Uttar Pradesh Projects Corporation Limited has published Tender For Medical Gas Pipe Line System For Kaili Hospital Basti. Submission Date for this Tender is 08-04-2024. Gas Pipe Line Tenders in basti Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 30-Mar-2024 | Corrigendum | Date | 08-04-2024 |
Sl. No. | Item Description |
1 | GAS PLANT EQUIPMENT(MGPS) |
2 | MEDICAL AIR COMPRESSOR SYSTEM,Receprocating air compressor with foundation, Filtration system. receiver,electrical connection from compressor to control panel and all as required as per specification. Entire system shall be installed as a package and compatible to fulfil the demand of system. Product shouldbe as per specification. |
3 | Main component of system is as below |
4 | Receprocating Aircompressor with suitable motor capacity 60 CFM @ 8 Bar (+/-5%) - 3 Nos. (TriplexSystem) |
5 | Air receiver tank 2500 Itr-1 No. |
6 | Three Stage Air filtration Set as per specification-2 Nos. |
7 | Air dryer Desicant Type with pre filter 60 CFM-2 Nos. |
8 | Air Pr. Reducing Station 4-Bar & 7-Bar-2 Nos. |
9 | MEDICAL VACUUM SYSTEM:Reciprocating Vacuum pump with foundation, Filtration system,receiver, electrical connection from compressor to control panel and all as required as per specification. Entire systemshall be installed as a package and compatible to fulfil the demand of system.Product should be as perspecification. |
10 | Main component of system is as below |
11 | Reciprocating Vacuum Pump With capacity 110 CFM (+/5%) with suitable Motor & Pressure Switch-3 Nos.(Triplex System) |
12 | Pressure Switch-2 Nos. |
13 | Silencer muffler type |
14 | Vacuum Receiver tank 2500 Ltr. |
15 | Vacuum Bacterial Filter for pump capacity-2 Nos. |
16 | OXYGEN SUPPLY SYSTEM |
17 | OXYGEN MANIFOLD-Oxygen manifold extendable type with middle frame along with tail pipe as sizegiven,having top frame comprising of high-pressure copper pipe with high pressure brass fitting made ofhigh tensile brass,NRV and high-pressure copper tail piece made of high-pressure copper pipe.One bankshall be a reserve source of oxygen supply. It shall automatically supply the pipeline when primary sourcebecomes exhausted or fails due to any reason.The system shall have source shut-off valve for easychanging and positioning.The cylinder should be placed with the help of cylinder brackets and fixing chainswhich should be zinc plated appropriate.(Gas cylinders are not in the scope of this work). Product should beas per specification. |
18 | 16+16 Size |
19 | Oxygen Emergency System:-The oxygen emergency system contains bulk Gas cylinder manifold along withcopper header,Brass Non-Return valve&High-pressure copper tail pipe for each cylinder complete. Product should be as per specification. |
20 | 6+6 Size |
21 | CE Marked compliant with ISO 7396 Oxygen Change-Over Reduction Box(Automatic Control Panel)ofDigital fully Automatic type, capable of switching from "Bank in Use" to "Reserve Bank" without fluctuation indelivery line pressure and without the need for external electrical power.The Changeover panel shall berated for min. 1000 LPM at 400 kPA,and shall include the following accessories.Panel shall comply withHTM/ISO as per specification. |
22 | Main component/feature of system is as below |
23 | Power Supply Module to provide power supply for alarm system display |
24 | Signaling Module for Pressure monitoring and Alarm Activation |
25 | Double line pressure Regulator |
26 | High and Low Limit Pressure Switches |
27 | Changeover and safety valve |
28 | Panel constructed with Stainless Steel material |
29 | NITROUS OXIDE SUPPLY SYSTEM |
30 | Nitrous Oxide Manifold:-The nitrous oxide manifold system contains bulk Gas cylinder manifold along withcopper header,Brass Non-Return valve& High-pressure copper tail pipe for each cylinder complete. Systemmust be equipped with high pressure Regulator.Product should be as per specification. |
31 | 2 Cylinder manifold for bulk cylinder |
32 | AGSS System consisting of duplexskid mounted AGSS pumps with remote switches-AGSS simplex switchMake:Altos/Aktiv/Sigma-Meditech |
33 | Combined Electrical Control Panel for suitable Medical Air Compressors & Vacuum Pumps as required inhospital for auto cascading and manual mode as required in compliance with ISO 7396 & specification withall required support foundation complete |
34 | For upto 6 Pump System as required and mention in system |
35 | PART-B (GAS DISTRIBUTION EQUIPMENTS) |
36 | Terminal Outlets:-Terminal Outlets gas specific for the services indicated (viz. 02, Air & Vacuum) and toaccept only compatible quick connect Pin/Geometric Index type adapters as per ISO 7396 standard. Manufactured in compliance with CE and ISO 13485 as per specification. |
37 | Oxygen Outlet |
38 | Vacuum Outlet |
39 | Medical Air Outlet |
40 | Nitrous Oxide Outlet |
41 | AGSS Outlet |
42 | Suitable Gas Outlet Adopter compatible with required ward Accessories made from stainless steel as percurrent latest standard. |
43 | Oxygen Outlet |
44 | Vacuum Outlet |
45 | MA-4 Outlet |
46 | Nitrous Oxide Outlet |
47 | AGSS Outlet |
48 | Gas lockable AVSU/CONTROL-CLOSING VALVE BOXES with integrated alarm system as perspecifications, and as required. Product should be as per specification and below mentions feature.As perspecification. |
49 | Microprocessor based module |
50 | Highly accurate "Heavy Duty" pressure transducer |
51 | Digital & illuminated LED display of "Normal", "High" & "Low" |
52 | Digital pressure unit display options-psi/ bar or kg/cm2 |
53 | Adjustment & parameter setting by touch button |
54 | Audio Mute option |
55 | Reusable lock assembly |
56 | PED:2014/68/EU certified full port Ball Valve (PN 30) |
57 | 2 Services (Oxygen,Vacuum) |
58 | 3 Services (Oxygen,MA-4,Vacuum) |
59 | 5 Services (Oxygen, MA-4, MA-7,Nitrous Oxide, Vacuum) |
60 | Modular bed head panel,with provision of gas outlet, electrical socket switch,made of high grade ofaluminium.Each panel must be equipped with IV Pole, Vacuum Slider, Utility Basket. Fabricated byextrusion method and powder coated as per approved colours. It has dual compartment facility separate forgases and electrical services as per international standard for safety and service. Unit must bemanufactured as per CE and ISO 13485 certifying facility as per specification. |
61 | Upto 3 Gas outlet 900mm long |
62 | Upto 4/5 gas outlet 1200mm long |
63 | Copper Piping:-copper pipes, for Medical Gases, complete with elbows, flanges,specials, others fittings, and steel supports. The copper pipe should be of solid drawn seamless deoxidized,un-arsenical,temperedand of degreased material conforming to BS-EN 13348/ASTM B819,of copper pipe.must be certified andinspected by third party inspection agency like LLoyds/SGS/TUV etc. |
64 | 12 mm OD |
65 | 15 mm OD |
66 | 22 mm OD |
67 | 28 mm OD |
68 | 42 mm OD |
69 | 54 mm OD |
70 | Isolation valve-All valves are to be ball valves type and PTFE or Teflon seals. They shall be suitable for aworking pressure of 10.2 Kg/c? gauge. Valves shall be fitted into the pipeline by means of capillary hardsoldered joints containing silver.it should be open/close with help of handle with rotation of 90 degree. |
71 | 12mm |
72 | 15mm |
73 | 22mm |
74 | 28mm |
75 | 42mm |
76 | 54 mm |
77 | PART-C(MEDICAL GAS PIPELINE SYSTEM ACCESSORIES) |
78 | Oxygen Flow Meter-Made from brass,chrome plated.It shall be back pressure compensated type havinghousing of Polycarbonate autoclavable reusable flow range 0-15 LPM.Fitted with matching adopter foroxygen outlet point and humidifier shall be compatible with flowmeter and reusable and as per specificationsand as required.Product should be as per specification. |
79 | SUCTION UNITS: |
80 | Ward Vacuum Unit-Regulator capable of controlling vacuum between 0 to 760 mm Hg and Polycarbonateautoclavable,reusable type receiver jar.Vacuum regulator shall have a dial gauge,on/off switch,valvecontrol knob and as per specifications and as required. Product should be as per specification. |
81 | 600 ml Receiver Jar |
82 | Low pressure suction tube for suction outlet adopter as required |
83 | Operation Theatre Suction Trolley-having 2 Nos.2000 ml receiver jars of Polycarbonate autoclavable up to121*C,reusable and mounted on trolley with wheel arrangement. The trolley shall have one number ofvacuum regulators having regulation control between 0-760 mm Hg and interconnecting suction tubes. Product should be as per specification. |
84 | High pressure tube for specific gas outlet adopter as required. |
85 | Oxygen |
86 | Nitrous Oxide |
87 | Medical Air |
88 | GST Extra As per Applicable |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy