Tender For Repair And Maintenance Of Defective Switchgears In Generator Room Main Feeder Pillar Sub Feeder Pillar And Joint Box For Bfls Installed In Aor Of 139 Bn Bsf Under Hq Bsf Panisagar, North Tripura-Tripura

Border Security Force-BSF has published Tender For Repair And Maintenance Of Defective Switchgears In Generator Room Main Feeder Pillar Sub Feeder Pillar And Joint Box For Bfls Installed In Aor Of 139 Bn Bsf Under Hq Bsf Panisagar. Submission Date for this Tender is 26-03-2024. Feeder Pillar Tenders in North Tripura Tripura. Bidders can get complete Tender details and download the document.




Tender Notice

42937896
Tender For Repair And Maintenance Of Defective Switchgears In Generator Room Main Feeder Pillar Sub Feeder Pillar And Joint Box For Bfls Installed In Aor Of 139 Bn Bsf Under Hq Bsf Panisagar
Open Tender
Indian
Tripura
North Tripura
26-03-2024

Tender Details

Repair And Maintenance Of Defective Switchgears In Generator Room Main Feeder Pillar Sub Feeder Pillar And Joint Box For Bfls Installed In Aor Of 139 Bn Bsf Under Hq Bsf Panisagar

Key Value

Document Fees
Refer document
EMD
INR 27058.0 /-
Tender Value
INR 13.52 Lakhs /-

BOQ Items

Name of Work:Repair and Maintenance of defective switchgears in Generator room, main feeder pillar, sub feeder pillar and joint box for BFLs installed in AOR of 139 BN BSF under HQ BSF Panisagar.
Sl. No. Item Description
1Providing & fixing of 200 amps, 415 volt, type FN(4P) switch disconnector fuse unit open execution with suitable for din fuse link, HN size 0, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 04 Nos din fuse link cat. No.SF94132 and complete with connections, testing and commissioning and dismentling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK90471 or its compitable to Havells/Standard/legrand/schneider.
2Providing & fixing of 160 amps, 415 volt, type FN(4P) switch disconnector fuse unit open execution with suitable for din fuse link, HN size 000/00, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 04 Nos din fuse link cat. No.SF94939 and complete with connections, testing and commissioning and dismentling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK90498 or its compitable to Havells/Standard/legrand/schneider.
3Providing & fixing of 125 amps, 415 volt, type FN(4P) switch disconnector fuse unit open execution with suitable for din fuse link, HN size 000/00, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 04 Nos din fuse link cat. No.SF94030 and complete with connections, testing and commissioning and dismentling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK90497 or its compitable to Havells/Standard/legrand/schneider.
4Providing & fixing of 63 amps, 415 volt, type FN(4P) switch disconnector fuse unit open execution with suitable for Din fuse link, size 14x51, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 04 Nos din fuse link cat. No.SF94027 and complete with connections, testing and commissioning and dismentling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK95421 or its compitable to Havells/Standard/legrand/schneider.
5Providing & fixing of 32 amps, 415 volt, type FN(TPN) switch disconnector fuse unit open execution with suitable for Bolted fuse link, size A1L, Fr 1, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 03 Nos bolted fuse link cat. No.ST34529 and complete with connections, testing and commissioning and dismentling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK95653 or its compitable to Havells/Standard/legrand/schneider.
6Providing & fixing of 125 amps, 415 volt, Bolted fuse link, size A4, for fixing in existing SDF switch, drilling holes i/c 03 Nos bolted fuse link cat. No.ST30769 and complete with connections, testing and commissioning and dismentling of existing fuse etc. as required. Make- Havells/Standard/legrand/schneider.
7Providing & fixing of 63 amps, 415 volt, Bolted fuse link, size A4, for fixing in existing SDF switch, drilling holes i/c 03 Nos bolted fuse link cat. No.ST35828 and complete with connections, testing and commissioning and dismentling of existing fuse etc. as required. Make- Havells/Standard/legrand/schneider.
8Providing & fixing of 32 amps, 415 volt, Bolted fuse link, size A4, for fixing in existing SDF switch, drilling holes i/c 03 Nos bolted fuse link cat. No.ST35828 and complete with connections, testing and commissioning and dismentling of existing fuse etc. as required. Make- Havells/Standard/legrand/schneider.
9Wiring for defective internal MFP & SFP interconnectionwiring with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface as required. (i) 1 X 16 sq. mm
10Wiring for defective internal MFP & SFP interconnectionwiring with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface as required.(ii) 1 X 10 sq. mm
11Wiring for defective internal MFP & SFP interconnectionwiring with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface as required. (iii) 1 X 6 sq. mm
12S/I/T/C of outdoor type joint box,made out of 16 SWG CRCA sheet duly primed & painted with synthetic enamel black paint of size 450 mm(height) x 450 mm (width) x 300 mm deep having 200 amps, 04 nos insulated aluminium bus bars and suitable size insulator,& angle iron frame of base size 450 mm x 300 mm with 600 mm long legs made out of 45 mm x 45 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, etc. as requiredAs per direction of Engineer Incharge.
13Supplying & laying of one number XLPE insulated and PVC sheathed Armoured power cable of 1.1 KV grade of size 3.5 x 35 sqmm, direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering Conf. to IS:7098 part - I of make Havells / Polycab/ KEI.
14Supplying & laying of one numberXLPE insulated and PVC sheathed , armoured aluminium power cable of 1.1 KV Grade of size 3.5 X 35 Sq. MM conf to IS: 7098 (Part-I) in the existing masonry open duct as required. makeMake Havells / Polycab /KEI.
15Add @ 1% labour cess
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail