Tender For Supply, Installation, Testing, Commissioning Of Hvac, Fire Fighting, Lift, Mgps, External Electrical Work Etc. Of Medical Hospital, Banswara, banswara-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Supply, Installation, Testing, Commissioning Of Hvac, Fire Fighting, Lift, Mgps, External Electrical Work Etc. Of Medical Hospital, Banswara. Submission Date for this Tender is 21-03-2024. Electrical Maintenance Tenders in banswara Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42828978
Tender For Supply, Installation, Testing, Commissioning Of Hvac, Fire Fighting, Lift, Mgps, External Electrical Work Etc. Of Medical Hospital, Banswara
Open Tender
Indian
Rajasthan
banswara
21-03-2024

Tender Details

Tender For Supply, Installation, Testing, Commissioning Of Hvac, Fire Fighting, Lift, Mgps, External Electrical Work Etc. Of Medical Hospital, Banswara

Key Value

Document Fees
INR 11800 /-
EMD
INR 2820000.0 /-
Tender Value
INR 14.10 Crore /-

BOQ Items

Name of Work : - SITC of HVAC, Fire Fighting, Lift, MGPS, External Electrical work etc. of Medical Hospital, Banswara
Sl. No. Item Description
1FIRE FIGHTING PUMPS
2Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H.
3(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
4(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
5(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
6(D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
7( E)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads.
8(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works inPhysical presence of Department’s representatives.
9(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
10(H)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
112280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM
12Supplying, Installation, Testing & Commissioning ofDiesel Engine Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H.
13(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
14(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
15(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
16(D) Heat Exchanger cooled Diesel Engineas per NFPA 20 developing suitable BHP for the below mentioned dischargeat 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank.
17(E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine System Controller in Existing Fire Fighting Control panel
18(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives.
19(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
20(H) Pump to be placed on Suitable size Existing Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
212280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 1800 / 2300 RPM
22Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Jockey pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E,F and G
23(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
24(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
25(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
26(D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads.
27(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.
28(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
29(G)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
30180 LPM suitable for 70 Mtr Single Stage
31Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Terrace pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H.
32(A) Horizontal End suction Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
33(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
34(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
35(D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads.
36(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.
37(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
38(G) Suitable size Reinforced cementconcreat (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra )
39(H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to protect it from weather All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
40450 LPM with 35 mtr head
41Supplying, Installation, Testing & Commissioningsubmersible type dewatering pump of stainless steel casing and Norylimpellorof discharge and head given below complete withall accessories suitable for operation on 230 V, single phase/415 V /3 phase, 50 Hz. AC supply complete with starter for automatic operation including water level sensing device / float switchinter connection with submersible cable etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
42180 LPM with 10 mtr head
43SITC of pressure switches ofpressure range 3 to 15 Bar for Main, Jockey, Terrace pumpandDiesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
44SITC of UL listed / FM Approved Brass Test and drain valve assembly for sprinkler system comprising of 3-position ( off, test and Drain ) ball valves with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI and Inbuilt sight glass etc. as required of following size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4525 mm Dia.
46SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Staticpressure rating up to 250 PSIin cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
47150 mm Dia.
48Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C " class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applicationsincluding cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of requiredshade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4925 mm dia
5032 mm dia
5140mm dia
5250mm dia
5365 mm dia
5480 mm dia
55100 mm dia
56150 mm dia
57200 mm dia, 6.0 mm thick
58250 mm dia, 6.35 mm thick
59Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C" class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supportsincluding cutting,welding etc & forged steel fittings like elbows, tees,tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
6080 mm dia
61100 mm dia
62150 mm dia
63Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height withflanged connection,Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
64Supplying and fixing cylindrical air vessel of continuous welded constructionfixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height withflanged connection, Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
65Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holesin existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick),nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
66150 mm dia
67200 mm dia
68Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
69100 mm dia
70150 mmdia
71200 mm dia
72Supplying and Fixing of PN 1.6Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
7380 mm dia
74100mmdia
75150mm dia
76200mm dia Gear Operated
77Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
7825 mm dia.
7950 mm dia
80SITC of installation control valve of cast iron body and brass/bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continous alarm when the wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
81150 mm
82Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick),nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
83Single Headed with 75 mm Dia. Flanged Inlet
84Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
85Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A)63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304male and female couplings(IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.
86Supplying & fixing SS-304 Short Branch Pipeconforming to IS: 903:93 fitted with 20mm (nominal internal diameter)bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
87Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required.(A) Thermoplastic / Rubber Hose(B)20 mmdia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall.(D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
88With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969and Bursting pressure 42 Kg/sqcm
89Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valvecomplete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following Ways. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
904 Way
91Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection)for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
92Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheetDuly powder coated in red color externally and white internally with 6 mm thick glazeddoors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
93Providing and fixing of Fire / Electrical Shaft Door made frompowder coated (50 Micron) aluminiumpartialy glazed with 6 mm thick glass and Partialy/ Fully Louvered with Outer frame of AluminiumSection of Size 100 mm x 45 mm x 1.5 mmand Shutter"s Top, Middle & sideSection of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mmComplete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
94Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler headswith Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
95Pendant/ Upright type
96Sidewall Sprinklers (ordinary)
97Extended Throw Sidewall type .
98Providing & fixing of UL listed 1.5 mm thick chrome plated Dual type MS Escutcheon platesfixed at junction of Sprinkler piping with the false ceiling. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
99Supply & Fixing of Fire Man"s Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
100Providing & fixingsprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1011000 mm Long
102Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cmwith 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, dulycalibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS PipeEtc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
103Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
104Capacity 4.5 Kg.
105Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1066 kg
107Supply & Fixing of Water + AFFF 6%Mechanical Foam typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
108Capacity - 9 Ltrs.
109Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Double mounted handle as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
110Supply & Fixing of Ceiling mounted UL listed clean Agent (HFC-236fa), Modular typeFire Extinguisher , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Fixed Bulb with Temerature 68 deg C, QR code for Product Traceability including Fixing on Ceiling with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1115 Kg Capacity
11210 Kg Capacity
113Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
11450 mm dia per running inch length
115100 mm dia per running inch length
116150 mm dia per running inch length
117200 mm dia per running inch length
118Non BSR Items
119Supply of strong rope ladder made from 18-20 mm dia Nylone/Polypropylene (PP) rope,with 20-25 mm solid wooden/aluminium rung of length 330-370 mm and span of 370-450 mm and loading capacity of 500 kg and loading of rung with 200 kg of following length
12030 meter
121SITC offloor mounted dust and vermin proof compartmentalisedcubical type main fire pump house panel made out of CRCA sheet , required hardware,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shadeThe panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear. Thickness of sheet shallnot be less than 1.6 mm up to 600 mm length / widthof any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall beof 2.0 mmthick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below:
122Incomer
123630 Amp. FP MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release,Digital Ammeter, Voltmeter, CT, Indicating Lamps, 900 AmpsAlum. Bus bar with with heat shrinkable sleeves.
124Out going
125(a) 400 Amp. TPN MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. DOL Starter of 100-125 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets
126(b) 100 Amp. TPN MCCB, 16 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. DOL Starter of15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Set
127© One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter
128(d) System controller to control Operation Main Electric pumps (two no), Diesel pump, jockey pump in sequence as per specs. Consisting of relays, timers, NO / NC contacts etc as required. Make:- Engineers & Engineerrs, Advance, Jhons Electrical, Milestone, Ankit Electricals
129Non BSR Items
130Providing, fixing, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges.It should be complete as per manufacturer"s specifications & as directed by Engineer- in-charge Make:- Danfoss, Resistoflex, EasyFlex
131200 mm dia
132150 mm dia
133100 mm dia
134HVAC
135Non BSR Items : Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge. Make:- Daikin/ Bluestar/ LG/ Hitachi/ OG/ Mistubushi
1360.8-1.0 TR ISEER not less then 4.6
1371.3-1.5 TR ISEER not less then 4.6
1381.6-1.8 TR ISEER not less then 4.6
139SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
140Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
14120 mm
14225 mm
14332 mm
144Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
145Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1464 core x 2.5 Sq.mm
147Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive)& fabricated as perIS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1480.60 mm
1490.80mm
1501.00mm
1511.25mm
