Tender For Renovation Of Electrical Work To Be Carried Out In Room No. 202, 115, 101, Toilet, Corridor At Department Of Environmental Studies, University Of Delhi, Delhi-Delhi

Delhi University has published Tender For Renovation Of Electrical Work To Be Carried Out In Room No. 202, 115, 101, Toilet, Corridor At Department Of Environmental Studies, University Of Delhi. Submission Date for this Tender is 20-03-2024. Electrical Maintenance Tenders in Delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

42882846
Tender For Renovation Of Electrical Work To Be Carried Out In Room No. 202, 115, 101, Toilet, Corridor At Department Of Environmental Studies, University Of Delhi
Open Tender
Indian
Delhi
Delhi
20-03-2024

Tender Details

Renovation Of Electrical Work To Be Carried Out In Room No. 202, 115, 101, Toilet, Corridor At Department Of Environmental Studies, University Of Delhi

Key Value

Document Fees
INR 500 /-
EMD
INR 19283.0 /-
Tender Value
INR 9.64 Lakhs /-

BOQ Items

Name of Work:Renovation of electrical work to be carried out in room no. 202, 115, 101, toilet, corridor at Department of Environmental Studies, University of Delhi
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
2Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
3Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.
46 Module
512 Module
6S/D the following size FRLS of PVC insulated copper conductor cable in the existing surface/recess PVC conduit as required.
71 x 1.5 sq.mm
82 x 2.5 sq mm
92 x 4 sq.mm
102 x 6 sq.mm
11Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 4 X 10 sq. mm + 2 X 10 sq. mm earth wire
12Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
1315/16 amps switch
146 pin 15/16 amps socket outlet
155/6 amps switch
163 pin 5/6 amps socket outlet
17Supplying and fixing of following sizes of medium class PVC conduit /batten along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
18(a) 25 mm
19(b) 20 mm
20Supplying and fixing suitable size G.I. box with modular plate and cover in front or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB "C" curve including connections, painting etc. as required.
21Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 12 way (4 + 36), double door
22Supplying and fixing 5 amps to 32 amps rating,240/415 colts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections testing and commissioning etc.as required single pole.
23Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
24Rewiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC Insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling as required. Group C.
25Supply, installation, testing and commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Moter, Class of Insulation: B, 3 Nos. Blades, 30 cm long down rod, 2 nos. conopies, shackle kit, safety rope, copper winding, power Factor not less than 0.9, service Value (CMM/W) minimum 6.85, Air Delivery minimum 215 CMM, 350 RPM (Tolerance as per IS:374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temprature rise= 75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230V, 50 Hz, single phase AC supply, earthing etc. complete as required. (2 years warranty)
26S/F/ testing & commissioning of LED fitting single box type fitting (1x20 watts) complete with all accessories and tube etc. directly on ceiling or wall i/c connection with 1.5 sqmm FR PVC copper cond. Cable etc. as required. (Model No. TMC 501 1xT-LED 22W P3241) (Make Philips)
27S/F/ testing & commissioning of LED fitting single box type fitting (2x20 watts) complete with all accessories and tube etc. directly on ceiling or wall i/c connection with 1.5 sqmm FR PVC copper cond. Cable etc. as required. (Model No. TMC 501 2xT-LED 22W P3242) (Make Philips)
28S/F DLP UPVC trunking compartment with cover clip on separates partition left right top internal angle, flat angle, raise function, flat function cover to body joints mosaic clip & support from mosaic isolation bracket 2 mm thick plastic (Legrand)
29105mm x50 mm with all accessories
3080mm x50 mm with all accessories
31Supplying, fixing and laying of one number PVC insulated and PVC sheathed/ XLPE aluminium armoured conductor power cable confirming to 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering, refilling the same etc. as required.
323½ X 150 sq. mm
333X 6 sq. mm
34P/F , installation, testing and commissioning of followig MCCB AC supply complete with connection in the suitable enclosure etc. as required at site. (L &T)
35200 amps MCCB 3 pole 50 KA
36100 amps MCCB 3 pole 35 KA
37Servicing/ cleaning/ meggering/ checking of load balancing/ checking with ton tester of existing panel i/c removing the dust and carbonized and dress up the hanging wire along with thimble if necessary etc. as required at site.
38Supplying & fixing of following flood light fitting5700K pressured dia cast housing with IP65 protection efficient high 220v-240v output emitter LED for better distribution with dimension and all accessories etc. as required at 120 watts (Model No. BVP410 LED 120 CW HE NB FG S4 XTFCL) (Philips) site.
39S/F street light pole box of size 8"x10" complete all accessories i/c suitable clamps suitable bakelite sheet, brass screws, washers and 1 Nos. SP MCB of 10 amps capacity i/c making connections etc. as required.
40Supplying and fixing of Exhaust fan 15" 900 RPM with all accessories and making connection etc. as required at site. If wooden work is required. (Crompton)
41Supplying and fixing of fan hook for the ceiling fan i/c drilling the hole and making connection etc. as requied at site.