| 1 | Laying and Jointing PVC Pipe. Heading |
| 2 | Providing and fixing circular / hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the castiron/M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standarddrawing . |
| 3 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 4 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 5 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavygauge including painting etc. as required. (Note: More than 5 cm length shall berounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 6 | Supplying and fixing 20 amps 415volts, TPN industrial type, socket outlet, with 4pole and earth, metal enclosed plug top along with 20 amps \"C\" curve, TPMCB, insheet enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. |
| 7 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 8 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 9 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 13 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 14 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125Amp, 36 KA, FPMCCB |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator8 way, Double door |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 17 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 19 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 20 | Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 21 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm |
| 22 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KVgrade conforming to IS-7098 of following size:-4C*35 sqmm |
| 23 | SITC of 60W LED Flood Light luminiare fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =60 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) ProtectionClass- IP-66 |
| 24 | S/I/T/C of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95 |
| 25 | Supply,Installation, testing and commissioning of power distribution board made out of 1.6 mm sheet steel, epoxy powder coated , specially designed Al bus bar 400A to 630A with heat shrinkcable colour coated sleeves suitable for accommodatingMCCBs/MCBs /Isolators as incoming and outgoing as required (without MCCBs/MCBs/Isolators ) complete with digital meter module, including Voltmeter Ammeter with selector switch, CTs control fuse and indicating lights includingconnections etc. as required ( Conforms to IS:8623) |
| 26 | Supply of 18\"(450mm sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required |
| 27 | supply of 1200mm sweep 50watt energy saver ISI marked BEE 5 star ratingAC ceiling fan suitable for 230V,50hertz AC supply without regulator with blades,downrods etc complete as required |