152Supply , Installation, Testing and Comissioning of site fabricated ducting made from aluminium sheet conforming to IS:737, Grade 31000fabricated as perIS:655 and as per approved drawings & designs including the cost of hangers, supports , angle , expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1530.60 mm
1540.80mm
155SITCof air cooled ducted splittype air conditioning machine with each having a capacity and details as mentioned below suitable for operation on factory chargedR-32/R-410A Green refrigerant comprising ofScroll /rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system,Suitable capacity squirrel cage induction motor with class "B" insulation suitable for operation on sigle / three phase supply, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers,Microprocessor based control panel complete with accessories, machine isolation / disconnect switch, valves and accessories to inter connect compressor and condender including pressure testing, vacuum.Necessary starters suitable for Indoor & outdoor unit complete with O/L , U/V, phase reversal protection,single phase preventors etc complete as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1568.5 TR
15711 TR
158Supply and Installation of Box type EU13 Hepa Filter of 99.997% efficiency down to 0.3 micron particle size installed in zero leakage Aluminium frame as per ISO 14644-1 clean room including sealing and packing material cost like silicon and hardware cost and Labour cost. NABL accredeated/ appropriated lab testing reportswith OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
159305 mm Thick
160Supply and fixing of acoustic lining of ducts withchemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm,including cost of adhesive etc. complete in all respect.All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
16110 mm thick
162NON BSR ITEMS
163Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified "Class O" in Fire Propagationas per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required.All as per pre approved by Engineer in charge.Make:- Aflex, kflex, supreme, Armacell
16419mm thick for Outdoor Application withAluminium Foil
165Supplying, installing, testing and balancing ofextruded Aluminium Powder coated supply/returnGrilles with fixed bars at fronthaving 0 / 15 / 30 / 45 degrees deflection as required. with Flange size 20 mm with rounded edges including fixing with steel screws etc. complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
166Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
167Supply , installation, testing & balancing of 20 Gauge G I Damper with brass bushes and 6" pitch multiblade box type galvanised sheet steel construction volume control damper for Ducting and air washers to be provided with suitable links and quadrants for control of volume of air as per specifications complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
168Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
16950 mm dia per running inch length
170100 mm dia per running inch length
171150 mm dia per running inch length
172200 mm dia per running inch length
173P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibrationwith GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etcas required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
174Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
175Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
176150mm x 50mm x 1.6mm
177300mm x 50mm x 1.6mm
178450mm x 50mm x 2.0mm
179Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
18025.0 Sq. mm
1813.5 core
18216.0 Sq. mm
1834 core
18410.0 Sq. mm
1854 core
1866.0 Sq. mm
1874 core
188Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1894 x 6.0 sq.mm
1904 x 10.0 sq.mm
1914 x 16.0 sq.mm
1923.5 x 25.0 sq.mm
193Non BSR ITems: Supplying, installing, and testing of AL volume control damper within ducts to be provided with levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system, Frame of the VCD shall be constructed from 18 gauge sheet & bladesshall be constructed from 20 gauge sheet Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
194Non BSR ITems: SITC of Digitalthermostat with cooling & heating mode including necessary control wiring to maintain the inside design condition as required Make:- Simens , Honeywell, Belimo
195Non BSR ITems: Supplying, installation, testing and commissioning of fire dampers, the blades and frame shall be min. 1.6 mm thick GI and factory fitted in a sleeve made out of 1.6 mm thick GI of min. 400 mm long, as & where required, of required sizes including control wiring. The damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal. CBRI tested and certified for 90 minute fire rating etc. complete as required and as per specifications. (Total assembly should be UL listed)Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
196Fire Damper
197Actuator
198Non BSR ITems: Supply, installation testing, commissioning and validation of Laminar Flow Units (LFU) comprising of Terminal EU 13 HEPA Filters of 99.997% Efficiency down to 0.3 Micron particle size installed in zero leakage Al frame with Al perforated plate type Al grille with Al VCD, LFD laminar flow diffusers are constructed from 18 swg aluminium sheet, perforated face with approx. 50% perforation od size 900x600mm-6nos, 600x600mm-3nos, including the cost of supply air 18 gauge Al plinum of size 8"x6"x1.5"/2", including all connection complete in all respect. Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
199LFU Size : 2400 x 1800 mm ( +/- 100mm )
200Non BSR ITems:SITC of Analogue, Megnehelic Differential Pressure Gages, Die Cast Al. case, 4" dial face, Zero Center Range 30-0-30 Pa with SS Boxes Breathing Pipe & Standard accessories.
201Non BSR ITems:SITC of 2.0 mm thick (both base & cover) GI sheet raceway for copper piping from outdoor unit to shaft, The raceway shall be fixed on the floor with the help of suitable size galvanized MS angle support at 8" distance as approved from engineer incharge of size 400mm x 150mm.
202Non BSR ITems:SITC of air cooled ducted splitair conditioning machine with each having a capacity and details as mentioned below suitable for operation on refrigerant comprising of Scroll / Rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class "B" insulation suitable for operation on 415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers,Microprocessor based control panel complete with accessories, machine isolation / disconnect switch as per specifications, Suction line insulation with minimum 19 mm thick polyvinyl rubber insulation,valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Pipe shall be hard drawn copper, Necessary starters suitable for compressor motor complete with O/L , U/V, phase reversal protection,single phase preventors etc complete as required.(Make: Daikin, Hitachi, Toshiba,Mitshibushi, Bluestar,LG)
203CONDENSING SPLIT AC - 11 TR CAPACITY,WITH R-410 (SINGLE CIRCUIT)
204CONDENSING SPLIT AC - 8.5 TR CAPACITY, WITH R-410 (Single CIRCUIT)
205Non BSR ITems:Supplying, installing, testing and commissioningof double skin construction Air Handling Units as per specification.All AHU"s shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working+ one standby) DX coil of coppertube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backwardcurve fan(s), beltdrive, vibrationisolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive. VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM.The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kitof following capacities. (Make: Zeco/ Edgetech/Systemaire)
2063000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER
207Non BSR ITems: Supplying, installing, testing and commissioningof double skin construction Air Handling Units as per specification.All AHU"s shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working+ one standby) DX coil of coppertube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backwardcurve fan(s), beltdrive, vibrationisolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive with sequential relay for sequential operation of outdoor units . VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM.The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kitof following capacities.(Make: Zeco/ Edgetech/Systemaire)
2083000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER HEPA FILTER
2092500 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER, HEPA FILTER
210Non BSR ITems: Supply, Installation, testing and Commissioning of accoustically insulated ceiling / floor mounted Rectangular box type/circulartype Inline fan, for toilet exhaust , ward normal exhaust constructed of GSS duly powder coatedas per detailed specifications, completewith forward curved SISW fan, motor and drive suitable for 220 ± 10% volts, 1 phase, 50 Hz A.C supply, with necessary canvas connection etc complete in all respects.Make :- Kurger/ Nikotra/ Airflow/ Greeneck/Otemberg/ sphere
211500 cfm at 15 mm static
212200-300 cfm at 15 mm static
213S.I.T.C. 150 MM DIA of an Exhaust valve/Disc Valve Manufactured from Sheet metal Dully powder coated/re-cyclabe polypropelene. The device should have lockable central cone which should be rotatable to adjust pressure & the Air Volume.Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
214LIFT
215Supplying , installation , Testing and commissioning of the Passenger having following main features:
216(a)MOTOR : Gearlesslift drivecomprising of high starting torque lift duty , 3 phase 440 Volts A.C. permanent magnetic synchronous motor (Located on shaft on top of guide rail ) of proper rating with high efficiency shall be used.
217(b) Operation / Drive : Microcessor based /PLC, AC Variable Voltagevariable frequency variable speed (V3F) vector control drive with encoder feedbackfeedback closed loop system shall be used for lift car and door operationwhich shall be full collective selective operation hall call demand response , UP/Down hall stops , main , Up/Down contactor with overload and phase reversal relay and safety controls .
218( c ) Traction Media: main hoist flat coated steel belt / rope . Thimbles of spring permit adjustment of uniform tension for smooth operation of the elevator Pulse belt monitoring system to avoid the cut in the belt.
219(d) Car :car should be with M S platform with bracings of adquate size and to sustain the impact load cabin plus passengers with safety factor of fire for steel withAnti skid PVC flooring / Granite flooring and side panels should be of Stainless steel with honey comb finish of sheet of grade 304 duty or higher with S.S. handrails . Car ceiling shall be steel finish with aesthetic appearances with LED ceiling lights (Ceiling light should be diffuser type) .The size of the car shall be taken as per available lift well size and relevant BIS code of lifts . Car panel will also be ofS S 304 or higher gradefinished with emergency stop device , emergency alarm,mechanical door safety device ,full length infra-red curtain in car door , facility of auto/attended mode . All car panel buttons and all floor switches must be with brail language as per lift act. Agency shall also provide & install one No. 2 MP , IR , IP based ceiling mounted Dome Camerain the car complete with connecting cables & accessories (To be connected with existing CCTV system in the Building by lift agency) .The inspection unit shall be provided at the top of the car.
220(e)Landing Doors : All landing door shall be fully automatic centre openingmade of honeycomb finish stainless steel grade 304 or higher with key holes and infrared curtains with unlocking facility from outside. The landing door should be fire rated (120 minuts)
221(f) Emergency light: Appropriate rechargeable battery operated LED emergency light in the car and along with alarm switch shall be provided.
222(g) ARD: Automatic rescue Device (ARD) shall be provided according to passenger capacity with SMF batteries of approved brands as per BSR.
223(h) Audio-Visual Indication : Audio visual indication in the lift car, showing over loadingsuch that doors kept open till excess load is removed.
224(i) Scrolling Indicators: LED TYPE dot matrixscrolling indicator system for up-down arrow with floor position indicator shall be provided inside the car and at all stops/floors.
225(j) Buffers : Spring buffers/PU Buffers shall be provided.
226(k) Car Fan :ENERGY EFFICIENT cross flow Car fan/blower with automatic sleep timer shall be provided.
227(l) Voice Annunciator: Voice annunciator with suitable music shall be provided in lift car.
228(m) Self diagnostics system for operational and safety parameters shall be provided in control panel .
229(n) Mechanical/Electronic over speed governor , door key holes in the floor doors, fireman switchshall be provided .
230(o) Lift machine hoisting arrangement in the lift machine room , Cast Iron counter balance to promote smooth and economic operation complete withfor the car & counter weight ,Trap Door , Lifting hooks as requiredand monkey ladders for lift pit should be provided by theagency along withall other steel structure works , foundations for the machine etc as required
231(p) Permanent wiring in lift machine roomand in lift well with providing and fixing of electrical distiribution boardcomplete with SP ,RCCB,TP/FP MCB"s etc , proper numbers of light points, with LED fixtures , exhaust fan , 2 nos copperplate /chemical earthing with 8 SWG copper earth wire and plug points shall be provided by the agency .
232(q) All civil work related to installation of lift like finishing , cleaning and levellingof lift pit , white wash of lift welland in machine room shall be done by the lift erecting agency without any extra cost.
233( s) Agency has to provide all working drawings and documents to comply latest BIS specifications and make proper liasion services for obtaining all necessary permissions.Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Kruppand Equivelent Make as per Annx.
23426 passengers/ 1768 Kg, (B+G+ 3) stops , 5 STOP,rated speed adjustable up to 1.5 mtr /sec with 5 years comprehensive maintenance / DLP,With Machine room MR ),Honeycomb Finish S.S. Car and HoneycombS.S. Landing door (Complete Lift Should be Honeycomb Finish ),Control Panel should be Made of SS. Steel Honeycomb finish material.
235BSR ITEM
236P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size.
23710.0 Sq.mm
2384 core
239INTERNAL FIXTURES
240Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2411200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
242Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts,making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
243750 mm sweep With three speed regulator
244Non BSR ITems: Supply, installation, testing & commissioning of Wall mounted Led Patient Bed light IP20 consuming a total system wattage of 31W with options of glare free downlight for reading and examination, up light for ambient lighting delivering an initial system lumen of 2533 lumens. Housing: non corrosive Extruded Aluminium with extruded ribbed translucence PMMA diffuser and self illuminated rocker switches. The luminaire shall have variable adjustment 10W Upward, 20W downward and 0.5W LED Bulb for generating multiple lighting modes as per the needs of Patient and doctor as well. The luminaire shall have optional suspended remote power switch for easy use in case of critical patrient care. The operating CCT shall be 5700K with CRI of =80. The luminaire shall be with electronic driver with input voltage range of 150 to 270V ,PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture Make:- Wipro/ Crompton/Havells/Philiphs
245Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
246OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
247Recessed/Surface Mounting
248Minimumlumen output 650 lm
249Minimumlumen output 1300 lm
250Minimumlumen output 1950 lm
251Minimumlumen output2400 lm
252Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
253OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
254Minimum lumen output 4200 lm
255EXTERNAL SUBSTATION
256SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H & I
257A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP(up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or aboverequired ) capable of taking 10% over loading for one hour after 12 hours of continuous operation.,Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber),up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required .
258B)AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled
259C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade.
260D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :
261E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA.
262F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.
263G) Servicing Contract of DG Set from OEM"s Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department.
264H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration.
265I) DG set will be offered for Inspection and Testing at Manufacturer"s Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
266500 KVA at 0.8 pf 415V 50Hz 3-?
267SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU)manually operated in combination ofVCB modules andLoad Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer.The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feeder of RMU should have voltage presence indicator. . and compring offollowings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder ModulesAll the type test certificates as per IEC from Third partyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR
268Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch
269Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch
270Non BSR Items
271Supply installation testing & Commissioning of star ratedCopper wound distribution Transformer ( All the distribution transformer must be star rated as per notification of (BEE) ministry of power, Goverenment of India)of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled & as per BEE star level- 2 & BIS approved as per IS 2026-1977 & lossesas defined as per IS 1180 part I 2014. including standardaccessories like conservator, silica gel breather,Bucholz relay,radiator, fins, HT cable box & LT cable boxes, OLTC (+10% to - 10% @ 1.25%) with RTCC panel, temperature rise of 40 degree C in oil / 45 degree C in winding , ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953 , Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer complete in all respect.NABL accredeated/ CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge .Transformer must be tested from CTL test lab of discom (if reqd.) before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, CTL testing charges & Inspection charges shall be reimbursed by the department to the contractor as per actual expenditure. All as per approved by Engineer in charge.
2722000 KVA
273Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
27411 KV End Termination Kit Indoor type
2753 core 240/300 Sq.mm
27611 KV End Termination Kit Outdoor type
2773 core 240/300 Sq.mm
27811 KV Straight Through JointKit
2793 core 240/300 Sq.mm
280Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2813 core 300.0 Sq.mm
282S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
283Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
284(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
285(b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
286© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
287(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
288(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
289(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
29025 mm thick and 3 Mtr. Long
291Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
29250mm x 6mm tinned copper strip
29332mm x6mm G.I. ( Hot Dipped) Strip
29450mm x 6mm G.I. ( Hot Dipped) Strip
295Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2968 SWG tinned copper Wire
297Non BSR Items
298S & Laying following size earth wire/strip of 1.5 mtr length for connecting earth strip of DG netural terminal including riveting, soldering, saddles, making connection etc. as required.
29950mm x 6mm flexible copper strip
300Non BSR ITems: Supply,installation &, laying of effecting proper connections, testing and commissioning of the following sizes of 1.1 KV grade PVC insulated copper conductor armoured stranded control cable complete as required and as per specifications. of RR kable , Unistar, Havell"s, Kei, Finolex make.
3018 core x 1.5 sq. mm cable
302Non BSR ITems: SITC ofmaking terminal joints for the following sizes of 1.1 KV PVC insulated Copper conductor cable including providing tinned copper terminal lugs, double compression brass cable glands, insulation tape, effecting terminal connections to the equipment complete as required.
3038 core x 1.5 sq. mm cable termination
304Non BSR ITems: Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications includingcutting,welding etc & fittings like elbows,flanges, tapers, reducer, gaskets, flexible below etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool as per IS : 8183-1993 (64 kg/m3 density) & 26 SWG aluminium sheet claddings etc complete as required complete in all respect.(Cost of Steel Structure for Exhaust pipe will be paid Extra). of Tata, Jindal , Surya make.
305250 mm dia
306Non BSR ITems: SITC of following capacity IK10Sandwich TypeRising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6standard & IS 8623 P-IIand Manufactured in India for use on 3 phase 4 wire, 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892,with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like(i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by OEM.
307Routine test as per OEM"s QAP in It"s own Manufacturing facility in Indiashall be witnessed by department Engineer virtually / Physically.Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
308Sandwich Type Bus Rising Main
309630 amps 40 KA SC for 1 sec
3101000 amps 50 KA SC for 1 sec
3111600 amps 50 KA SC for 1 sec
312SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable forSandwich / Compact Air Insulatedtype bus bar trunking Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but without MCB/MCCB/ACB) with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
313Plug in Box suitable for Sandwich Type Bus rising Main
314100/125 amps (Suitable for MCCB) without MCCB
315160/200/250 amps (Suitable for MCCB) without MCCB
316400 amps (Suitable for MCCB) without MCCB
317SITC ofBus Rising Main OEM manufactured following capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB), Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
318For 630 Amp. (Without MCCB)
319For 1000/1250 Amp. (Without ACB)
320For 1600 Amp. (Without ACB)
321SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3224 pole MCCB With Thermal Magnetic release
323125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
324250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
325400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
326630 Amp , 50 kA, adjustable O/L & adjustable S/C setting,
327SITC ofDraw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existingLT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, Instantaneous , earth fault(LSIG) withseparate LED indication for each type of fault shall confirm to EMI/ EMC test , LCD/LEDdisplay, last 10 trip history, provision ofZSI, Communication, Power metering module, Thermal memory , trip free mechanisum , suitable for ambient 50 degree and utilization catagary B.In built electrical & mechanical anti pumping feature , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electricaloperation10000 upto 2000 A rating and 5,000 for 2500 A to 4000 A. including making connections, testingetc. as required. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
328Microprocessor based release Draw out type (Manual spring charged) 4 Pole
3291000 A Rating , 50 kA
3301600 A Rating ,50 kA
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail