuilt isolator as per NFPA7 style 7 wiring & standard base complete as per specification. |
127 | Supply, Installation, Testing & Commisioning of Analogue AddressableIntelligent Heat Detector with fixed & rate of rise temperature function with decentralise intelligence , soft addressable type, with inbuilt fault isolatoras per NFPA style 7 wiring complete with base as required. |
128 | Supply Installation, Testing & Commissioning of Intelligent addressable Manual Call Point / Pull station complete as per specification. |
129 | Supply, installation, testing and commissioning of addressablecontrolmodulecompleteasper specification. |
130 | Supply, installation, testing and commissioning of addressablemonitormodulecompleteasper specification. |
131 | SupplyInstallation,Testing&Commissioningofwall mounting loop powered addressable type hooter with all accessories. |
132 | Supply Installation, Testing & Commissioning of Response Indicator single LED / 2 LED. |
133 | SupplyInstallation,Testing&CommissioningofFire fighters telephone handset. |
134 | SupplyInstallation,Testing&CommissioningofFire fighters telephone jack. |
135 | Supply, Installation, Testing & Commissioning of 2corex1.5sq.mmsizesof1.1KVgrademulticore copperconductor FRLSinsulatedandFRLS sheathed armoured cable conforming torelevant IS. Outer sheathing of cable shall be in red colour. (DSR- 1.17.2) |
136 | Supply Installation, Testing & Commissioning of Intelligent addressable photothermal detector with CO sensor to sense 50 ppm and 100 ppm carbon mono oxider for pre alarm and alarm with inbuilt isolator as per NFPA7style7 wiring & standardbase complete as per specification. (DSR-1.17.2) |
137 | Supply,installation,testing&commissioningofM.S. junctionbox(4""X4""RectangularOR4""Circularas per detector size.) etc. complete as required. |
138 | Supply,Erection,Testing&CommissiongofPanic Bar, Shall be with Local Scare alarm, with dedicated powersupplyunitwithbatterybackupandshallbe with magnetic contact.The same shall be as an input totheAccessControlleronthenetwork.EachPB shall be provided with sounder output at the Security controlroomforanyemerrgencydooralarmsand same to be intergrated with Fire Alarm Panel. |
139 | P.A. SYSTEM |
140 | SITCofIPbasedPAController cabableofhandling 50zones, expandableupto250Zoneswith required sizeofrack.DigitalaudiocontrollercomlyingtoIEC EN 60849 / VDE 0828 with built-in high and low pass filters and parametric equalizer capable of handling 24 loudspeakerlines.Supervisionofpoweramplifiers andhot-standbyprovisionforamplifierredundancy. Permenant,non-audiblesupervisionofloudspeaker linesalsoduringpowersavemode.4inputsfor Automatic Volume Control. 4 ethernet 100Mbps sockets with switching. Non volatile audio memory up to176seconds,freelyscalable1I2Cbus. including suitable size of rack for complete system. |
141 | Power Amplifier 2x500W/100V -Meets standards IED BS EN 60286-3, 55013, 55020 -Inrush restraint and softstart -Integrated electronic protection against thermal overload and short circuit. -Temperature controlled fans, airflow from front to rear.-Method of control: Class AB -Power output of amplifier: 2 x 500W sin. /100V -Output range: 50 Hz-22kHz; 0/-0,5 dB -Signal tonoise ratio (not valuated): > 105 dB -Channel separation: > 75 dB -THD (total harmonic distortion): < 0,08% -Input level at max. output voltage: 0 dBu -The amplifier has to be switched into Stand-by Mode in case of power loss by the control centre. -500W amplifier to work as a hot-standby in case any amplifier channel failure |
142 | Supply, Installation, Testing & Commissionig of Volume Controller for all the closed areas. |
143 | 6WmultitapvoicealarmspeakerwithFireDome complyingwithBS2839part8-linevoltage100V (Wall / Ceiling speaker) |
144 | NetworkableDigital Storage- |
145 | E2695onnected to the Ethernet -Compliant to EN60849 standard -Flash memory for critical messages -Hard disk memory for 150hours of audio playback -Unit should be able to log & record announcements |
146 | 8 port LAN switch |
147 | Wiring for PA system with the following sizes of PVC insulated copper conductor twisted cables in existing surface/recessed M.S. conduit etc. as complete as required. |
148 | 2 x 1.5 sq.mm twin twisted PVC wire (30/0.25mm) |
149 | Labour Cess will be paid extra as per applicable |
150 | GST will be paid extra as per applicable |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy