Rajasthan State Road Development And Construction Corporation Limited has published Tender For Supply, Installation, Testing, Commissioning Of Lift, Fire Fighting And External Electrical Work At Medical College Hospital, Karauli. Submission Date for this Tender is 26-03-2024. Electrical Maintenance Tenders in Karauli Rajasthan. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | FIRE FIGHTING PUMPS |
2 | Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H. |
3 | (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head |
4 | (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal |
5 | (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head |
6 | (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . |
7 | ( E)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads. |
8 | (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works inPhysical presence of Department’s representatives. |
9 | (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM |
10 | (H)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
11 | 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM |
12 | Supplying, Installation, Testing & Commissioning ofDiesel Engine Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H. |
13 | (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head |
14 | (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal |
15 | (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head |
16 | (D) Heat Exchanger cooled Diesel Engineas per NFPA 20 developing suitable BHP for the below mentioned dischargeat 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank. |
17 | (E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine System Controller in Existing Fire Fighting Control panel |
18 | (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. |
19 | (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM |
20 | (H) Pump to be placed on Suitable size Existing Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
21 | 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 1800 / 2300 RPM |
22 | Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Jockey pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E,F and G |
23 | (A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head |
24 | (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal |
25 | (C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . |
26 | (D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads. |
27 | (E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives. |
28 | (F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM |
29 | (G)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
30 | 180 LPM suitable for 70 Mtr Single Stage |
31 | Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Terrace pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H. |
32 | (A) Horizontal End suction Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head |
33 | (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal |
34 | (C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . |
35 | (D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads. |
36 | (E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives. |
37 | (F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM |
38 | (G) Suitable size Reinforced cementconcreat (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) |
39 | (H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to protect it from weather All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
40 | 450 LPM with 35 mtr head |
41 | Supplying, Installation, Testing & Commissioningsubmersible type dewatering pump of stainless steel casing and Norylimpellorof discharge and head given below complete withall accessories suitable for operation on 230 V, single phase/415 V /3 phase, 50 Hz. AC supply complete with starter for automatic operation including water level sensing device / float switchinter connection with submersible cable etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
42 | 180 LPM with 10 mtr head |
43 | SITC of pressure switches ofpressure range 3 to 15 Bar for Main, Jockey, Terrace pumpandDiesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
44 | SITC of UL listed / FM Approved Brass Test and drain valve assembly for sprinkler system comprising of 3-position ( off, test and Drain ) ball valves with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI and Inbuilt sight glass etc. as required of following size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
45 | 25 mm Dia. |
46 | SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Staticpressure rating up to 250 PSIin cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
47 | 150 mm Dia. |
48 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C " class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applicationsincluding cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of requiredshade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
49 | 25 mm dia |
50 | 32 mm dia |
51 | 40mm dia |
52 | 50mm dia |
53 | 65 mm dia |
54 | 80 mm dia |
55 | 100 mm dia |
56 | 150 mm dia |
57 | 200 mm dia, 6.0 mm thick |
58 | 250 mm dia, 6.35 mm thick |
59 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C" class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supportsincluding cutting,welding etc & forged steel fittings like elbows, tees,tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
60 | 80 mm dia |
