Tender For External Electrical Work, Hvac And Lift Work At Construction Of Phase-2 Of Medical College And Upgrdation Of Hospital At Dausa Rajasthan, Jaipur-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For External Electrical Work, Hvac And Lift Work At Construction Of Phase-2 Of Medical College And Upgrdation Of Hospital At Dausa Rajasthan. Submission Date for this Tender is 21-03-2024. Electrical Maintenance Tenders in Jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42817666
Tender For External Electrical Work, Hvac And Lift Work At Construction Of Phase-2 Of Medical College And Upgrdation Of Hospital At Dausa Rajasthan
Open Tender
Indian
Rajasthan
Jaipur
21-03-2024

Tender Details

External Electrical Work, Hvac And Lift Work At Construction Of Phase-2 Of Medical College And Upgrdation Of Hospital At Dausa Rajasthan

Key Value

Document Fees
INR 5900 /-
EMD
INR 1990100.0 /-
Tender Value
INR 9.95 Crore /-

BOQ Items

Name of Work : - External Electrical work, HVAC and Lift work at Construction of Phase-II of Medical College and Upgradation of Hospital at Dausa, Rajasthan.
Sl. No. Item Description
1PART A : External Electrical Work
2Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
33 core 300.0 Sq.mm
4Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage gradedirect in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) ,with procedure as per followingpoints:-(a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thicknessand 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
5Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
611 KV End Termination Kit Indoor type
73 core 120/150/185 Sq.mm
811 KV End Termination Kit Outdoor type
93 core 120/150/185 Sq.mm
1011 KV Straight Through JointKit
113 core 240/300 Sq.mm
12SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU)manually operated in combination ofVCB modules andLoad Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer.The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feeder of RMU should have voltage presence indicator. . and compring offollowings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder ModulesAll the type test certificates as per IEC from Third partyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR
13Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch
14SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm having provision for Following: (i)Provision for fixing Trivector / Import - Export Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections,etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
15SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H & I
16A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP(up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or aboverequired ) capable of taking 10% over loading for one hour after 12 hours of continuous operation.,Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber),up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required .
17B)AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled
18C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade.
19D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :
20E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA.
21F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.
22G) Servicing Contract of DG Set from OEM"s Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department.
23H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration.
24I) DG set will be offered for Inspection and Testing at Manufacturer"s Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
25500 KVA at 0.8 pf 415V 50Hz 3-?
26SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
27(a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
28(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
29[c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra )
30(d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
31(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
32(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra )
33(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
34(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
35Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
36Electrolytic grade Aluminium bus bar 6010 grade
37Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
38Threephase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS
39Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
40Ring type tape wound CT
41C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA
42C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA
43Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
44Red/yellow/Green colour
45Blue / white Colour
46SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
474 pole MCCB With Thermal Magnetic release
48up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
49125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
50160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
51200 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
52250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
53400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
54630 Amp , 50 kA, adjustable O/L & adjustable S/C setting,
554 pole MCCB With Microprocessor based release with adjustable O/L &S/C setting with Inbuilt Instantaneous and Ground fault Protection.
56400 Amp , 50 kA
57Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
584 x 6.0 sq.mm
594 x 10.0 sq.mm
60Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
61Single pole MCB (With B/C curve tripping Characteristics)
620.5 A to 5 A rating
63Double pole MCB(With B/C curve tripping Characteristics)
646 A to 32 A rating
65Triple pole MCB(With B/C curve trippingCharacteristics)
6640 A rating
6750/63 A rating
68Four pole MCB (With B/C curve tripping Characteristics)
6940 A rating
7050/63 A rating
71Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 160 (upto 160 A Incomer) / 250 Amp.  copper bus bar, neutral bars with shrouds,  earth bar , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, ferrules,  detachable gland plate, including making connections, testing etc. as required.  OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
72Double door IP-43 & IK-09 with Provision of Incomer MCCB 100/ 125 A Rating with Metal end box
736 Way
74Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal end box
756 Way
76Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
77Open execution type
78125 A
79160 A
80400 A
81Supply and fixing of following accessories for Moulded case circuit breaker (MCCB)compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
82Extended Rotary Handle
83Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
846.0 Sq. mm
854 core
8610.0 Sq. mm
874 core
8816.0 Sq. mm
894 core
9035.0 Sq. mm
913.5 core
9270.0 Sq. mm
933.5 core
9495.0 Sq. mm
953.5 core
96185.0 Sq. mm
973.5 core
98240.0 Sq. mm
993.5 core
100300.0 Sq. mm
1013.5 core
102400.0 Sq. mm
1033.5 core
104Add extrain item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
105Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width,with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
106Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
107Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1083.5 x 35.0 sq.mm
1093.5 x 70.0 sq.mm
1103.5 x 95.0 sq.mm
1113.5 x 185.0 sq.mm
1123.5 x 240.0 sq.mm
1133.5 x 300.0 sq.mm
1143.5 x 400.0 sq.mm
1154 x 6.0 sq.mm
1164 x 10.0 sq.mm
1174 x 16.0 sq.mm
118P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
11950 mm
120110 mm
121160 mm
122200 mm Dia.
123SITC of following capacity IK10Sandwich TypeRising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6standard & IS 8623 P-IIand Manufactured in India for use on 3 phase 4 wire, 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892,with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like(i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by OEM.
124Routine test as per OEM"s QAP in It"s own Manufacturing facility in Indiashall be witnessed by department Engineer virtually / Physically.Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
125Sandwich Type Bus Rising Main
126630 amps 40 KA SC for 1 sec
127Sandwich Type Bus Duct
1281600 Amps 80kA SC for 1 sec
129Out Door Bus Duct IP66 with Canopy
1301600 Amps 80kA SC for 1 sec
131SITC ofBus Rising Main OEM manufactured following capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB), Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
132For 630 Amp. (Without MCCB)
133SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable forSandwich / Compact Air Insulatedtype bus bar trunking Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but without MCB/MCCB/ACB) with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
134Plug in Box suitable for Sandwich Type Bus rising Main
135160/200/250 amps (Suitable for MCCB) without MCCB
136SITC ofBus Rising Main OEM manufacturedTinned copper flexible joint with enclosure of following capacity with Transformer / DG / Panelas required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1371600 Amp.
138Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
139(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
140(b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
141© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
142(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
143(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
144(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
14517.2 mm thick and 3 Mtr. Long
146Plate Earthing as per IS:3043 withcopper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying3 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
147Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
14825mm x 3mm G.I. ( Hot Dipped) Strip
14950mm x 6mm copper strip
15032mm x6mm G.I. ( Hot Dipped) Strip
15150mm x 6mm G.I. ( Hot Dipped) Strip
152Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1538 SWG G.I. ( Hot Dipped) Wire
154Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
155Providing and laying Non Pressure NP-3 classR.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth& Back filling with compaction is to be Paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
156300 mm dia
157labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.:
158Ordinary Rocks
159Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
160150mm x 50mm x 1.6mm
161300mm x 50mm x 1.6mm
162450mm x 50mm x 2.0mm
163Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
164LED Street Light fixture with Minimum lumen output 11225 lm
165Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
166Poles with Octagonal Cross Section
1673 Mtr.
1687 Mtr.
169Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
170Single arm overhang
171Providing and Laying RCC Foundation for Octagonal/ Conical Street Light poles, High mast Poles as per Drawing attach at TableP-4with Following Procedure& All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
172A) Excavation of Pit for Foundation Size upto required depth from Ground level
173B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.
174C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness
175D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.
176E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal
177F) Providing & Fixing of 2 no. Required SizePLB HDPE Pipe& Foundation Bolt with template as per OEM Recommendations.
178G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.
179H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.
180Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr.
181Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr.
182Providing & Fixing of IK08IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece constructionpowder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser andAluminium anodised with sand blast reflector. The System level Luminous efficacy =100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA.Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
183Minimum lumen output 4500 lm Post top Luminarie
184Supply installation testing & Commissioning ofhigh mast lighting system (as per PLG 07of ILP UKtechinical report no7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstructionlights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required on Existing Foundation.(See table P - 03 for specs.) OEM Must haveType test certificate for wind tunnel test .All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18520.0 Mtr Hm (in 2 section) suitable for 12 No. Luminaries
186Providing & Fixing ofIK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles,of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K±355K.Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
187High Power LED Flood Light Minimum lumen output 25000 lm
188Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18940 mm Dia.
190Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler withhermeticallysealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick)and tank (0.5 mm thick) , stainless steel water tray,minimum two nosBrass Chrome plated faucets and suitable drainage system complete in all respect with requiredheight MS fabricated and Painted Angle iron frame( Cost of frame to be paid Extra )complete in all respect of the following capacity.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
191cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs
192Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
19311 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms)
194Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
195One day & week reserve (digital type )
196P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen freefor less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
1974.0 Sq.mm 3 core flat / Round
198Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1991200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
200Providing & Fixing of 400 mm SweepBLDC technology Oscillating type Wall mounting / Pedestal typefans with Three speed, ON andOFF position, Double Wall bearing withfront and back 120 or moreribs guard; Three no.blades, noise level should be <= 75 dB,including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
201Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM
202Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts,making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
203450 mm sweep Wall mounting and three speed regulator with Minimum Air Delivery 150 Cum. / Minute
204Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
205300 mm sweep(900/1400 RPM)
206Providing & Fixing ofof ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
207250 mm sweep
208Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
209300 mm sweep
210P & F of Gravity Louver shutter of superior quality made out of frame of18 swg M.S. sheet & Louvers made from 24 swg MS Sheetwith enamel paint including cost of nuts, bolts, etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
211Up to 380 mm size
212Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap actionadjustable thermostat , Dual indicating lampsInjected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top with Portable Residual Current Device ( PRCD ) , including making inlet, outlet Flexible alloyconnection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
21325 Ltr.
21435 Ltr.
215Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
216570mm (+/-10%) batten with min. lumen output 1000 lm
2171170mm(+/-10%) LED batten with min. lumen output 2200 lm
218Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
219OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
220Recessed Mounting
221Minimum lumen output 1300 lm
222Minimum lumen output 1950 lm
223Surface Mounting (with extruded alumn. Housing )
224Minimum lumen output 1950 lm
225Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
226OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
227Recessed Mounting
228Minimum lumen output 4200 lm
229Surface Moutning
230Minimum lumen output 4200 lm
231Providing & Fixing of IP20 SMD Mid Power LED batten with integratedbox (min.1200mmx40mmx60mm including reflector) with replacable driverfixture made from Powder coated Extruded aluminiumhousing ,Min. lumen output 4400 lm,System lumen efficacy = 110 lm/Watt output, internal surge protection of 4.0 KV with Short & Open circuit protection,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.
232OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
233SITC of Indoor Type Floor mounted metal clad 11 KV, 630 Amps 3 phase, 50 HzVacuum Circuit Breaker (VCB) Panel Fabricated by System Integrator of VCB Manufactureras per IEC 62271-1,100,200 Standard made from Powder painted pre-fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc) coated sheet steel. Fabrication shall be done through CNC turret press and CNC bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR clasificationtotally enclosed with Aluminium bus bar of 630 Amps for each phase, flush front,Horizontal isolation, Horizontal drawouttypewith Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assambly of 3 vaccum interrupters (VCB manufacturer"s own make) , with each pole individually encapsulated by epoxy insulations to make it dust proofand self - aligning finger type isolating contacts, truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motor charged independent closing/ tripping spring , trip free operating mechanism withclosing and tripping push buttons and mechanical breaker.
234interconnected with HT sleeve bus bar of 630 Amps , Basic Insulation level (BIL) : 28KV (RMS) / 75KV (Peak) and Altiude less than 1000 meters,includingall protection, indication, Operation, monitoring and control and accessories etc. as required. Factory Tests of VCB panel as per System Integrator"s QAP in it"s own Manufacturing facility shall be witnessed by department Engineer virtually / Physically. (Cost of RCC Foundation / Steel Structure to be paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
235Incoming Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB operationg mechanism should be of M2 duty for minimum 10000 mechanical operation. - Closing & tripping coil of VCB should be of continious rating to achive minimal failure. - Resin Cast type CT havingRatio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement) - VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VAshould be floor mounted and to be connected from the back side of the panel. - Numerical relay (should be VCB manufacturer"s own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI. - Ammeter with Selectorswitch and Volt meter with Selector switch -Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA, KVAR, PF, KWH, KVARH, KVAH, A,V etc. - Trip circuit supervision relay (feature of numerical relay) - LR,TNC switch,indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.
236Outgoing Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB operationg mechanism should be of M2 duty for minimum 10000 mechanical operation. - Closing & tripping coil of VCB should be of continious rating to achive minimal failure. - Resin Cast type CT havingRatio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement) - Numerical relay (should be VCB manufacturer"s own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI. - Ammeter with Selectorswitch and Volt meter with Selector switch -Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA, KVAR, PF, KWH, KVARH, KVAH, A,V etc. - Trip circuit supervision relay (feature of numerical relay) - LR,TNC switch,indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC)
237Non BSR Item
238Supply installation testing & Commissioning of Copper wound distribution Transformer With OLTC, RTCC & AVR Having Tapping Range +5% to -15% Tapping in Steps Of 1.25%of following ratingand % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core designincluding standardaccessories like conservator with prismaticoillevelgauge , silica gel breather,Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box,LT cable box with Busbar connection for outgoing cables,,temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test inOEM"s own lab shall be witnessed by Department engineer Physically.
239Transformer shall be tested from CTLof discombefore charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge.Approved Makes:- Uttam Bharat/Danish/Vardhman/RTS
2401000 KVA with % Impedance 5.0
241Non BSR Item
242MAIN LT Panel
243SITC of IP-42 and general construction confirming to IEC 61439-1&2.type tested assembly (TTA)wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g) as below:-
244(a) Panel having short circuit withstand capacity of minimum of 50 kA for 1s (Icw rating) at 415 V, 50 HZ AC supply, Rated Impulse withstand voltage (Uimp) of 12kV for withstanding against transient Overvoltages, mechanical impact level of IK10 level and internal arc for 50kA for 0.3 second with aluminum busbar and fully type tested at an Independent Laboratory, Type test certifacte has to be submitted for all rating of LV Switchgear to be used in Panel.
245(b) All four Horizontal Busbars shall be in same compartment. Certified design of switchboards shall be proven design from OEM (Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panel builder. Panel shall be fabricated with a double door arrangement. Front Door shall be fitted with transparent Glass to allow maintenance staff to visually access device status, meter readings, indicating lamp status without opening the door.
246©Panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness, same as as per OEM Design. Sheet Steel having vibration free structure chemically treated with nine tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Aluminium busbar extensible type, busbar supports,
247(d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
248(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
249(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm
250(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test and Heat run test(type test) shall also be carried out.
251Approved Makes of Panel :- Engineer & Engineers/Ankit Electricals/Johns Electrical/Precesion control/Zeniya/Expert Engineers/Bafna Electric Co
252All the Main panel incomer shall have 3 pole + neutral type 1 + 2 SPD & all the sub main panel incomer shall have 3 pole + neutral type 2 SPD with suitable rating 4 pole MCB.
253PROVISION OF BUSDUCT/CABLE MUST BE AS PER SLD.
254Note:
255The incoming of Transformer feeders as shown on drawing shall be connected through bus duct. The suitable adopter box shall be provided on top only and DG feeders & Solar Incommer through cable from bottom.
256All Intelligent ACB shall have Micro processor based O/C, S/C & E/F. All ACB"s shall have Ics=Icu=Icw as per BOQ for 1Sec & should be supplied with Adopter Terminal Connections whose orientation can be changed on site.
257All Intelligent MCCB shall have Micro processor/Thermal Megnatic based release. With Ext rotary handel & spreader link. All CTs and PTs shall be cast resin type. All MCCB shall have Ics = 100% Icu & should have Isolation Feature & Class II Front Face as standard.
258The LT Panel manufacturer shall provide necessary,CT"s Aux. contacts; multiply those contacts in the respective panels etc. to hook up in to PLC system
259INCOMING
260TRANSFORMER INCOMER (2 Nos. * 1000 KVA) one set for each incomer
2612 No. 1600 A, 50KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases
2622 No. 230 volt D.C.Shunt release
2632 No. 230 volt A.C.closing coil
2642 No. 415 volt A.C. under voltage release.
2654 Set of CTs 1600 A/ 5A, 15VA class-1 for metering & APFC
2662 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB. CL1.0 with Rs485
2672 Set of O/C, S/C, and E/F relay
2682 No Breaker control switch
2692 Set of phase indication lights R,Y,B.
2702 set ofON-OFF-TRIP ckt. Healthy. indication lights
2712 No Spring charged indication.
272D.G. PANEL INCOMERS (2 Nos * 500 KVA DG set)one set for each incomer
2732 No. 800 A, 50KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases.
2742 No. 230 volt D.C.Shunt release
2752 No. 230 volt A.C.closing coil
2762 No. 415 volt A.C. under voltage release.
2772 Set of CTs 800 A/ 5A class-1 for metering
2782 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB. CL1.0 with Rs485
279Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.
2802 Set of O/C, S/C, and E/F relay
2812 No Reverse power relay
2822 No Breaker control switch
2832 Set of phase indication lights R,Y,B.
2842 set ofON-OFF-TRIP ckt. Healthy. indication lights
2852 No Spring charged indication.
286SOLAR POWER PLANT INCOMERS
287250A FP 25kA TM Based MCCBWithO/C+S/C Protection
2881 Set of CTs 250A/ 5A class-1 for metering
2891 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.
2901 Set of phase indication lights R,Y,B.
2911set ofON-OFF-TRIP ckt. Healthy. indication lights
292BUS BARS:-
2932400 Amps. 4P aluminium bus bars
294BUS COUPLER:-
2951 No. 1600 A, 50KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases
2961 sets Breaker Control switch
2971Sets of phase indication lights R,Y,B.
