Tender For Modular Operation Theater, Semi Modular Operation Theater Work For Kaili Hospital Basti, basti-Uttar Pradesh

Uttar Pradesh Projects Corporation Limited has published Tender For Modular Operation Theater, Semi Modular Operation Theater Work For Kaili Hospital Basti. Submission Date for this Tender is 13-03-2024. clocks Tenders in basti Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

42775519
Tender For Modular Operation Theater, Semi Modular Operation Theater Work For Kaili Hospital Basti
Open Tender
Indian
Uttar Pradesh
basti
13-03-2024

Tender Details

Tender For Modular Operation Theater, Semi Modular Operation Theater Work For Kaili Hospital Basti- 1 Modular Ot ( 04 Nos ) 2 Pre-Fabricated Walls & Ceiling Panel 3 Pre-Fabricated Modular Constructin Shall Be Designed And Constructed For Exact Size. The Prefabricated Operating Room Will Be Free Standingstructure From Composite Free-Standing Insulated Steel Wall Panels.The Wall Will Be Constructed Using 1.0Mm Ss 304 Sheet Panel In The Front Panels&0.8Mm Ss 304At The Back Panel. The Core Between Two Panels Will Consist Of Rigid Polyurethane Foam Which Has Been Injected Under Highpressure, With A Minimum, Density Of 40 Kg / M3.The Individual Wall Panels Shall Use The Tongue And Groove Technology For Joining Two Panels, Nowelding Will Be Allowed.The Gaps Between Panels Be Suitably Filled With Metal Filler / Epoxy And Sanded Flush. 4 The External Walls Of The Room Shall Be Constructed With Solid Bricks And Mortar By The Hospital As Part Of Its Scope Of Work.The Inner Surface Wallsshall Be Fixed To The Brick Wall With Essential Supports.There Shall Be Minimum Possible Cavity / Gap In Between The Masonry And Steel Walls.Thetotal Distance Between Inside And Outside Surface Of Or Shall Be Variable To Suit Architects Layout, But Shall Be Sufficient For Flush Mounting Of Theequipments.The Cavity Between Inner And Outer Walls Shall Be Left With Minimum Obstructions For Possible Addition Of Equipment At A Later Date Andto Enable Services, Pipes, Conduits Etc, To Be Run Within The Cavity.All Wall-Mounted Equipment Shall Be Flush Mounted And Sealed Into Theatre.Thewall Panel Design And Construction Shall Allow For Installation And Suppor Of All Equipment And Provision Of Openings Required For The Installations, Without Affecting Rigidity And Strength.Access Boxes Shall Be Fitted To The Rear Of All The Wall-Mounted Equipments To Enable Maintenance To Becarried Out From Outside The Operating Room.All The Sharp Edges And Corners Shall Be Smoothened To Avoid Bacterial Contamination. 5 Anti Bacterial / Anti Fungal-Paint 6 The Internal Surfaces Of The Ss-304 Ot Walls Should Be Sprayed With Water Based, Non-Reflective Liquid Plastic, To A Colour Approved Be The Architecta Minimum Dry Film Thickness Of 300 Microns.These Plastic Coatings Should Overlap The Floor Covering, Ceiling System And Door Frames By 25Mm Toprovide A Continuous Sealed Surface.Sterile Coating Applied Should Be Water Resistant, Does Not Support Bacteriological Or Fungal Growth And Isresistant To Most Chemicals Commonly Used In Hospital Departments.The Sterile Coating Should Remain Unaffected By Radiation And Other Ionizingradiation At Levels In Excess Of 1000 Mrad And Is Classified To Class I When Tested In Accordance With The Requirements Specified Under Bs.476:Part7 1971, Surface Spread Of Flame Test For Materials.The Coating System Should Be Easily Maintained And Can With Stand Repeated Cleaning Withalkaline Detergents, Antiseptics And Fumigation Agents Without Any Degradation To The Surface Finish Or Performance. 7 Laminar Air Flow Ceiling 8 Each Modular Ot Shali Have Plan Air Ceiling.The Plan Air Ceiling Shall Be Constructed Out Of 2 Mm Thick Extruded Aluminium Profiles, Overall Size2400x2400 Mm Or Larger As Per Actual Layout, Having Six Nos Hepa Filters With Mpps Efficiency Of 99.995% And Spot Efficiency Of 99.99% @0.3 Micron.The Plenum Should Provide The Required Air Volume To Achiee The Temperature, Pressure ( 15-30Pa ) And Humidity Specified, And Terminalvelocity 90 To 120 Fpm At The Diffuser Face.Air And Light Diffuser Made Of Two Layer Of Mono Filament Precision Woven Polyester For Plan Air Ceiling Togive A Laminar Flow Of Filtered Air.It Shall Also Provide A Shadow Less Lighting System With Control Of The Intensity Of Luminance By Using Highefficiency Electronic Fluorescent Tubes.All Hepa Filters Shall Be Factory Tested And Certified In Accordance With International Standards.All Ceilingshall Include Integral Lighting And Composite Air / Light Diffuser.Air Shall Be Diffused Into The After Uniformly Over The Total Area.The Laminar Flowceiling Should Also Have Illumination Across Its Total Area. 9 Automatic Hermetically Sealing Door 10 2100X1500mm 11 Automatic Door Shall Be Provided At The Main Entry Of The Ot.Door Frames Shall Be Made Of Aluminium Extrusion Profile To Carry Any Door Weight. The Core Door Size Is Of 60Mm Size Built Of High Density Puf ( Density 40Kg / M3 ) Of 52Mm And 1.5Mm Consist Of Solid Stainless Steel ( Ss-304 ) Onboth Side Of The Door.Door Blade Is Made With 3-Tier Specially Designed 3 Slide Heavy Duty Replaceable Epdm Gasket Against Wall Frame.Bottomsealing With 2-Tier Heavy Duty Epdm Gasket To Flush With Finished Floor.Stainless Steel Lever Handle On Both Side Of The Door Blade For Smooth Andeasy Door Opening And Closing.The Thickness Of Aluminium Extrusion For Door Frame & Door Panel Surfaces Shall Not Less Than 1.5Mm.There Shallnot Be Any Visible Screws Or Similar Other Uneven Surfaces On The Door Panel. A Lock Shall Be Provided. Door Shall Have Vision Panels ( Viewingwindow ) At Least 300Mmx 300Mm.Automation Of The Door Has Digilal Controlier, Motor And Suitable Switches To Open The Door Thru Hands, Foots Etc.The Door Size Shall Be As Per Boq. 12 Surgeon Control Panel 13 The Control Panel Will Be User Friendly And Operation And Maintenance Will Be Easy.The Control Panel Shall Be Tiled Membrane Type;Can Beconfigured To Incorporate All The Services That Operating Theatre Staff Required.The Fascia Shall Be Made With Superior Quality Uv Resistant. Sterilisable Membrane.The Membrane Backing Is Made Of 2.5 Mm Thick Aluminium That Is Rust Resistance.The Connection Between The Surgeoncontrol Panel And The Distribution Board Will Be By A Mutiplexed System. The Panel Will Contain 6 Servicestiles For: ( A ) Time Day Clock ( B ) Time Elapsed Clock ( C ) Temperature / Humidity Indicator ( D ) General Lighting System ( E ) Medical Gas Alarm Panel ( 1 ) Hand Free Phone. 