61 | 100 mm dia |
62 | 150 mm dia |
63 | Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height withflanged connection,Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
64 | Supplying and fixing cylindrical air vessel of continuous welded constructionfixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height withflanged connection, Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
65 | Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holesin existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick),nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
66 | 150 mm dia |
67 | 200 mm dia |
68 | Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
69 | 100 mm dia |
70 | 150 mmdia |
71 | 200 mm dia |
72 | Supplying and Fixing of PN 1.6Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
73 | 80 mm dia |
74 | 100mmdia |
75 | 150mm dia |
76 | 200mm dia Gear Operated |
77 | Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
78 | 25 mm dia. |
79 | 50 mm dia |
80 | SITC of installation control valve of cast iron body and brass/bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continous alarm when the wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
81 | 150 mm |
82 | Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick),nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
83 | Single Headed with 75 mm Dia. Flanged Inlet |
84 | Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
85 | Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A)63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304male and female couplings(IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. |
86 | Supplying & fixing SS-304 Short Branch Pipeconforming to IS: 903:93 fitted with 20mm (nominal internal diameter)bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
87 | Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required.(A) Thermoplastic / Rubber Hose(B)20 mmdia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall.(D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
88 | With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969and Bursting pressure 42 Kg/sqcm |
89 | Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valvecomplete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following Ways. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
90 | 4 Way |
91 | Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection)for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
92 | Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheetDuly powder coated in red color externally and white internally with 6 mm thick glazeddoors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
93 | Providing and fixing of Fire / Electrical Shaft Door made frompowder coated (50 Micron) aluminiumpartialy glazed with 6 mm thick glass and Partialy/ Fully Louvered with Outer frame of AluminiumSection of Size 100 mm x 45 mm x 1.5 mmand Shutter"s Top, Middle & sideSection of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mmComplete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
94 | Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler headswith Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
95 | Pendant/ Upright type |
96 | Sidewall Sprinklers (ordinary) |
97 | Extended Throw Sidewall type . |
98 | Providing & fixing of UL listed 1.5 mm thick chrome plated Dual type MS Escutcheon platesfixed at junction of Sprinkler piping with the false ceiling. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
99 | Supply & Fixing of Fire Man"s Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
100 | Providing & fixingsprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
101 | 1000 mm Long |
102 | Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cmwith 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, dulycalibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS PipeEtc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
103 | Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
104 | Capacity 4.5 Kg. |
105 | Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
106 | 6 kg |
107 | Supply & Fixing of Water + AFFF 6%Mechanical Foam typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
108 | Capacity - 9 Ltrs. |
109 | Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Double mounted handle as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
110 | Supply & Fixing of Ceiling mounted UL listed clean Agent (HFC-236fa), Modular typeFire Extinguisher , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Fixed Bulb with Temerature 68 deg C, QR code for Product Traceability including Fixing on Ceiling with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
111 | 5 Kg Capacity |
112 | 10 Kg Capacity |
113 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
114 | 50 mm dia per running inch length |
115 | 100 mm dia per running inch length |
116 | 150 mm dia per running inch length |
117 | 200 mm dia per running inch length |
118 | NON BSR : Supply of strong rope ladder made from 18-20 mm dia Nylone/Polypropylene (PP) rope,with 20-25 mm solid wooden/aluminium rung of length 330-370 mm and span of 370-450 mm and loading capacity of 500 kg and loading of rung with 200 kg of following length |
119 | 30 meter |
120 | SITC offloor mounted dust and vermin proof compartmentalisedcubical type main fire pump house panel made out of CRCA sheet , required hardware,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shadeThe panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear. Thickness of sheet shallnot be less than 1.6 mm up to 600 mm length / widthof any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall beof 2.0 mmthick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below: |
121 | Incomer |
122 | 630 Amp. FP MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release,Digital Ammeter, Voltmeter, CT, Indicating Lamps, 900 AmpsAlum. Bus bar with with heat shrinkable sleeves. |
123 | Out going |
124 | (a) 400 Amp. TPN MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. DOL Starter of 100-125 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets |
125 | (b) 100 Amp. TPN MCCB, 16 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. DOL Starter of15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Set |
126 | © One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter |
127 | (d) System controller to control Operation Main Electric pumps (two no), Diesel pump, jockey pump in sequence as per specs. Consisting of relays, timers, NO / NC contacts etc as required. Make:- Engineers & Engineerrs, Advance, Jhons Electrical, Milestone, Ankit Electricals |
128 | NON BSR : Providing, fixing, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges.It should be complete as per manufacturer"s specifications & as directed by Engineer- in-charge Make:- Danfoss, Resistoflex, EasyFlex |
129 | 200 mm dia |
130 | 150 mm dia |
131 | 100 mm dia |
132 | LIFT |
133 | Supplying , installation , Testing and commissioning of the Bed Elevatorhaving following main features: |
134 | (a)MOTOR : Gearlesslift drivecomprising of high starting torque lift duty , 3 phase 440 Volts A.C. permanent magnetic synchronous motor (Located on shaft on top of guide rail ) of proper rating with high efficiency shall be used. |
135 | (b) Operation / Drive : Microcessor based /PLC, AC Variable Voltagevariable frequency variable speed (V3F) vector control drive with encoder feedbackfeedback closed loop system shall be used for lift car and door operationwhich shall be full collective selective operation hall call demand response , UP/Down hall stops , main , Up/Down contactor with overload and phase reversal relay and safety controls . |
136 | ( c ) Traction Media: main hoist flat coated steel belt / rope . Thimbles of spring permit adjustment of uniform tension for smooth operation of the elevator Pulse belt monitoring system to avoid the cut in the belt. |
137 | (d) Car :car should be with M S platform with bracings of adquate size and to sustain the impact load cabin plus passengers with safety factor of fire for steel with 19 mm Granite flooring and side panels should be of Stainless steel with honey comb finish of sheet of grade 304 duty or higher with S.S. handrails . Car ceiling shall be steel finish with aesthetic appearances with LED ceiling lights (Ceiling light should be diffuser type) .The size of the car shall be taken as per available lift well size and relevant BIS code of lifts . Car panel will also be ofS S 304 or higher gradefinished with emergency stop device , emergency alarm,mechanical door safety device ,full length infra-red curtain in car door , facility of auto/attended mode . All car panel buttons and all floor switches must be with brail language as per lift act. Agency shall also provide & install one No. 2 MP , IR , IP based ceiling mounted Dome Camerain the car complete with connecting cables & accessories (To be connected with existing CCTV system in the Building by lift agency) .The inspection unit shall be provided at the top of the car. |
138 | (e)Landing Doors : All landing door shall be fully automatic centre openingmade of honeycomb finish stainless steel grade 304 or higher with key holes and infrared curtains with unlocking facility from outside. The landing door should be fire rated (120 minuts) |
139 | (f) Emergency light: Appropriate rechargeable battery operated LED emergency light in the car and along with alarm switch shall be provided. |
140 | (g) ARD: Automatic rescue Device (ARD) shall be provided according to passenger capacity with SMF batteries of approved brands as per BSR. |
141 | (h) Audio-Visual Indication : Audio visual indication in the lift car, showing over loadingsuch that doors kept open till excess load is removed. |
142 | (i) Scrolling Indicators: LED TYPE dot matrixscrolling indicator system for up-down arrow with floor position indicator shall be provided inside the car and at all stops/floors. |
143 | (j) Buffers : Spring buffers/PU Buffers shall be provided. |
144 | (k) Car Fan :ENERGY EFFICIENT cross flow Car fan/blower with automatic sleep timer shall be provided. |
145 | (l) Voice Annunciator: Voice annunciator with suitable music shall be provided in lift car. |
146 | (m) Self diagnostics system for operational and safety parameters shall be provided in control panel . |
147 | (n) Mechanical/Electronic over speed governor , door key holes in the floor doors, fireman switchshall be provided . |
148 | (o) Lift machine hoisting arrangement in the lift machine room , Cast Iron counter balance to promote smooth and economic operation complete withfor the car & counter weight ,Trap Door , Lifting hooks as requiredand monkey ladders for lift pit should be provided by theagency along withall other steel structure works , foundations for the machine etc as required |
149 | (p) Permanent wiring in lift machine roomand in lift well with providing and fixing of electrical distiribution boardcomplete with SP ,RCCB,TP/FP MCB"s etc , proper numbers of light points, with LED fixtures , exhaust fan , 2 nos copperplate /chemical earthing with 8 SWG copper earth wire and plug points shall be provided by the agency . |
150 | (q) All civil work related to installation of lift like finishing , cleaning and levellingof lift pit , white wash of lift welland in machine room shall be done by the lift erecting agency without any extra cost. |
151 | ( s) Agency has to provide all working drawings and documents to comply latest BIS specifications and make proper liasion services for obtaining all necessary permissions.Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Kruppand Equivelent Make as per Annx. |
152 | 26 passengers/ 1768 Kg (Bed Elevator), (G+ 4) stops , 5 STOP,rated speed adjustable up to 1.5 mtr /sec with 5 years comprehensive maintenance / DLP,With Machine room MR ),Honeycomb Finish S.S. Car and HoneycombS.S. Landing door (Complete Lift Should be Honeycomb Finish ),Control Panel should be Made of SS. Steel Honeycomb finish material. |
153 | 26 passengers/ 1768 Kg (Bed Elevator) , (G+ 1) stops , 2 STOP,rated speed adjustable up to 1 mtr /sec with 5 years comprehensive maintenance / DLP,With Machine room MR ),Honeycomb Finish S.S. Car and HoneycombS.S. Landing door (Complete Lift Should be Honeycomb Finish ),Control Panel should be Made of SS. Steel Honeycomb finish material. |
154 | BSR ITEM |
155 | P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. |
156 | 10.0 Sq.mm |
157 | 4 core |
158 | EXTERNAL SUBSTATION |
159 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU)manually operated in combination ofVCB modules andLoad Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer.The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feeder of RMU should have voltage presence indicator. . and compring offollowings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder ModulesAll the type test certificates as per IEC from Third partyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR |
160 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
161 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
162 | NON BSR : Supply installation testing & Commissioning of 1600 KVAstar ratedCopper wound distribution Transformer ( All the distribution transformer must be star rated as per notification of (BEE) ministry of power, Goverenment of India)of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled & as per BEE star level- 2 & BIS approved as per IS 2026-1977 & lossesas defined as per IS 1180 part I 2014. including standardaccessories like conservator, silica gel breather,Bucholz relay,radiator, fins, HT cable box & LT cable boxes, OLTC (+5% to - 15% @ 1.25%) with RTCC panel, temperature rise of 40 degree C in oil / 45 degree C in winding , ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953 , Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer complete in all respect.NABL accredeated/ CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge .Transformer must be tested from CTL test lab of discom (if reqd.) before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, CTL testing charges & Inspection charges shall be reimbursed by the department to the contractor as per actual expenditure. All as per approved by Engineer in charge. Make : Uttam Bharat / Danish / United / Verdhaman/RTS. |
163 | 1600 KVA |
164 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
165 | 11 KV End Termination Kit Indoor type |
166 | 3 core 240/300 Sq.mm |
167 | 11 KV End Termination Kit Outdoor type |
168 | 3 core 240/300 Sq.mm |
169 | 11 KV Straight Through JointKit |
170 | 3 core 240/300 Sq.mm |
171 | Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
172 | 3 core 300.0 Sq.mm |
173 | S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
174 | SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H & I |
175 | A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP(up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or aboverequired ) capable of taking 10% over loading for one hour after 12 hours of continuous operation.,Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber),up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required . |
176 | B)AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled |
177 | C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade. |
178 | D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity : |
179 | E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA. |
180 | F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department. |
181 | G) Servicing Contract of DG Set from OEM"s Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department. |
182 | H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. |
183 | I) DG set will be offered for Inspection and Testing at Manufacturer"s Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
184 | 500 KVA at 0.8 pf 415V 50Hz 3-? |
185 | Synchonisation Panel |
186 | NON BSR : SITC of Synchronisation cum AMF Controller suitable for for two no external source and three nos DG sets. |
187 | Suitable PLC for Syncronisation & AMF operation of three DG sets - 1 nos |
188 | Digital I/P module |
189 | Digital O/P module |
190 | Suitable slot I/O rack with power supply |
191 | Analouge I/P module |
192 | KW tranducer |
193 | EEPROM memory module |
194 | Phase angle tranducer |
195 | Operator interface 3" diagonal with key pad |
196 | Communication cable from Operator interface to PLC |
197 | Hooter for varios status annunciation |
198 | All the software required for proper operation |
199 | 1 KVA online UPS with half an hour battery (SMF) back up for start operation |
200 | SPARE SPACE |
201 | The panel should have sufficient space for expansion modules & required hardware for future expansion as per SLD. |
202 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
203 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
204 | (a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
205 | (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
206 | [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) |
207 | (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
208 | (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
209 | (f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra ) |
210 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
211 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
212 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
213 | Electrolytic grade Aluminium bus bar 6010 grade |
214 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
215 | Threephase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
216 | Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
217 | Ring type tape wound CT |
218 | C T Class 1, Ratio upto 150/5, Burden 5 VA |
219 | C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA |
220 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
221 | C T Class 1, Ratio 3200/5 to 4000/5, Burden 15 VA |
222 | Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
223 | Red/yellow/Green colour |
224 | Blue / white Colour |
225 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
226 | 3.3 KV,class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
227 | 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) |
228 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
229 | Heavy dutyThree phase 525V, 50 Hzcylindrical typecapacitor (Bank) |
230 | Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
231 | 12 to 14 stage |
232 | Providing & Fixing ofAC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
233 | 3 pole Power contactorswith following AC 3 Rating |
234 | 300 Amp |
235 | 4 pole Power contactorswith following AC 1 Rating |
236 | 63 Amp |
237 | Providing & Fixing of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
238 | up to 6 KVAR |
239 | 12.5 KVAR |
240 | 25.0 KVAR |
241 | 50.0 KVAR |
242 | 100 KVAR |
243 | Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
244 | One day & week reserve (Analog type ) |
245 | SITC ofDraw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existingLT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, Instantaneous , earth fault(LSIG) withseparate LED indication for each type of fault shall confirm to EMI/ EMC test , LCD/LEDdisplay, last 10 trip history, provision ofZSI, Communication, Power metering module, Thermal memory , trip free mechanisum , suitable for ambient 50 degree and utilization catagary B.In built electrical & mechanical anti pumping feature , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electricaloperation10000 upto 2000 A rating and 5,000 for 2500 A to 4000 A. including making connections, testingetc. as required. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR |
246 | Microprocessor based release Draw out type (Manual spring charged) 4 Pole |
247 | 1000 A Rating , 50 kA |
248 | 1600 A Rating ,50 kA |
249 | 2500 A Rating ,50 kA |
250 | Microprocessor based release Draw out type ( Motorised charging type ) 4 Pole |
251 | 800 A Rating ,50 kA |
252 | 2500 A Rating ,50 kA |
253 | Microprocessor based release Draw out type ( Motorised charging type ) 3Pole |
254 | 800 A Rating ,50 kA |
255 | Microprocessor based release Draw out type (Manual spring charged) 3 Pole |
256 | 1250 A Rating ,50 kA |
257 | Supply and fixing of following accessories for Air circuit breaker (ACB)compatible with MAin ACB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
258 | Shunt Trip Release |
259 | Under voltage Release |
260 | Microswitch for Indication |
261 | Auxiliary Contact 4 NO + 4 NC |
262 | Breaker Control Switch (TNC) |
263 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB)compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
264 | Extended Rotary Handle |
265 | Spreaders for 160A, 3 Pole MCCB |
266 | Spreaders for 160A, 4 Pole MCCB |
267 | Spreaders for 250A, 3 Pole MCCB |
268 | Spreaders for 250A, 4 Pole MCCB |
269 | Spreaders for 400A, 4Pole MCCB |
270 | Spreaders for 630A, 4Pole MCCB |
271 | Spreaders for 800A, 4Pole MCCB |
272 | Phase Barriers up to 630A, 3/4Pole MCCB |
273 | SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR |
274 | 3 pole MCCB With Thermal Magnetic release |
275 | 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
276 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
277 | 4 pole MCCB With Thermal Magnetic release |
278 | up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
279 | 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
280 | 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
281 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
282 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
283 | 4 pole MCCB With Microprocessor based release with adjustable O/L &S/C setting with Inbuilt Instantaneous and Ground fault Protection. |
284 | 630 Amp, 50 kA |
285 | 800 Amp , 50 kA |
286 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR |
287 | Single pole MCB (With B/C curve tripping Characteristics) |
288 | 6 A to 32 A rating |
289 | Four pole MCB (With B/C curve tripping Characteristics) |
290 | 6 A to 32 A rating |
291 | 50/63 A rating |
292 | Providing & Fixing ofCam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
293 | 10 AMP |
294 | Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % Detuned Reactors conforming to IEC 61558-2-20 & IEC 60076-6 Aluminium woundfor harmonics filter with 180% to 200 % Linearity, H - Class Insulation ( 180 degree C), high temp. Disconnection above 155 deg C., ambient temperature: +60 deg C. with thermal cut off switch in existing panel with following Capacitor ratings. including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
295 | 14 % (133 Hz) Aluminium wound Reactors |
296 | For 1 to 5 KVAR capacitor |
297 | 12.5KVAR |
298 | 25 KVAR |
299 | 50 KVAR |
300 | 100 KVAR |
301 | Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
302 | 125 A |
303 | 200 A |
304 | 400 A |
305 | 630 A |
306 | SITC of following capacity IK10Sandwich TypeRising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6standard & IS 8623 P-IIand Manufactured in India for use on 3 phase 4 wire, 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892,with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like(i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by OEM. |
307 | Routine test as per OEM"s QAP in It"s own Manufacturing facility in Indiashall be witnessed by department Engineer virtually / Physically.Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
308 | Sandwich Type Bus Rising Main |
309 | 400 amps 25 KA SC for 1 sec |
310 | 630 amps 40 KA SC for 1 sec |
311 | 800 amps 50 KA SC for 1 sec |
312 | Out Door Bus Duct IP66 with Canopy |
313 | 2500 Amps 80kA SC for 1 sec |
314 | SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable forSandwich / Compact Air Insulatedtype bus bar trunking Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but without MCB/MCCB/ACB) with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
315 | Plug in Box suitable for Sandwich Type Bus rising Main |
316 | 100/125 amps (Suitable for MCCB) without MCCB |
317 | 160/200/250 amps (Suitable for MCCB) without MCCB |
318 | 400 amps (Suitable for MCCB) without MCCB |
319 | 500 / 630 amps (Suitable for MCCB) without MCCB |
320 | SITC ofBus Rising Main OEM manufactured following capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB), Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
321 | For 400 Amp. (Without MCCB) |
322 | For 630 Amp. (Without MCCB) |
323 | For 800 Amp. (Without MCCB) |
324 | SITC ofBus Rising Main OEM manufacturedTinned copper flexible joint with enclosure of following capacity with Transformer / DG / Panelas required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
325 | 1000 Amp. Rating |
326 | 2500 Amp. |
327 | Supply, installation, testing & commissioning of the following: IGBT basedparallel True Online Double Conversion UPS suitable for unbalanced, 3 Phase input and 3 phase 415 V output UPS system with isolation transformer, suitable for operating in parallel and each comprising as per technical specification complete as required. |
328 | VRLA sealed maintenance free batteries forUPS system, for providing 30 minutes back upto eachUPS. Each bank of batteries shall comprise required Nos. ofSMF batteries etc as per specifications as required.(cost Included in above) |
329 | Matching cabinet to house SMF batteries for UPS system along with interconnecting links andI/c S/F MCCB as required.(Cost Included in above) Make:- Nemuric/ Eaton/ APC/Vertik |
330 | 10 KVA |
331 | 5 KVA |
332 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
333 | 8 SWG copper Wire |
334 | 50mm x 6mm copper strip |
335 | 25mm x 3mm G.I. ( Hot Dipped) Strip |
336 | 32mm x6mm G.I. ( Hot Dipped) Strip |
337 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
338 | Supply & Laying following size" B " class ,G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc.for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per pre approved by Engineer in charge.(Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annex ure "A" attached with this BSR . |
339 | 40 mm dia. |
340 | 50 mm dia. |
341 | Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
342 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
343 | (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts |
344 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
345 | (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. |
346 | (d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. |
347 | (e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
348 | 25 mm thick and 3 Mtr. Long |
349 | SUBHEAD-VI-L.V. CABLES |
350 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR |
351 | Un-armoured |
352 | 6.0 Sq. mm |
353 | 4 core |
354 | Armoured Cable |
355 | 6.0 Sq. mm |
356 | 4 core |
357 | 10.0 Sq. mm |
358 | 4 core |
359 | 16.0 Sq. mm |
360 | 4 core |
361 | 35.0 Sq. mm |
362 | 3.5 core |
363 | 50.0 Sq. mm |
364 | 3.5 core |
365 | 95.0 Sq. mm |
366 | 3.5 core |
367 | 150.0 Sq. mm |
368 | 3.5 core |
369 | 185.0 Sq. mm |
370 | 3.5 core |
371 | 300.0 Sq. mm |
372 | 3.5 core |
373 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArmouredCoppercable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withelectrolytic gradeCopper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie)includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure "A" attached with this BSR |
374 | 2.5 Sq. mm |
375 | 10 core |
376 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
377 | 4 x 6.0 sq.mm |
378 | 4 x 10.0 sq.mm |
379 | 4 x 16.0 sq.mm |
380 | 3.5 x 35.0 sq.mm |
381 | 3.5 x 50.0 sq.mm |
382 | 3.5 x 95.0 sq.mm |
383 | 3.5 x 120.0 sq.mm |
384 | 3.5 x 150.0 sq.mm |
385 | 3.5 x 185.0 sq.mm |
386 | 3.5 x 300.0 sq.mm |
387 | Supplying and makingend termination with heavy duty Copper lugs ( ANY type ) confirming toIS 8337 -1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
388 | 2.5 Sq.mm |
389 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
390 | 150mm x 50mm x 1.6mm |
391 | 300mm x 50mm x 1.6mm |
392 | 600mm x 62.5mm x 2.0mm |
393 | S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
394 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
395 | 50/55 mm |
396 | 110 / 95 mm |
397 | 160 / 136 mm |
398 | Providing and laying Non Pressure NP-3 classR.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth& Back filling with compaction is to be Paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
399 | 200 mm dia internal. |
400 | 300 mm dia internal. |
401 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
402 | M20 grade Nominal Mix 1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
403 | Earth work in excavation/ by mechanical means (Hydraulic Excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m , disposed earth to be levelled and neatly dressed: |
404 | Ordinary rock |
405 | Supply installation testing & Commissioning ofhigh mast lighting system (as per PLG 07of ILP UKtechinical report no7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstructionlights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required on Existing Foundation.(See table P - 03 for specs.) OEM Must haveType test certificate for wind tunnel test .All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
406 | 16.0 Mtr HM (in 2 section) suitable for 9 No. Luminaries |
407 | Providing & Fixing ofIK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles,of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K±355K.Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
408 | High Power LED Flood Light Minimum lumen output 18650 lm |
409 | Providing & Fixing of IK08IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece constructionpowder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser andAluminium anodised with sand blast reflector. The System level Luminous efficacy =100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA.Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
410 | Minimum lumen output 4000 lm Post top Luminarie |
411 | Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
412 | 4 Mtr. |
413 | Providing and Laying RCC Foundation for Octagonal/ Conical Street Light poles, High mast Poles as per Drawing attach at TableP-4with Following Procedure& All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
414 | A) Excavation of Pit for Foundation Size upto required depth from Ground level |
415 | B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. |
416 | C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness |
417 | D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. |
418 | E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal |
419 | F) Providing & Fixing of 2 no. Required SizePLB HDPE Pipe& Foundation Bolt with template as per OEM Recommendations. |
420 | G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. |
421 | H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
422 | Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. |
423 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
424 | Providing & Fixing of IK10IP65 protected 600 mm height LED Bollard Luminarie with base platemade of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy =90 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintainedLight output in Cool white or Warm White Colour as per engineers choice. driver current <750mA.Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
425 | Minimum lumen output 800 lmBollard |
426 | Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
427 | 7 Mtr. |
428 | Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
429 | Single arm overhang |
430 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
431 | LED Street Light fixture with Minimum lumen output 8700 lm |
432 | Providing and fixing of IP 65 protected Polycarbonate / Polysterene fuse box moulded with inside knock outs of following size with hinged cover, transparent window,PU gasket, locking arrangement, duly holded with 2 nos. pole clamps of 20 mm x 3 mm flat with nut and bolts, The box shall be provided with Din rail, 4 / 8 way 10.0 / 16.0sq.mm heavy duty connector, earth terminal,complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
433 | 175mm X 150mm X100mm |
434 | Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . |
435 | 32 mm Dia. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy