Tender For Electrification Work In Stadium At Salasar Distt Churu, sujangarh-Rajasthan

Public Works Department-PWD has published Tender For Electrification Work In Stadium At Salasar Distt Churu. Submission Date for this Tender is 12-03-2024. Electrification Work Tenders in sujangarh Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42823613
Tender For Electrification Work In Stadium At Salasar Distt Churu
Open Tender
Indian
Rajasthan
sujangarh
12-03-2024

Tender Details

Tender For Electrification Work In Stadium At Salasar Distt Churu

Key Value

Document Fees
INR 500 /-
EMD
INR 12000.0 /-
Tender Value
INR 6 Lakhs /-

BOQ Items

Name of Work: Electrification work in Stadium at Salasar Distt Churu
Sl. No. Item Description
1Electrification work in Stadium at Salasar Distt Churu
2Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3Short point (up to 3 mtr.)
4Medium point (up to 6 mtr.)
5Long point(up to 10 mtr.)
6Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
7On board
8S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
920 mm
10Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
112 x 2.5 sq. mm. + 1x1.5sqmm
122 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
13Supply and laying PVC Insulated and PVC Round Sheathed Multi Core copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen freefor less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
141.5 sq.mm x 3 core
15Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
16Single pole MCB (With B/C curve tripping Characteristics)
176 A to 32 A rating
18Double pole MCB(With B/C curve tripping Characteristics)
1940 A rating
20Four pole MCB (With B/C curve tripping Characteristics)
2150/63 A rating
22Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
23Metal door (single phase) IK-09 and IP-43 with Metal end box
248 Way (8+2)
25Metal door (Three phase) IK-09 and IP-43with Metal end box
264 Way
27Providing & Fixing of modular type 120W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-2rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
285 step fan regulator 2 Module 360 dgree rotating
29Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
30Blanking plate
31Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure "A" attached with this BSR
32Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
336.0 Sq. mm
342 core
3510.0 Sq. mm
364 core
37S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
38P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3950 mm
40Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole (b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. (d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. (e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
4117.2 mm thick and 3 Mtr. Long
42Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
4332mm x6mm G.I. ( Hot Dipped) Strip
44Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
4510 SWG G.I. ( Hot Dipped) Wire
46Supply & Laying following size" B " class ,G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc.for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per pre approved by Engineer in charge.(Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annex ure "A" attached with this BSR .
4740 mm dia.
48Supply & Fixing of phenolic laminated boardof 6.4 mm thick forfresh air fan/exhaust fan up to size of 300 mm onexisting window frame including cost of board, cutting of hole , Nut bolts etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
49Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
501200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
51P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
52Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
53300 mm sweep
54Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
551170mm(+/-10%) LED batten with min. lumen output 2200 lm 20W
56Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
57Surface Mounting (with extruded alumn. Housing )
58Minimum lumen output 1300 lm 12 W
59Minimum lumen output 2400 lm 22 W
60Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
61Poles with Octagonal Cross Section
627 Mtr.
63Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
64Single arm overhang
65Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . A) Excavation of Pit for Foundation Size upto required depth from Ground level B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face
66Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr.
67Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
68LED Street Light fixture with Minimum lumen output 5600 lm45W
69LED Street Light fixture with Minimum lumen output 8700 lm70W
70Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
71High Power LED Flood Light Minimum lumen output 14800 lm 120W
72Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
7340 mm Dia.