| 1 | Taking down copper/ aluminum point wiring for (light, fan, socket point 5/15 amps) complete including fitting such as switches, ceiling rose, light fittings, sockets, Lamp holder, ceiling roses etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surface of walls, floors etc all as specified and as directed by Engineer-in-charge. |
| 2 | Material and labour for point wiring with approved colour coded multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm, 1100 volts grade, two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm,1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in and including new concealed PVC conduit terminated on and including new modular sunken box of suitable size of frame, cover for mounting switches, socket and regulator fixed on surface flush with wall, comprising of One light/ bell/ buzzer point controlled by one switch or one fan point controlled by one switch & fan regulator complete all as specified and as directed by engineer-in-charge. |
| 3 | All as per serial item 02 here-in-before but for socket outlet, 3 pin 5 Amps on same board complete all as specified and as directed by engineer-in-charge. |
| 4 | All as per serial item 02 here-in-before but for socket outlet, 3 pin 6 Amps on independent board complete all as specified and as directed by engineer-in-charge. |
| 5 | All as per serial item 02 here-in-before but One socket outlet three pin, 6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSHcable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 6 | Point wiring with approved colour coded multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm, 1100 volts grade, with two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm, 1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in and including new concealed PVC conduit terminated on and including new steel sunken boxes 1.2mm thick covered with provision of 3mm thick plastic laminated sheet, comprising of One light/ bell/ buzzer point controlled by one switch or one fan point controlled by one switch & fan regulator complete all as specified and as directed by engineer-in-charge.Note: Quoted rate shall be inclusive of cutting chases in wall/ floor/ PCC and making good the disturbed surfaces to match the originalfinishes surface and nothing extra shall be paid on this account. |
| 7 | All as per serial item no. 06 here-in-before but for socket outlet 3 pin 6 Amps on same board complete all as specified and as directed by engineer-in-charge. |
| 8 | All as per serial item 06 here-in-before but for socket outlet 3 pin 6 Amps on independent board complete all as specified and as directed by engineer-in-charge. |
| 9 | All as per serial item 06 here-in-before but One socket outlet three pin, 6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSHcable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 10 | S&F modular switch one way 6 Amps, one module, 230 volts, single pole, complete all as specified and as directed by engineer-in-charge. |
| 11 | S&F modular switch one way, 16 Amps, one module, 230 volts, single pole complete all as specified and as directed by engineer-in-charge. |
| 12 | S&F modular socket outlet 2 in 1, 3/5 pin 6 Amps two module 230 volts complete all as specified and as directed by engineer-in-charge. |
| 13 | S&F modular socket outlet 2 in 1, 6/16 Amps, two module, 230 volts complete all as specified and as directed by engineer-in-charge. |
| 14 | S&F modular fan regulator, single pole, one module, 230 volts complete all as specified and as directed by engineer-in-charge. |
| 15 | S&F modular bell push, single pole, one module, 230 volts complete all as specified and as directed by engineer-in-charge. |
| 16 | S&F Switch, piano type, flush button type, single pole one way 5 Amps 230 volt complete all as specified and as directed by engineer-in-charge. |
| 17 | S&F Switch, piano type, flush button type, single pole one way, 15 Amps 230 volt complete all as specified and as directed by engineer-in-charge. |
| 18 | S&F ceiling rose, surface bakelite 65 x 50 mm dia, three terminal complete all as specified and as directed by engineer-in-charge. |
| 19 | S&F bell push, piano flush type, 6 Amps, single pole complete all as specified and as directed by engineer-in-charge. |
| 20 | S&F stepped type electronic fan regulator, piano flush type complete all as specified and as directed by engineer-in-charge. |
| 21 | S&F electric bell, AC 230 volt, single pole complete all as specified and as directed by engineer-in-charge. |
| 22 | S&F socket outlet 2 in 1, 3 pin 5 Amps, ISI marked, 230 volts complete all as specified and as directed by engineer-in-charge. |
| 23 | S&F socket outlet, 2 in 1, 3 pin 5/15 Amps, ISI marked, 230 volts complete all as specified and as directed by engineer-in-charge. |
| 24 | S&F Lamp holder insulated body PVC/ Polycarbonate type with backplate suitable for batten fitting complete all as specified and as directed by engineer-in-charge. |
| 25 | Disconnection and taking down old unserviceable MCB DB, junction box, panels of any size complete with all MCCB\"s, MCB\"s etc and removing from site, complete all as specified and as directed by engineer-in-charge. |
| 26 | S&F sheet metal enclosures for MCB DB, SPN, 240 volts, 2 way, single door fitted without bus bar complete all as specified and as directed by engineer-in-charge. |
| 27 | S&F sheet metal enclosures for MCB DB, SPN, 240 volts, 4 way, double door fitted with 200 amps bus bar, neutral link, earth bar and din ral complete all as specified and as directed by engineer-in-charge. |
| 28 | S&F sheet metal enclosures for MCB DB SPN 240 volts, 8 way, double door fitted with 200 amps bus bar, neutral link, earth bar and din ral complete all as specified and as directed by engineer-in-charge. |
| 29 | S&F sheet metal enclosures for MCB DB SPN 240 volts, 12 way, double door fitted with 200 amps bus bar, neutral link, earth bar and din ral complete all as specified and as directed by engineer-in-charge. |
| 30 | S&F MCCB 4 pole, 3 phase 415 volts of capacity 125 Amps, 16 KA with adjustable thermal and magnetic release complete with proper cooper thimble connection complete all as specified and as directed by engineer-in-charge. |
| 31 | S&F vertical TPN distribution board, double door, flush mounting with provision for MCCBs incomer upto 125 Amp, 415 volts & outgoing 4 way having IP-43 protection complete all as specified and as directed by engineer-in-charge. |
| 32 | S&F MCB, SPN, 32 Amp, 230 volts having breaking capacity 10KA \"C\" type complete all as specified and as directed by engineer-in-charge. |
| 33 | S&F MCB, SPN, 40 to 63 Amp, 230 volts having breaking capacity 10KA \"C\" type complete all as specified and as directed by engineer-in-charge. |
| 34 | S&F MCB, SP, 6 to 32 Amp, 230 volts having breaking capacity 10KA \"C\" type complete all as specified and as directed by engineer-in-charge. |
| 35 | S&F LED light fitting 1x 9W/ 1x 10W bulkhead luminaries including LED light driver connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by engineer-in-charge. |
| 36 | S&F SLIM LED batten with polycarbonate housing and diffuser with elegantly desinged end caps 1 x 20W, 220 V, AC connecting up with three core flexible of suitable size from ceiling rose complete all as specified and as directed by engineer-in-charge. |
| 37 | S&f LED Mirror light fitting, 10 watt with high output diffuser, 2 feet length, 220 volts, AC decorative box type with driver, holder incl LED tubelight connection up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by engineer-in-charge. |
| 38 | Disconnection and Taking down carefully copper/ aluminium sub main wiring including PVC conduit pipe of any size and any type complete all as specified and as directed by engineer-in-charge. |
| 39 | M&L of Sub main wiring with two runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 4.0 sqmm, LT, 1100V grade, down through and incl adequate sizes PVC non metallic conduit of 20mm/ appropriate dia with accessories and fittings and one run of 4.0 sq mm single core multi stranded copper conductor cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 40 | Note: 1. Two runs of cable, one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length.2. Cable required for connection to DBs shall deemed to be incl in the quoted rates and shall not be measured separately. 3. Earth wire shall run inside the conduit pipe. |
| 41 | M&L of Sub main wiring with two runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 6.0 sqmm, LT, 1100V grade, down through and incl adequate sizes PVC non metallic conduit of 20mm/ appropriate dia with accessories and fittings and one run of 6.0 sq mm single core multi stranded copper conductor cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 42 | Note: 1. Two runs of cable, one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length.2. Cable required for connection to DBs shall deemed to be incl in the quoted rates and shall not be measured separately. 3. Earth wire shall run inside the conduit pipe. |
| 43 | M&L of Sub main wiring with two runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 10.0 sqmm, LT, 1100V grade, down through and incl adequate sizes PVC non metallic conduit of 20mm/ appropriate dia with accessories and fittings and one run of 10.0 sq mm single core multi stranded copper conductor cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 44 | Note: 1. Two runs of cable, one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length.2. Cable required for connection to DBs shall deemed to be incl in the quoted rates and shall not be measured separately. 3. Earth wire shall run inside the conduit pipe. |
| 45 | M&L of Sub main wiring with four runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 10.0 sqmm, LT, 1100V grade, down through and incl adequate sizes PVC non metallic conduit of 20mm/ appropriate dia with accessories and fittings and one run of 10.0 sq mm single core multi stranded copper conductor cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge. |
| 46 | Note: 1. Four runs of cable, one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length.2. Cable required for connection to DBs shall deemed to be incl in the quoted rates and shall not be measured separately. 3. Earth wire shall run inside the conduit pipe. |
| 47 | Material and labour in replacement for fabrication, install, testing and commission ofwall mounted sheet metal busbar chamber, CPRI approved, grouted with nut and bolts (with proper locking arrangement and holes to distribute circuits) of size 600x 500x 300 mm with copper strip 40mm x6mm (04 Nos) of length 450mm with approved colour coded and PVC adhesive coated, IP-54 as per IS-13947 protection fixed on insulator with the help of nut/ bolts including provision of 10 Nos 08 mm dia hole with 8 mm dia 50 mm long nut/ bolts with 02 Nos of washer connected with 16 sqmm single core colour coding stranded copper cable with thimble/ lugs including one MCCB, 125 Amps, four pole 3 Phase 25 KA, 415 volt with adjustable thermal and megnetic release complete having adjustable type base frame and equal space around MCCB as incommer one No, making good distrubed surfaces to match with original complete all as specified and directed by Engr-in-Charge. |
| 48 | NOTE:- Contractor shall submit drawing of this panel to GE through Engr-in-Charge for approval before placing order for procurement. |
| 49 | Material and labour for fabrication, installation, testing and commission of wall mounted sheet metal busbar chamber, CPRI approved, grouted with nut and bolts (with proper locking arrangement and holes to distribute circuits) ofsize 500x 300x 200 mm with copper strip 40mm x 6mm (04 Nos) of length 400 mm with approved colour coded and PVC adhesive coated, IP-54 as per IS-13947 protection fixed on insulator with the help of nut/ bolts including provision of 6 Nos 08 mm dia hole with 8 mm dia 50 mm longnut/ bolts with 02 Nos of washer connected complete having adjustable type base frame and equal space around, making good distrubed surfaces to match with original complete all as specified and directed by Engr-in-Charge. |
| 50 | NOTE:- Contractor shall submit drawing of this panel to GE through Engr-in-Charge for approval before placing order for procurement. |
| 51 | M&L for earthing complete with galvanised steel eath plate electorde 600x 600x 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr below ground level) connected to galvanised earth lead wire 4 mm dia by means of GI bolts nuts, check nuts washer of galvanised iron or steel all as shown in electric plate No 5 of MES SSR Part-I and including excavation & earth work in any type of soil, disposal of soil,providing alternate layers of charcoal and common salt, construction of PCC earth chamber in mix (1:3:6) type C-Iwith 40 mm thick RCC 1:2:4 type B-1, cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering pipe of 20 mm dia GI light grade and 15 mm dia light grade pipe for earth lead protection and testing on completion, complete all as specified and as directed by engineer-in-charge. |
| 52 | Material & labour for earthing complete with galvanized steel earth plate electrode size 600x 600x 6.0 mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized including GI protection pipe light grade 40mm bore connected to main earth wire on pole light grade 20 mm bore connected to main earth wire on pole or control board or main switch and GI pipe mediumgrade 20mm bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:2:4 type B-1 20 mm graded stone aggregate excavation and earth work all as shown in electrical plate No 3 of MES Schedule part I of 2009 connected to earthing test point indicaed including testing on completion complete all as specified and as directed by engineer-in-charge. |
| 53 | Note: The quoted unit rate shall be including of protection pipe and GI strip 32x 6mm from top to earth plate up to 7.5 meters. |
| 54 | Supply, Install, testing and commmisoning of Sealed maintenance free chemical filled Earthing electrode, earthing electrode having following specifications :- (a) Diameter of the pipe-80 mm, thickness of the pipe-3.9 mm, Length of the pipe:- 3000 mm, Galvanised thickness:- 80-100 micron, Type of galvanising:- Hot dipped, Chemical used in the pipe:- High conductive and crystalline conductive mixture (CCM), Chemical approx weight:-12 kg.(b)ground back filled compound 50 kg as conformong to IS 3043, properly mixed the after all around the earthing electrode. (c) incl necessary boring in ground in any type of strata/soil and connecting to test point.(d) Construction of brick masonry earth pit of internal size 310 mm x 310 mm and 300 mm deep incl finishing work and fixing of CI cover as manufacturer specification complete all as specified and directed by engr-in-charge.(e) Testing for proper working. |
| 55 | S & F sheet metal enclosure of size of 900 x 600 x 200 mm with locking arrangement and provn of 4 nos of glass 75mm x 150mm size in front door for measuring meter reading flush to wall for fixing of 04 Nos energy meter including taking down carefully energy meter including connection complete all as specified and as directed by engineer-in-charge. |
| 56 | S&F LED street light fitting, 35 watt LED, 230 volts outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp including bracket up to 1.5 mtr length as per suitable for fitting including clamps, GI bracket with impact and corrosion resistant including thermal management in multiple cptics complete with IP 65/ 66 protection complete all as specified and as directed by engineer-in-charge. |
| 57 | Cutting chases in existing wall for laying of PVC conduits including making good disturbed surface of wall after concealing the conduit inwall complete all as specified and as directed by engineer-in-charge. |
| 58 | Supply and fixing copper strip 20 x 3.15 mm laid on wall/ floor/ ground complete all as specified and as directed by engineer-in-charge. |