2981sets ofON-OFF-TRIP ckt. Healthy. indication lights
299Interlocking: Transformer incomers , DG Panel Incommers, and bus couplers shall be electrically andinterlocked so that no different source can be paralled at any point of time.
300OUTGOINGS:-
3016 Nos. 630 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
3026 Nos. 400 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
3035 Nos. 250 AFP MCCB , 36KA,with T.M. releases for O/C, & S/C.
3041 Nos. 200 AFP MCCB , 36KA,with T.M. releases for O/C, & S/C.
3052 Nos. 160 AFP MCCB , 36KA,withT.M. releases for O/C, & S/C.
3064 Nos. 100 AFP MCCB , 25KA,with T.M. releases for O/C, & S/C.
3074 nos 63 Amp 4P MCB (10KA)
308APFC SECTION(2nos * 360 Kvar)
309Incomer 2 No. 800A ,3POLE ,Microprocessor based MDO ACB with 230 V A.C. spring charged motor with Indicating Lamp & A/M Selector Switch.
3102 No.12 step APFC Relay (intelligent micro-processor based with current sensitivity less than 1%)
3112 Set phase indication lights (R, Y, B)
3121200 Amps. TP&N aluminium bus bars (50 KA)
31312 No.160 Amps. TPN MCCB (16 KA) with thermal magnetic release
3144 nos 63 Amp TP MCB (10KA) D curve
3152 nos 16 Amp TP MCB (10KA) D curve
3166 nos 10 Amp TP MCB (10KA) D curve
31712 No. 50 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter
3184 No. 25 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
3192 No. 5 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
3204 No. 2 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
3212 No. 1 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
32212 No. 50 KVar. TP capacitor duty contactors.
3234 No. 25 KVar. TP capacitor duty contactors.
3242 No. 5 KVar. TP capacitor duty contactors.
3254 No. 2 KVar. TP capacitor duty contactors.
3262 No. 1 KVar. TP capacitor duty contactors.
32726 No. Auto-Off-Manual selector switch.
32826 Sets self illuminated Red-Green ON-OFF push buttons.
3294 Sets of Axial flow fans with thermostate.
330Auto synchronisation :-The Auto synchronisation cum AMF panel should be capable for two nos external source and Two nos DG sets.
331Suitable PLC for synchronisation & AMF operation of four DG sets - 1 nos
332Synch Controller
333Digital I/P module
334Digital O/P module
335Suitable slot I/O rack with power supply
336Analouge I/P module
337KW tranducer
338EEPROM memory module
339Phase angle tranducer
340Operator interface 3" diagonal with key pad
341Communication cable from Operator interface to PLC
342Hooter for varios status annunciation
343A/M Selectror Switch, Push Button, Indicating Lights, DC Amp & Volt Meter, Auxilary Contactors for Ac & DC, Auxilary Relay Card, Control MCBs and all the software required for proper operation
3441 KVA online UPS with half an hour battery (SMF) back up for start operation
345SITC ofRO water system with Filtration stage = Particulate filter-Membrane life enhancer filter - sediment filter - Pre carbon filter -RO Membrane filter - Post carbon filter,Input power Rating - 230 V AC , 50 HZ, Percentage of Rejection TDS - 90% or better having following Features (a) Double purification by RO with ESS or latest technology with TDS indicator (b).Spin welded RO Membrane Housing to prevent tempering (c). Push fit components for leak proof performance (d). Fully automatic operation with auto start and auto off (e). SS/ABS construction for corrosion free lifespan (f). Equally suitable for water from all bore wells,,overhead storage tanks,water tankers and even municipal taps (g) RO Membrane Flushing - Auto Flush @ Every Start , Every Stop and every One Hourof working for one minute. complete in all respect with following capacity.(Make: Eureka Forbes/Kent).
346Purification capacity- 50 LPH,Duty Cycle 270-500 liters/day,
347P & F of Early streamer Emission type lightning arrester on GI mast with air terminal configured as spheroid which is comprised ofseparate electrically isolated 4 panels surrounding an earthed central finial, the terminal shall be tested by CPRI for impulse current of 45 kA ( 8 / 20 Sec ) with 5 positive & 5 negative impulse, the arrester having following protection radius at level 1
34860 - 79 Mtr.
349S & Laying of down conductor of 70 Sq.mm single core insulated flexible copper cable with accessories as required.
350Supply, installation, testing & commissioning of the following: IGBT based Rectifier & Inverter 60 KVA parallel True Online Double Conversion UPS having Inbuilt Isolators at UPS input,output and bypass, suitable for unbalanced, 3 Phase input and 3 phase 415 V output UPS system with Inbuilt isolation transformer with suitable stand at UPS Input and Inbuilt Static & Maintenance Bypass, UPS should have Unity output power factor (KVA=KW) at 40deg without derating, THDi <5%, UPS suitable for operating in parallel and each comprising as per technical specification complete as required.Make: Numeric / ABB / Emerson / APC
351VRLA sealed maintenance free batteries for 60 KVA UPS system, for providing 30 minutes back upto each 60 KVA UPS. Each bank of batteries shall comprise of 75AHx 60 Nos. ofSMF batteries etc as per specifications as required.(cost Included in above).Make: Exide /Quanta/ Panasonic
352Matching cabinet to house SMF batteries for 60 KVA UPS system along with interconnecting links andI/c S/F MCCB as required.(Cost Included in above).
353SITC of 10 KVA 3 Phase Input, 3 Phase Output advance DSP controlled UPS with IGBT based rectifier, LCD display, double conversion / Digital Signal Processing UPS,without isolationtransformer,with 30 minute battery back up, with MS rack for battery, with required cabling for incoming & outgoing connectionofMake : Numeric/ APC / Emersson/ Reilo.
354Supply, installation, testing & commissioning of Wall mounted Led Patient Bed light IP20 consuming a total system wattage of 31W with options of glare free downlight for reading and examination, up light for ambient lighting delivering an initial system lumen of 2533 lumens. Housing: non corrosive Extruded Aluminium with extruded ribbed translucence PMMA diffuser and self illuminated rocker switches. The luminaire shall have variable adjustment 10W Upward, 20W downward and 0.5W LED Bulb for generating multiple lighting modes as per the needs of Patient and doctor as well. The luminaire shall have optional suspended remote power switch for easy use in case of critical patrient care. The operating CCT shall be 5700K with CRI of =80. The luminaire shall be with electronic driver with input voltage range of 150 to 270V ,PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture. Similar to Wipro (Cat No: LW04-411-XXX-57-WS) or equivalent in Philips/Cropmton/Bajaj.
355PART B: HVAC Work
356Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3571.0 TR ISEER not less then 4.6
3581.5 TR ISEER not less then 4.6
3591.8 TR ISEER not less then 4.6
360SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
361Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
36220 mm
36325 mm
36432 mm
365Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
366Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3672 core x 1.5 Sq.mm
3684 core x 2.5 Sq.mm
369Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive)& fabricated as perIS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3700.60 mm
3710.80mm
3721.00mm
3731.25mm
374Supply , Installation, Testing and Comissioning of site fabricated ducting made from aluminium sheet conforming to IS:737, Grade 31000fabricated as perIS:655 and as per approved drawings & designs including the cost of hangers, supports , angle , expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3750.60 mm
3760.80mm
377SITCof air cooled ducted splittype air conditioning machine with each having a capacity and details as mentioned below suitable for operation on factory chargedR-32/R-410A Green refrigerant comprising ofScroll /rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system,Suitable capacity squirrel cage induction motor with class "B" insulation suitable for operation on sigle / three phase supply, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers,Microprocessor based control panel complete with accessories, machine isolation / disconnect switch, valves and accessories to inter connect compressor and condender including pressure testing, vacuum.Necessary starters suitable for Indoor & outdoor unit complete with O/L , U/V, phase reversal protection,single phase preventors etc complete as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3785.5 TR
3798.5 TR
38011 TR
381Supply and Installation of Box type EU13 Hepa Filter of 99.997% efficiency down to 0.3 micron particle size installed in zero leakage Aluminium frame as per ISO 14644-1 clean room including sealing and packing material cost like silicon and hardware cost and Labour cost. NABL accredeated/ appropriated lab testing reportswith OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
382305 mm Thick
383Supply and fixing of acoustic lining of ducts withchemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm,including cost of adhesive etc. complete in all respect.All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
38410 mm thick
385Supplying, installing, testing and balancing ofextruded Aluminium Powder coated supply/returnGrilles with fixed bars at fronthaving 0 / 15 / 30 / 45 degrees deflection as required. with Flange size 20 mm with rounded edges including fixing with steel screws etc. complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
386Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
387Supply Air Diffuser with Volume Control damper
388Return Air Diffuser without Volume Control damper
389Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
390Supply , installation, testing & balancing of 20 Gauge G I Damper with brass bushes and 6" pitch multiblade box type galvanised sheet steel construction volume control damper for Ducting and air washers to be provided with suitable links and quadrants for control of volume of air as per specifications complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
391Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
39250 mm dia per running inch length
393100 mm dia per running inch length
394150 mm dia per running inch length
395200 mm dia per running inch length
396P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibrationwith GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etcas required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
397Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
398Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
399150mm x 50mm x 1.6mm
400300mm x 50mm x 1.6mm
401Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
40216.0 Sq. mm
4034 core
40410.0 Sq. mm
4054 core
4066.0 Sq. mm
4074 core
408Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4094 x 6.0 sq.mm
4104 x 10.0 sq.mm
4114 x 16.0 sq.mm
412P & F of trap door for AHU / FCU"s  in existing false ceiling duly made from 12 mm thick laminated board, hinged with wooden frame of cheed wood size 50mm x 80mm, Frame suspended with MS strip 25 x 3 mm with ancor fastner min 8 supports from ceiling, Hinges, Locking arrangementetc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
413Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified "Class O" in Fire Propagationas per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required.All as per pre approved by Engineer in charge.
41413mm thick for indoor Application
41519mm thick for Outdoor Application with 26 SWG Aluminium Cladding
416NON BSR ITEMS
417Supplying, installing, and testing of Al volume control damper within ducts to be provided with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system as per approved shop drawings Supplying, installing, and testing of GI volume control damper within ducts to be provided with levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system, Frame of the VCD shall be constructed from 18 gauge sheet & bladesshall be constructed from 20 gauge sheet Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
418SITC of Digitalthermostat with cooling & heating mode including necessary control wiring to maintain the inside design condition as required Make:- Simens , Honeywell, Belimo
419Supplying, installation, testing and commissioning of fire dampers, the blades and frame shall be min. 1.6 mm thick GI and factory fitted in a sleeve made out of 1.6 mm thick GI of min. 400 mm long, as & where required, of required sizes including control wiring. The damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal. CBRI tested and certified for 90 minute fire rating etc. complete as required and as per specifications. (Total assembly should be UL listed)Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
420Fire Damper
421Actuator
422Supply, installation testing, commissioning and validation of Laminar Flow Units (LFU) comprising of Terminal EU 13 HEPA Filters of 99.997% Efficiency down to 0.3 Micron particle size installed in zero leakage Al frame with Al perforated plate type Al grille with Al VCD, LFD laminar flow diffusers are constructed from 18 swg aluminium sheet, perforated face with approx. 50% perforation od size 900x600mm-6nos, 600x600mm-3nos, including the cost of supply air 18 gauge Al plinum of size 8"x6"x1.5"/2", including all connection complete in all respect. Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro
423LFU Size : 2400 x 1800 mm ( +/- 100mm )
424SITC of Analogue, Megnehelic Differential Pressure Gages, Die Cast Al. case, 4" dial face, Zero Center Range 30-0-30 Pa with SS Boxes Breathing Pipe & Standard accessories.
425SITC of 2.0 mm thick (both base & cover) GI sheet raceway for copper piping from outdoor unit to shaft, The raceway shall be fixed on the floor with the help of suitable size galvanized MS angle support at 8" distance as approved from engineer incharge of size 400mm x 150mm.
426SITC of air cooled ducted splitair conditioning machine with each having a capacity and details as mentioned below suitable for operation on refrigerant comprising of Scroll / Rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class "B" insulation suitable for operation on 415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers,Microprocessor based control panel complete with accessories, machine isolation / disconnect switch as per specifications, Suction line insulation with minimum 19 mm thick polyvinyl rubber insulation,valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Pipe shall be hard drawn copper, Necessary starters suitable for compressor motor complete with O/L , U/V, phase reversal protection,single phase preventors etc complete as required.(Make: Daikin, Hitachi, Toshiba,Mitshibushi, Bluestar,LG)
427CONDENSING SPLIT AC - 8.5 TR CAPACITY, WITH R-410 (Single CIRCUIT)
428CONDENSING SPLIT AC - 11 TR CAPACITY,WITH R-410 (DOUBLE CIRCUIT)
429CONDENSING SPLIT AC - 16.5 TR CAPACITY, WITH R-410 (SINGLECIRCUIT)
430Supplying, installing, testing and commissioningof double skin construction Air Handling Units as per specification.All AHU"s shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working+ one standby) DX coil of coppertube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backwardcurve fan(s), beltdrive, vibrationisolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive. VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM.The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kitof following capacities. (Make: Zeco/ Edgetech/Systemaire)
4313000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER
432Supplying, installing, testing and commissioningof double skin construction Air Handling Units as per specification.All AHU"s shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working+ one standby) DX coil of coppertube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backwardcurve fan(s), beltdrive, vibrationisolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive. VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM.The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kitof following capacities.(Make: Zeco/ Edgetech/Systemaire)
4332500 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER, HEPA FILTER
4345000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER HEPA FILTER (for ICU/ Operation Theatre)
435Providing, fixing, testing and commissioning of AMCA Certified (For Air and Sound Performance) tube axial flow fan of different capacity as mentioned below in standard M.S.contruction. Entire fan model & AMCA Seal shall apear in techncial submittal of fan. All the fans are synthetic enamelled panited/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. The electric motor coupler shall be squirrel cage induction motor (IE-2 type) confirming to IS - 325 IP55 with class `H" insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Fan shall be EN 12101-3 Certified & CE/UL Listed for high temprature. Fan efficiency should not be less than 70 %, noise level should not be more than 80 db @ 3 m distance when measured in hemisperical reverberant room conditions for Normal mode Fans and noise level should not be more than 90 db @ 3 m distance when measured in hemisperical reverberant room conditions for Emergency mode Fans. Fan shall have all provision for start on emergancy signal from fire alarm panel. Fans should be as per specification and drawings.Make :- Kurger/ Nikotra/ Airflow/ Greeneck
4367500 cfm at 20 mm static (for lift well pressurization)
437Supply, Installation, testing and Commissioning of accoustically insulated ceiling / floor mounted Rectangular box type/circulartype Inline fan, for toilet exhaust , ward normal exhaust constructed of GSS duly powder coatedas per detailed specifications, completewith forward curved SISW fan, motor and drive suitable for 220 ± 10% volts, 1 phase, 50 Hz A.C supply, with necessary canvas connection etc complete in all respects.Make :- Kurger/ Nikotra/ Airflow/ Greeneck/Otemberg/ sphere
4381000 cfm at 15 mm static
439500 cfm at 15 mm static
440SITC of Desert Cooler(Ashoka fitted) cooling capacity 5000 cum/Hr. Cooler Size 28"X28"X38" fitted and tank size 9" height with 20" 1400 RPM Cooler fan motor(cool home/CG make) with three speed control fan motor and submercible pump melborne or eq. make)made of 18 SWG GI sheet for tank,front and top of 20 SWG GI sheet,Filter panel of 22 or better SWG,Grill of 22 or better SWG and Grill size 22"X24" complete as required with suitable stand.
441PART C: LIFT Work
442Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it"sISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
443Long point(up to 10 mtr.)
444Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
445On board
446S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
44725 mm
448Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
4493x 1.5 sq.mm
4502 x 2.5 sq. mm. + 1x1.5sqmm
451Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
452Single pole MCB (With B/C curve tripping Characteristics)
4536 A to 32 A rating
454Four pole MCB (With B/C curve tripping Characteristics)
45550/63 A rating
456Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protectionwith ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA,provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 35sq.mm. , IP 20 contact protection with existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
457Four pole 100/300 mA sensitivity
45840 A rating
459Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
460Metal door (single phase) IK-09 and IP-43 with Metal end box
46112 Way (12+2)
462Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
463Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
46435.0 Sq. mm
4653.5 core
466Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
467(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
468(b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
469© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
470(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
471(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
472(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
47325 mm thick and 3 Mtr. Long
474Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
47525mm x 6mm G.I. ( Hot Dipped) Strip
476Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4778 SWG copper Wire
478NON BSR
479SITC of 26 Passenger Bed (1768 KG)(With m/c Room)Lift with speed of 1.5 M/Sec., travel of Ground to Sixth:7 Stop/7 Open,power operated doors, ACVVVF Control, and automatic rescue operation during power failure. (Hospital, dimensions and travelling as per drawings) etc. as per Terms & conditions & specifications attached and as per direction of engg- in chargewith 5 year defect liability period.Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Krupp / Omega / Schindler and Equivelent Make as per Annx.
480SITC of 26 Passenger Bed (1768 KG)(With m/c Room)Lift with speed of 1.5 M/Sec., travel of Ground to Fifth :6 Stop/6 Open,power operated doors, ACVVVF Control, and automatic rescue operation during power failure. (Hospital, dimensions and travelling as per drawings) etc. as per Terms & conditions & specifications attached and as per direction of engg- in chargewith 5 year defect liability period.Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Krupp / Omega / Schindler and Equivelent Make as per Annx.