| 1 | Schedule A1 : Schedule of Quantities for 11/0.433 kV Distribution Transformer (Non-Sealed Type) - 750 kVA, 500 kVA, 315 KVA, 250 KVA |
| 2 | DISTRIBUTION TRANSFORMER(NON-SEALED TYPE), 11/ 0.433 KV, Dyn 11, Copper Wound (3 phase), ONAN COOLED, OUT-DOOR TYPEWITH OFF-CIRCUIT TAPPINGS OF +5% TO -10%IN STEPS OF 2.5%ON H.V SIDE, PROVIDED WITH STANDARD FITTINGS & ACCESSORIES WITH FIRST FILLING OF TRANSFORMER OIL CONFORMING TO IS:1180 (PART-I)2014 : ENERGY EFFICIENCY LEVEL -2 |
| 3 | 500 KVA |
| 4 | 315 KVA |
| 5 | 250 KVA |
| 6 | L.T distribution switch board with copper bus bar,415 V, out-door type Kiosk, having electrolytic annealed copper bus bar 50x12mm for phase & 50x6mm for neutral circuits mounted on glazed porcelain or bakelite base & fitted with voltmeter, ammeter, selector switches for ammeter & voltmeter, electronic KWH meter, indicating lamps cabin light, fabricated with 12 gauge M.S plain sheet, painted with anti- rust primer & two coats of Epoxy paint of shade 631 as per IS: 8623, front opening doors with gasket & locking arrangement complete with following incoming & outgoing controls: |
| 7 | INCOMING:- No. 800 Amp, 415 Volt, FP, manually Draw Out type ACB with in built Thermo Magnetic Release & 6No+6Nc Auxiliary contacts.Outgoing:- 3 Nos. 200 Amp TP MCCB breaking capacity 35 KA , 1 No. 100 Amp TP MCCB breaking capacity 35 KA& 1 No. 63 Amp. TP MCCB breaking capacity 35 KA, all with built in Thermo Magnetic Release |
| 8 | L.T distribution switch board with aluminum bus bar, 415 V, out-door type Kiosk, having electrolytic annealed Aluminum bus bar 50x12mm for phase & 50x6mm for neutral circuits mounted on glazed porcelain or Bakelite base & fitted with voltmeter, ammeter, selector switches for ammeter & voltmeter, electronic KWH meter, indicating lamps cabin light, fabricated with 12 gauge M.S plain sheet, painted with anti- rust primer & two coats of Epoxy paint of shade 631 as per IS: 8623-1, front opening doors with gasket & locking arrangement complete with following incoming & outgoing controls: |
| 9 | INCOMING:1 No. 630 A, 4P,50KA, MCCBOUTGOING: 3 Nos. 200A TP MCCB, 50 KA & 1 No. 63A TP MCCB, 35 KA all with built in Thermo Magnetic Release. |
| 10 | INCOMING:1 No. 400 A, 4P,50KA, MCCB OUTGOING: 1 No. 200A TP MCCB, 50 KA ,2 Nos. 100A TP MCCB, 35 KA& 1 No. 63A TP MCCB,35 KA, all with built in Thermo Magnetic Release. |
| 11 | 11 KV, 3 Pole 400 amp, Air Break Gang Operated Switch (G.O.S) tilting type, three insulator per phase, complete with all fittings confirming to IS: 9920 & IS: 9921 Raychem RPGmake or equivalent |
| 12 | 11 KV, 3 Pole, 400 amp. Drop-out Fuse (D.O.F Unit) complete with all accessories including fuse element rated for transformer capacity confirming to IS: 9385 Raychem RPG make or equivalent |
| 13 | 11 kV, 3 X 35 sq.mmCu / XPLE Cable |
| 14 | Heat Shrinkable Outdoor type end termination kit for 11 KV (E) 3 core XLPE (Kit No.EOKT 3091-3131) Raychem make or equivalent : 3 C X 35 sqmm |
| 15 | 9 Mtrs. Steel lattice structure of 35x35x6mm M.S Angle complete with nuts & bolts conforming to specification of design detail No. 2/L/FT/E&PD/ 9 Mtrs. |
| 16 | G.I. channel 75X40X4.8mmX2.2 m long for DP. |
| 17 | Back clamps of 50x8mm G.I. flat for holdingchannel. |
| 18 | G.I. nuts & bolts of 16mm dia.X 40mm length. |
| 19 | 9 KV, 10KA Single pole unit Metal Oxide Gapless Surge Arrestor with earth lead disconnector, bird protection cap andmounting brackets. for 11 KV, 50 c/s solidly earthed neutral system confirming to IS:3070 (Part III) Raychem RPG make or equivalent |
| 20 | SAFE EARTHING MODEL T-19 SHORT CURRENT 20KA RMS FOR 1 SEC(LV / MV) APPLICATION CONFORMING TO IS: 3043: 50 mm diameter x 2 mtrs. Electrode (Copper bonded) & One bag backfill chemical compound. |
| 21 | G.I. strip 25x6 mm. for earthing |
| 22 | 1.1 kV 1Cx240 sqmm, Cu/XLPE/PVC (DTR to LT D-Board Incomer) (2 cables /cct for 750 / 500 KVA, 1 cable/cct for 315/250 KVA) |
| 23 | Tinned Copper Lugs - 240 sqmm |
| 24 | AAAC Rabbit Conductor (for down wires) |
| 25 | Al Line Tap / PG Clamp, Double Bolt, 25-150 sqmm |
| 26 | Red oxide paint @ 1.5 ltr/ pole |
| 27 | Aluminium paint @ 1.0 ltr / pole |
| 28 | 11 kV Caution Board |
| 29 | Mandetory Spare Parts |
| 30 | Spare Fuse element tubes for DOF of 500 KVA Distribution Transformer |
| 31 | Spare Fuse element tubes for DOF of 315 KVA Distribution Transformer |
| 32 | Spare Fuse element tubes for DOF of 250 KVA Distribution Transformer |
| 33 | Schedule A2 : Schedule of Quantities for 11/0.433 kV Distribution Transformer (Hermetically Sealead) - 100 kVA, 63 kVA, 25 KVA |
| 34 | DISTRIBUTION TRANSFORMER(SEALED TYPE), 11/ 0.433 KV, 50 Hz, Dyn 11, Copper Wound (3 phase), ONAN COOLED, OUT-DOOR TYPE(WITH OFF-CIRCUIT TAPPINGS +2.5% TO -5% IN STEPS OF 2.5% ON H.V SIDE) PROVIDED WITH STANDARD FITTINGS & ACCESSORIES OIL FILLED AND HERMETICALLY SEALED CONFORMING TO IS:1180 (PART-I) 2014: ENERGY EFFICIENCY LEVEL -2 |
| 35 | 100 KVA |
| 36 | 63 KVA |
| 37 | 25 KVA |
| 38 | L.T distribution switch board with aluminum bus bar, 415 V, out-door type Kiosk, having electrolytic annealed Aluminum bus bar 50x12mm for phase & 50x6mm for neutral circuits mounted on glazed porcelain or Bakelite base & fitted with voltmeter, ammeter, selector switches for ammeter & voltmeter, electronic KWH meter, indicating lamps cabin light, fabricated with 12 gauge M.S plain sheet, painted with anti- rust primer & two coats of Epoxy paint of shade 631 as per IS: 8623-1, front opening doors with gasket & locking arrangement complete with following incoming & outgoing controls: |
| 39 | INCOMING:1 No. 200 A, 4P,50KA, MCCB OUTGOING: 3 Nos. 100A TP MCCB, 35 KA, & 1 No. 32A TP MCCB, 35 KA all with built in Thermo Magnetic Release. |
| 40 | INCOMING:1 No. 100 A, 4P,50KA, MCCB OUTGOING: 3 Nos. 63A TP MCCB, 35 KA, & 1 No. 32A TP MCCB, 35 KA all with built in Thermo Magnetic Release. |
| 41 | INCOMING:1 No. 63 A, 4P,50KA, MCCBOUTGOING: 2 Nos. 40A TP MCCB, 35 KA, & 1 No. 32A TP MCCB, 35 KA all with built in Thermo Magnetic Release. |
| 42 | 11 KV, 3 Pole 400 amp, Air Break Gang Operated Switch (G.O.S) tilting type, three insulator per phase, complete with all fittings confirming to IS: 9920 & IS: 9921 Raychem RPGmake or equivalent |
| 43 | 11 KV, 3 Pole 200 amp, Air Break Gang Operated Switch (G.O.S) tilting type, three insulator per phase, complete with all fittings confirming to IS: 9920 & IS: 9921 Raychem RPGmake or equivalent |
| 44 | 11 KV, 3 Pole, 400 amp. Drop-out Fuse (D.O.F Unit) complete with all accessories including fuse element rated for transformer capacity confirming to IS: 9385 Raychem RPG make or equivalent |
| 45 | 11 KV, 3 Pole,200 amp. Drop-out Fuse (D.O.F Unit) complete with all accessories including fuse element rated for transformer capacity confirming to IS: 9385 Raychem RPG make or equivalent |
| 46 | 9 Mtrs. Steel lattice structure of 35x35x6mm M.S Angle complete with nuts & bolts conforming to specification of design detail No. 2/L/FT/E&PD/ 9 Mtrs. |
| 47 | G.I.channel 75X40X4.8mmX2.2 m long for DP. |
| 48 | G.I.channel 75 X 40x4.8mm X 1.2 m long for mounting of DT |
| 49 | Back clamps of 50x8mm G.I. flat for holdingchannel. |
| 50 | G.I. nuts & bolts of 16mm dia.X 40mm length. |
| 51 | 9 KV, 10 KA Single pole unit Metal Oxide Gapless Surge Arrestor with earth lead disconnector, bird protection cap andmounting brackets. for 11 KV, 50 c/s solidly earthed neutral system confirming to IS:3070 (Part III) |
| 52 | SAFE EARTHING MODEL T-19 SHORT CURRENT 20KA RMS FOR 1 SEC(LV / MV) APPLICATION CONFORMING TO IS: 3043: 50 mm diameter x 2 mtrs. Electrode (Copper bonded) & One bag backfill chemical compound. |
| 53 | GI strip 25x6 mm. for earthing |
| 54 | 1.1 kV 1Cx50 sqmm, Cu/XLPE/PVC (DTR to LT D-Board Incomer) |
| 55 | Tinned Copper Lugs - 50 sqmm |
| 56 | AAAC Rabbit Conductor (or down wires) |
| 57 | Al Line Tap / PG Clamp, Double Bolt, 25-150 sqmm |
| 58 | Red oxide paint @ 1.5 ltr/ pole |
| 59 | Aluminium paint @ 1.0 ltr / pole |
| 60 | 11 kV Caution Board |
| 61 | Mandetory Spare Parts |
| 62 | Spare Fuse element tubes for DOF of 100 KVA Distribution Transformer |
| 63 | Spare Fuse element tubes for DOF of 63 KVA Distribution Transformer |
| 64 | Spare Fuse element tubes for DOF of 25 KVA Distribution Transformer |
| 65 | Schedule B : Schedule of Quantities for 11/0.433 kV Packaged Substation - 750 kVA, 500 kVA |
| 66 | Packaged sub-station 11/0.433 KV, 50 Hz consisting of 11 kV, 3 way SF6insulated compact RMU, oil cooled (Aluminium wound)/ dry type copper wound transformer and LT section with one ACB as incoming and 4 nos outgoing MCCB feeders and with encloser made of electromechanically galvanized |
| 67 | 11 kV RMU - 2 X 630 A LBS + 1 X 200 A VCB(Motor Operated / SCADA ready )500 KVA Oil cooled(Al wound) / Dry Type (Cu wound) transformerLT Compartment : INCOMING:-1 No. 800 Amp, 415 Volt, 50 KA, FP,ACB with microprocessor Release (IPR E 4 Pole) Outgoing:- - 2 Nos. 200 Amp + 1x100 Amp + 1x63 Amp, TP MCCBs breaking capacity 35 KA with built in Thermo Magnetic Release |
| 68 | SAFE EARTHING MODEL T-19 SHORT CURRENT 20KA RMS FOR 1 SEC(LV / MV) APPLICATION CONFORMING TO IS: 3043: 50 mm diameter x 2 mtrs. Electrode (Copper bonded) & One bag backfill chemical compound. |
| 69 | G.I. strip 25x6 mm. for earthing |
| 70 | Schedule C : Schedule of Quantities for Low Voltage OH Lines |
| 71 | 8.5 mtr. steel latticed structure of 35x35x6 mm complete with nuts & bolts. |
| 72 | LT shackle insulator 3\"x3 1/2\". |
| 73 | D-clamp complete with G.I. pin, washers, nuts & bolts. |
| 74 | Guy assembly complete with 7/12 SWG GI stay wire, 110x75 mm LT guy insulator, 16mm dia stay rod,1.8 mtrs. long withbow thimble, turn buckle and 150x150x6mm anchor plate, GI stay clamp for lattice structure |
| 75 | AAC ANTconductor 50 sq.mm. |
| 76 | AAC GNATconductor 25 sq.mm. |
| 77 | No. 12 SWG G.Iwire for continuous earth wire |
| 78 | Al Binding Wire 10 SWG |
| 79 | SAFE EARTHING MODEL T-19 SHORT CURRENT 20KA RMS FOR 1 SEC(LV / MV) APPLICATION CONFORMING TO IS: 304350 mm diameter x 2 mtrs. Electrode (Copper bonded) & One bag backfill chemical compound. |
| 80 | Danger Board 440 Volts. |
| 81 | Red Oxide paint @1.5 Ltr./pole. |
| 82 | Aluminium paint @1 Ltr./pole. |
| 83 | G.I Barbed wire @ 2Kg/pole. |
| 84 | Schedule D : Schedule of Quantities for Low Voltage UG cable lines |
| 85 | 1.1 kV gradearmoured cable(Al Conductor/XLPE Insulated/SWA/PVC Sheathed) |
| 86 | 3.5 core x 240 sq.mm. |
| 87 | 3.5 core x 185 sq.mm. |
| 88 | 3.5 core x 120 sq.mm. |
| 89 | 3.5 core x 95 sq.mm. |
| 90 | 3.5 core x 50 sq.mm. |
| 91 | 3.5 core x 25 sq.mm. |
| 92 | 4 core x 16 sq.mm. |
| 93 | 2 core x 16 sq.mm. |
| 94 | 2 core x 10 sq.mm. |
| 95 | Rigid U PVC pipe as per IS 4985-2000 working pressure 6Kgf/cm2 |
| 96 | 160 mm dia. |
| 97 | 110 mm dia. |
| 98 | 75 mm dia. |
| 99 | 50 mm dia. |
| 100 | 1.1 KV indoor/outdoor end termination kit suitable for: |
| 101 | 3.5 core x 240 sq.mm. |
| 102 | 3.5 core x 185 sq.mm. |
| 103 | 3.5 core x 120 sq.mm. |
| 104 | 3.5 core x 95 sq.mm. |
| 105 | 3.5 core x 50 sq.mm. |
| 106 | 3.5 core x 25 sq.mm. |
| 107 | 1.1 KV straight through jointing kit suitable for: |
| 108 | 3.5 core x 240 sq.mm. |
| 109 | 3.5 core x 185 sq.mm. |
| 110 | 3.5 core x 120 sq.mm. |
| 111 | 3.5 core x 95 sq.mm. |
| 112 | 3.5 core x 50 sq.mm. |
| 113 | FEEDER PILLARS:OUTDOOR TYPE CUBICLE CONFORMING TO IS:8623-1Main Feeder Panel: Cubicle design totally enclosed and water proof outdoor type floor mounted suitable for use in 440 V,400A as main feeder pillarIncomer : 1 No 400 A, MCCB, 50KAOutgoing: 2 Nos. 200 A TPN MCCB & 4 Nos. 32 A TPN, MCB for individual service connections. |
| 114 | FEEDER PILLARS:OUTDOOR TYPE CUBICLE CONFORMING TO IS:8623-1Sub-Main Feeder Panel: Cubicle design totally enclo.& water proof outdoor type floor mounted suitable for use in 440V 200 A as a sub-main feeder pillar:Incomer: 1 No. 200 A, TPN MCCBOutgoing: 3 Nos. 63 A TPN MCCB & 4 Nos. 32 A MCCB for individual service connections & 8 Nos.16 A TPN for individual service |
| 115 | L.T distribution switch board with copper bus bar, out-door type Kiosk, having electrolytic annealed copper bus bar 50x12mm for phase & 50x6mm for neutral circuits mounted on glazed porcelain or Bakelite base & fitted with voltmeter, ammeter, selector switches for ammeter & voltmeter, electronic KWH meter, indicating lamps cabin light, fabricated with 12 gauge M.S plain sheet, painted with anti- rust primer & two coats of Epoxy paint of shade 631 as per IS: 8623-1, front opening doors with gasket & locking arrangement complete with following incoming & outgoing controls: INCOMING:1 No. 100 A, 4P,50KA, MCCBOUTGOING: 3 Nos. 63A TP MCCB, 35 KA, & 1 No. 32A TP MCCB, 35 KA all with built in Thermo Magnetic Release. |
| 116 | Safe earthing electrode Model T-19 short time current 20 KA rms for 1 sec (MV) application: 50 mm dia.x3 mtrs. electrode & 2 bags backfill Chemical compound . |
| 117 | GI strip 25mm X 5mm for earthing |
| 118 | Aluminium thimble of size; |
| 119 | 240 sq.mm |
| 120 | 185 sq.mm |
| 121 | 120 sq.mm |
| 122 | 95 sq.mm |
| 123 | 70 sq.mm |
| 124 | 50 sq.mm |
| 125 | 25 sq.mm |
| 126 | 16 sq.mm |
| 127 | Sundry itmes for 3.5C x 25 or 35 / 4C x 16 sqmm cable line installation for upto 30 Nos 3-phase connections for termination at switchgear / meterboxes ( like nails, saddle, etc.) |
| 128 | Sundry itmes for4C x 16 / 2Cx 16 & 10 sqmm cable line installation for upto 50 Nos 1-phase & 3-phase connections for termination at switchgear / meterboxes ( like nails, saddle, etc.) |
| 129 | Schedule E : Schedule of Quantities for Low Voltage ABC lines |
| 130 | 8.5 Mtr STP 410 SP21 complete with base plate, nuts & bolts |
| 131 | Tension / Dead End Clampwith hookattachment for AB Cable with insulated messenger, 50-70 sqmm, 20 kN breaking load |
| 132 | Tension / Dead End Clampwith hookattachment for AB Cable with insulated messenger, 25-35 sqmm, 20 kN breaking load |
| 133 | Suspension Clamp with hook attachment for AB Cable with insulated messenger, 25-95 sqmm, 16 kN breaking load |
| 134 | GI Pole Clamp for fixting hook attachment on STP pole |
| 135 | Piercing Connector TYPE -I,(Main 25-120 sqmm Tap Off25-120 Sqmm) |
| 136 | Piercing Connector TYPE -II,(Main35 -120sqmm Tap Off 16-25 Sqmm) (provisional qty for st. lighting tapping) |
| 137 | 1.1 kVXLPE Aerial Bunched Cable 3x120+1x70+1x16 sqmm, insulated neutral cum Messenger |
| 138 | 1.1 kVXLPE Aerial Bunched Cable 3x95+1x70 +1x16 sqmm, insulated neutral cum Messenger |
| 139 | 1.1 kVXLPE Aerial Bunched Cable 3x70+1x50+1x16 sqmm, insulated neutral cum Messenger |
| 140 | 1.1 kVXLPE Aerial Bunched Cable3x50+1x35+1x16 sqmm, insulated neutral cum Messenger |
| 141 | 1.1 kVXLPE Aerial Bunched Cable3x35+1x35+1x16 sqmm, insulated neutral cum Messenger |
| 142 | Stay set including 16 mm Dia x 1.8 mtr Long Rod, and 110 x 75 x 6 mm Anchor Plate complete with 7/12 SWG Stay Wire, G.I Stay clamp |
| 143 | G.I. Back Clamps 75 x 8 mm flat complete with G.I Pole Clamp |
| 144 | Earthing Coil of 115 Turns of 50 MM Dia and 2.5 Mtr Lead of 4.0 mm G.I Wire |
| 145 | Push on type end capsfor ABC, 16-120 sqmm |
| 146 | Threephase LTABC Distribution Box with Spring Loaded Busbar System suitable for 1 Incoming 3 Outgoing 3 Phase Circuits |
| 147 | Single phase LTABC Distribution Box Spring Loaded Busbar System suitable for 1 Incoming 6 Outgoing 1 Phase Circuit |
| 148 | 4C x35 sqmm Al/PVC cable for connecting Dist. Box to ABC |
| 149 | 2C x25 sqmm Al/PVC cablefor connecting Dist. Box to ABC |
| 150 | Red Oxide Paint |
| 151 | Aluminium Paint |
| 152 | Anti Climbing Device (Barbed Wire) |
| 153 | 440 Volt Caution Board |