14 Led Twin Plate X-Ray Viewer 15 The Operation Theatre Shall Be Equipped With A X-Ray Viewing Led Screen, Designed To Provide A High Level Of Control Luminance Without Flicker.Itshall Be Equipped With Loaded Clips To Secure The X-Ray Negative When In Use. 16 Pressure Relief Dampers 17 Pressure Relief Dampers To Be Provided In Theatre To Prevent Cross Contamination Of Air From Clean And Dirty Areas. Suitably Sized Air Pressure Reliefdamper Will Be Strategically Placed, Enable Differential Room Pressure To Be Maintained And Ensure That When Doors Are Opened Between Clean Anddirty Area.Counter Weight Balancing System Will Be Provided In The Prd To Maintain Positive Pressure Inside The Operation Theatre.Air Pressurestabilizers Will Have Unique Capability Of Controlling Differential Pressure To Close Tolerance.The Prd Will Remain Closed At Pressure Below The Setpressure And Will Open Fully At Pressure Only Fractionally Above The Threshold Pressure. The Body Will Be Epoxy Powder Coated As Per Standard Bscolours And Meets International Quality And Safety Requirements. First Class Electrolyzed Steel Plate Will Be Used For Body And With High-Grade Ss304 Stainless Steel For Blades. 18 Anti-Static Flooring 19 Anti-Static Flooring ( Static Conductive Tiles ) :The Floor Finishing The Operating Room Will Be Imported 2 Mm Statics Conductive Pvc Tiles, Laid On Asemi Conductive Adhesive Base.The Floor Finish Will Terminate At The Room Perimeter Passing Over A Concealed Cove Former And Continuing Up Thewall For 100 Mm.Flooring Will Fulfil En.It Will Have Chemical Resistance As Per En 423. It Will Have Electrical Resistance Conforming To En 1081 / Iec613404-1.All Joints Will Be Welded And The Plastic Wall Finish Will Overlap The Floor Coving By 25Mm, To Provide A Continuous Sealed Surface. The Self- Levelling Compound Will Be Of The Type That Does Not Promote Bacteriological Growth. Copper Grounding Strips ( 0.05Mm Thick, 50Mm Wide ) Will Be Laidflat On The Floor In The Conductive Adhesive And Connect To Copper Wire Of Grounding. 20 Storage Cabinets 21 Providing, Fixing, Supply And Installation Of Storage Unit Will Be Made With The Wall Cladding Material I.E. Ss-304.The Unit Will Be Divided Into 2 Equalparts And Each Part Will Have Individual Glass Doors With Locking System.Each Part Will Have Glass Racks To Keep Surgical Medicines Etc. 22 2-Bay Scrub Sink 23 Compact Surgical Scrub Sink Will Be Designed For Use In Operation Theatre Complex Providing Surgeons With A Convenient Sink For Pre-Up Scrub Up. Each Fixture Will Be Fabricated From Heavy Gauge Type 304 Stainless Steel & Will Be Welded Construction Polished To A Satin Finish.The Scrub Sink Willbe Provided With A Front Access Panels, Which Will Be Easily Removed For Access To The Water Control Valve, Waste Connections Stoppers &Strainers. Handsfree Operation Will Include Infrared Sensor With Built In Range Of Adjustment.Thermotic Mixing Valve Control Will Be Located Behind The Accesspanel& Maintain Constant Water Temperature. User Defined Settings Of 1 To 3 Minaret Available.This Timing Will Be Adjustable To Meet Individualapplication Requirement, Provided With Infrared Sensor Thermostatic Controlled Taps With Fail-Safe Temperature Controls. 24 Writing List Board 25 The Writing Unit Shall Comprise Of Flush Mounted 1.5Mm Thick, White Laminate Board, Bonded To A 40Mm High Density Lire Board Sheet For Aoditionalrigidity.The Unit Shall Be Opened To Create A Wall Mounted Writing Surface Within Operating Room.The White Board Shall Be Constructed From 1.6Mmthick, White Laminate Board. 26 Peripheral Lights ( Led ) 27 Eight Sets Of Double Peripheral Lights Shall Be With Stepped Finish Aluminium With Reflectors.Peripheral Lights Shal Be Clean Room Compatible.Ratingof Peripheral Lighting Shall Be Ip 54.Control Equipment For The Peripheral Lighting Shall Be Provided In The Theatre Control Panel To Allow Independentcontrol Of The Lighting Levels By The Surgical Team.Recessed Mounted. 28 Hatch Box 29 The Hatch Box Should Be Provided In Each Operation Theatre To Remove Waste Materials From The Operation Theatre To Dirty Linen Area Just Adjacentto Operation Theatre.Each Hatch Should Be Equipped With Two Doors And The Door Should Be Opened One At A Time. The Hatch Should Be Designedin Such A Way That Only One Door Should Be Opened At One Time.The Uv Light Should Be So Installed That It Is Kept On While Both The Doors Areclosed, This Uv LightHas To Be Automatically Turned Off In Case Of Opening Of Either Of The Doors.There Shall Be Indicators On Both Side Of Ot So Thatdoor Open / Close Status Can Be Monitored From Both Ends. 30 SurgeonS Double Arm Pendant ( Us Fda And European Ce Certified ) : 31 Pendant Should Be Double Arm ( 1000Mm+800Mm ) With Load Carrying Capacity Of 80Kg.The Arm Should Rotate Upto 330°-340° With Adjustablestopper.Dampened Stoppers And Very Low Hand Forces For Horizontal Movements Should Contribute To An Ergonomically Optimized Workplace.Thelarge Interior Cross-Section For Supply Lines Offers Should Completely New Applications With 120Mm Diameter.The Stoppers Should Be Infinitelyvariable From 0-330°-340°. 32 The Service Head Should Be Of Modular Design To Achieve Maximum Location Efficiency With Minimum Required Space.Service Head Should Designto Host, Base, Gas Module ( Upto 8 Gas Outlets ) , Electrical Module ( 10 Electrical Outlets ) And Two Shelves And One Infusion Pump Rack. 33 The Total Length Of The Manager Should Be 800Mm Surgeon Pendant 34 Should Have 2 Arms With Shelves As Per Following Details: 35 Horizontal Arm System-2 36 Weight Carrying Capacity-80 Kg 37 5 / 15 Amp. Electrical Sockets Without Switches-10 Nos. 38 Shelves With Slide Rails-2 Nos 39 Provision To Fix Gas Outlets ( I.E. ) Oxygen-2, Vacuum-2, Air 4 Bar-1, 40 Air 7 Bar-1, C02-1 Agss-1 41 Ceiling Mounting System Up To 1000Mm-1 42 Ceiling Cover For False Ceiling-1 43 AnaesthetistS Single Arm Pendant ( Us Fda And European Ce Certified ) : 44 Pendant Should Be Single Arm ( 900Mm ) Withload Carrying Capacity Of 80 Kg. Dampened Stoppers And Very Low Hand Forces For Horizontalmovements Should Contribute To An Ergonomically Optimized Workplace.The Interior Cross Section Available For Supply Lines Shall Be Minimum120mm Diameter.The Stoppers Should Be Infinitely Variable From 0-330°-340°.The Service Head Should Be Provided With The Modular Design Toachieve Maximum Supply With Minimum Required Space.Service Head Should Be Designed To Host, Gas Module, Electric Module And Shelves. Upto8 Gas Outlets & 10 Electrical Outlets.Racks & Shelves Should Be Provided To Mount The Equipments Like Monitor Etc.The Total Length Of Themanager Should Be 800Mm.Anaesthesia Pendent Should Be Have 1 Arm With Shelves As Per Following Details: 45 Horizontal Arm System-1 46 Weight Carrying Capacity-80 Kg 47 5 / 15 Amp.Electrical Sockets Without Switches-10 Nos. 48 Shelves With Slide Rails-2 Nos 49 Provision To Fix Gas Outlets ( 8 Nos. ) Oxygen-2, Vacuum-2, Air 4 Bar- 50 1, N20-1, Agss-1.Spare-1 51 Ceiling Mounting System Up To 1000Mm-1 52 Ceiling Cover For False Ceiling-1 53 Electrical Work Inside The Ot 54 All High Voltage Equipment Is Installed In A Separate Enclosure.The Remote Cabinet Houses The Operating Lamp Transformers Main Failure Relays, Electrical For All Circuits Within The Operating Theatre.All Internal Wiring Is Terminated In Connectors With Screw And Clamp & Spring Connections Of Theclip-On Type Mounted, On A Din Rail Labelled With Indelible Proprietary Labels. Individual Miniature Circuit Breakers Shall Be Provided To Protect Allinternal Circuits With 5 / 16-Amp Switch Sockets For The Modular Operation Theatre.Mcb For Circuits For Critical Equipments And Outlets Shall Beclearly Marked For Ups Connection-Operating Light, Monitor, Ot Panel, Ot General Light And Other Critical Equipments ( 4 Out Of 10 On The Pendant ) 55 Ot Light With Provision Of Camera ( Us Fda And European Ce Certified ) : 56 Description:Dual Dome Led Surgical Lighting System With One Dedicated Spring-Arm Suspension Flat Pane And Progressive Scan Hd Flat Panelwith An Integrated In-Light Camera System ( Or Only Provision For Installation Of Camera, Flat Panel And Suspension Arm In Future, As May Bespecified In The Boq ) The Ot Light Should Be European Us Fda And European Ce Certified Ot Light. Operating Room Surgical Lighting Systemwill Provide An Ideal Combination Of Brightness, Manoeuvrability, And Shadow Resolution Without Sacrificing Colour Accuracy Through A Consistentled Technology With A Faceted Reflector Design Technology, Such Lighting System Will Have The Following Technical Specifications: 57 Colour Temperature Range-4000-5000 K Adjustable, Minimum Range 58 Field Size Diameter ( Variable ) -Minimum140mm At Minimum, 59 Maximum 300Mm At Maximum 60 Depth Of Field-Minimum 650Mm For All Field Diameters. 61 Lllumination Level At No Dimming-Minimum 160000 Lux 62 Colour Rendition Index-General Ra 94 Or More, Enhanced Red ( R9 ) 63 97 Or More 64 Control-Wall Control, Touch Panel Rotation-Around X-360 Degrees, Around Y-290 Degrees Location Positioning ( C / 1 Of Light ) -Within A Minimumradius Of 15 Mts From Mount ( Both Lights ) 65 Minimum Floor Clearance-1.5 Mt For Ceiling Height Of 2.75 Mt. Vertical Adjustment Range-+450Mm To-600Mm W.R.T Main Arm Position ( Minimum ) 66 Secondary Arm Tilt Angle ( Z ) Range-+ / -30 Degree Minimum 67 Sterilizable Handle-Yes 68 Mounting Type-Ceiling 69 Supply Voltage Range-140-270 Vac 50 / 60 Hz 70 Bulb Type-Led 71 Protection-Ip54 72 Maximum Power Consumption-Dimming Range ( Minimum ) -10%-100% 73 Operating / Storage Humidity- 10-95%- 74 Life Of Light Source->40, 000 Hrs 75 Camera System With Monitor ( Compatible For O.T.Light ) 76 Description:Integrated In-Light Camera System Will Be Integrated At The Centre Of One Of The Domes Of This Lighting System In Order To Captureimages & Video Sequences Of The Open Cases.The Camera And Mount Should Be Such That The Camera Can Be Removed And Fixed To Different Lightsas Per Need, Without Any Special Tools Or Training. Such A Camera Will Have The Following Specifications: 77 Signal To Noise Ratio ( S / N Ratio ) -<50Db 78 Minimum Lllumination-<3Lx 79 Optical Zoom-25-30X 80 Digital Zoom-21-15X 81 Power Suppy-Max.12W. 82 Relative Humidity-Upto 90% 83 Video Output-Dvi, S-Video & Composite Video 84 White Balance & Gain-Automatic I Manual 85 Such Surgical Light System Will Be Complaint With Relevant European / Us Standards Such Light And Integrated Camera Wil Have Control Throughtouch Panel Of The Control Equipment Placed Inside The Operating Room And At The Documentation Station / Nurse Works Station. 86 Flat Panel Monitor 87 Will Be 26High Definition Progressive Scan Flat-Panel Monitors With Ceiling Mounted Spring Arm Suspension To Support High-Definition / Hdtv Progressive Scan Images And Will Be Able To Support And Display Dvvhdtv, Rgbhv, S-Video, Composite Video Signals. 88 The Flat Panel Suspension Will Be Ready With The Cables For Integration Of High Definition Digitl ( Dvi / Hdtv ) , Rgbhv ( High Resölution ) , Svhs ( S-Video ) , Composite Video Signals To Travel From The Various Sources Of Video Like Endoscopic Camera, Room Camera, Inflight Camera, High Definition Flat Panel Monitors, While Assuring Native Resolution / Signal. 89 Such Monitor Will At Least Meet The Following Technical Criteria: 90 Resolution-1600 Dots X1200 Dots, Progressive Scan Display Colors-16 Million Colours Inputs-Dvi, Rgbhv, S-Video, Composite Video Synchronization-2.5-5.0 Vpp Separated Sync Response Time-<25 Ms 91 Cable Kit For Integration-Dvi, Fibre Optic, Rgbhv, S-Video, Composite 92 Ups System With Isolation Transformer 10Kva 93 Semi Modular Ot ( 07 Nos ) 94 Pre-Fabricated Ceiling Panel 95 Pre-Fabricated Modular Construction Shall Be Designed And Constructed For Exact Size.The Ceiling Will Beconstructed Using 1.0Mm Ss 304 Sheet Panel In Thefront Panels & 0.8Mm Ss 304 At The Back Panel.The Corebetween Two Panels Will Consist Of Rigid Polyurethane Foam Which Has Been Injected Under High Pressure, With Aminimum, Density Of 40 Kg / M3.The Individual Wall Panels Shall Use The Tongue And Groove Technology Forjoining Two Panels, No Welding Will Be Allowed. The Gaps Between Panels Be Suitably Filled With Metalfiller / Epoxy And Sanded Flush. 96 Anti-Bacterial / Anti-Fungal Paint 97 The Internal Surfaces Of The Ss-304 Ot Walls Should Be Sprayed With Water Based, Non-Reflective Liquid Plastic, Toa Colour Approved Be The Architect A Minimum Dry Film Thickness Of 300 Microns. These Plastic Coatings Shouldoverlap The Floor Covering, Ceiling System And Door Frames By 25Mm To Provide A Continuous Sealed Surface. Sterile Coating Applied Should Be Water Resistant, Does Not Support Bacteriological Or Fungal Growth And Isresistant To Most Chemicals Commonly Used In Hospital Departments.The Sterile Coating Should Remainunaffected By Radiation And Other Ionizing Radiation At Levels In Excess Of 1000 Mrad And Is Classified To Class Lwhen Tested In Accordance With The Requirements Specified Under Bs.476:Part 7 1971, Surface Spread Of Flame Test For Materials.The Coating System Should Be Easily Maintained And Can With Stand Repeated Cleaning Withalkaline Detergents, Antiseptics And Fumigation Agents Without Any Degradation To The Surface Finish Orperformance. 98 Laminar Air Flow Ceiling 99 Each Modular Ot Shall Have Plan Air Ceiling.The Plan Air Ceiling Shal Be Constructed Out Of 2 Mm Thick Extrudedaluminium Profiles, Overall Size 2400X 2400 Mm Or Larger As Per Actual Layout, Having Six Nos Hepa Filters Withmpps Efficiency Of 99.995% And Spot Efficiency Of 99.99%@0.3 Micron.The Plenum Should Provide Therequired Air Volume To Achieve The Temperature, Pressure ( 15-30Pa ) And Humidity Specified, And Terminalvelocity 90 To 120 Fpm At The Diffuser Face.Air And Light Diffuser Made Of Two Layer Of Mono Filament Precisionwoven Polyester For Plan Air Ceiling To Give A Laminar Flow Of Filtered Air. It Shall Also Provide A Shadow Lesslighting System With Control Of The Intensity Of Luminance By Using High Efficiency Electronic Fuorescent Tubes. All Hepa Filters Shall Be Factory Tested And Certified In Accordance With International Standards.All Ceiling Shallinclude Integral Lighting And Composite Air / Light Diffuser.Air Shall Be Diffused Into The After Uniformly Over Thetotal Area.The Laminarflow Ceiling Should Also Have Il Umination Across Its Total Area. 100 Automatic Hermetically Sealing Door 101 2100X1500mm 102 Automatic Door Shall Be Provided At The Main Entry Of The Ot.Door Frames Shall Be Made Of Aluminiumextrusion Profile To Carry Any Door Weight.The Core Door Size Is Of 60Mm Size Built Of High Density Puf ( Density40kg / M3 ) Of 52Mm And 1.5Mm Consist Of Solid Stainless Steel ( Ss-304 ) On Both Side Of The Door.Door Blade Ismade With 3-Tier Specially Designed 3 Slide Heavy Duty Replaceable Epdm Gasket Against Wall Frame. Bottomsealing With 2-Tier Heavy Duty Epdm Gasket To Flush With Finished Floor.Stainless Steel Lever Handle On Both Sideof The Door Blade For Smooth And Easy Door Opening And Closing. The Thickness Of Aluminium Extrusion For Doorframe & Door Panel Surfaces Shall Not Less Than 1.5Mm. There Shall Not Be Any Visible Screws Or Similar Otheruneven Surfaces On The Door Panel. A Lock Shall Be Provided.Door Shall Have Vision Panels ( Viewing Window ) Atleast 300Mmx 300Mm.Automation Of The Door Has Digital Controller, Motor Andsuitable Switches To Open Thedoor Thru Hands, Foots Etc.The Door Size Shall Be As Per Boq. 103 Pressure Relief Dampers 104 Pressure Relief Dampers To Be Provided In Theatre To Prevent Cross Contamination Of Air From Clean And Dirtyareas. Suitably Sized Air Pressure Relief Damper Will Be Strategically Placed, Enable Differential Room Pressure Tobe Maintained And Ensure That When Doors Are Opened Between Clean And Dirty Area.Counter Weight Balancingsystem Will Be Provided In The Prd To Maintain Positive Pressure Inside The Operation Theatre.Air Pressurestabilizers Will Have Unique Capability Of Controlling Differential Pressure To Close Tolerance.The Prd Will Remainclosed At Pressure Below The Set Pressure And Will Open Fully At Pressure Only Fractionally Above The Thresholdpressure.The Body Will Be Epoxy Powder Coated As Per Standard Bs Colours And Meets International Quality Andsafety Requirements.First Class Electrolyzed Steel Plate Will Be Used For Body And With High-Grade Ss 304 Stainless Steel For Blades. 105 Anti-Static Flooring 106 Anti-Static Flooring ( Static Conductive Tiles ) :The Floor Finishing The Operating Room Will Be Imported 2 Mmstatics Conductive Pvc Tiles, Laid On A Semi Conductive Adhesive Base. The Floor Finish Will Terminate At The Roomperimeter Passing Over A Concealed Cove Former And Continuing Up The Wall For 100 Mm. Flooring Will Fulfil En.Itwill Have Chemical Resistance As Per En 423. It Will Have Electrical Resistance Conforming To En 1081 / Iec 613404- 1. All Joints Will Be Welded And The Plastic Wall Finish Will Overlap The Floor Coving By 25Mm, To Provide Acontinuous Sealed Surface.The Self-Levelling Compound Will Be Of The Type That Does Not Promotesactenological Growth.Copper Grounding Suips ( 0.05Mm Thick, 5Umm Wide ) Will Be Laid Flat On The Floor In Theconductive Adhesive And Connect To Copper Wire Of Grounding. 107 2-Bay Scrub Sink 108 Compact Surgical Scrub Sink Will Be Designed For Use In Operation Theatre Complex Providing Surgeons With Aconvenient Sink For Pre-Up Scrub Up. Each Fixture Will Be Fabricated From Heavy Gauge Type 304 Stainless Steel & Will Be Welded Construction Polished To A Satin Finish.The Scrub Sink Will Be Provided With A Front Access Panels, Which Will Be Easily Removed For Access To The Water Control Valve, Waste Connections Stoppers & Strainers. Handsfree Operation Will Include Infrared Sensor With Built In Range Of Adjustment. Thermotic Mixing Valvecontrol Will Be Located Behind The Access Panel & Maintain Constant Water Temperature.User Defined Settingsof 1 To 3 Minaret Available.This Timing Will Be Adjustable To Meet Individual Application Requirement, Providedwith Infrared Sensor Thermostatic Controlled Taps With Fail-Safe Temperature Controls. 109 Peripheral Lights ( Led ) 110 Eight Sets Of Double Peripheral Lights Shall Be With Stepped Finish Aluminium With Reflectors.Peripheral Lightsshall Be Clean Room Compatible.Rating Of Peripheral Lighting Shall Be Ip 54. Control Equipment For Theperipheral Lighting Shall Be Provided In The Theatre Control Panel To Allow Independent Control Of The Lightinglevels By The Surgical Team.Recessed Mounted. 111 AnaesthetistS Single Arm Pendant ( Indigenous ) : 112 Pendant Should Be Single Arm ( 900Mm ) With Load Carrying Capacity Of 80 Kg.Dampened Stoppers And Very Lowhand Forces For Horizontal Movements Should Contribute To An Ergonomically Optimized Workplace.The Interiorcross Section Available For Supply Lines Shall Be Minimum 120Mm Diameter. The Stoppers Should Be Infinitelyvariable From 0-330°-340°.The Service Head Should Be Provided With The Modular Design To Achieve Maximumsupply With Minimum Required Space. Service Head Should Be Designed To Host, Gas Module, Electric Moduleand Shelves.Upto 8 Gas Outlets & 10 Electrical Outlets. Racks & Shelves Should Be Provided To Mount Theequipments Like Monitor Etc.The Total Length Of The Manager Should Be 800Mm.Anaesthesia Pendent Shouldbe Have 1 Arm With Shelves As Per Following Details: 113 Horizontal Arm System-1 114 Weight Carrying Capacity-80 Kg 115 5 / 15 Amp. Electrical Sockets Without Switches-10 Nos. 116 Shelves With Slide Rails-2 Nos 117 Provision To Fix Gas Outlets ( 8 Nos ) Oxuren-2, Vauum-2 Air 4 Bar- 118 1, N20-1, Agss-1.Spare-1 119 Ceiling Mounting System Up To 1000Mm-1 120 Ceiling Cover For False Ceiling-1 121 Electrical Work Inside The Ot 122 All High Voltage Equipment Is Installed In A Separate Enclosure. The Remote Cabinet Houses The Operating Lamptransformers Main Failure Relays, Electrical For All Circuits Within The Operating Theatre.All Internal Wiring Isterminated In Connectors With Screw And Clamp & Spring Connections Of The Clip-On Type Mounted, On A Din Raillabelled With Indelible Proprietary Labels. Individual Miniature Circuit Breakers Shall Be Provided To Protect Allinternal Circuits With 5 / 16-Amp Switch Sockets For The Modular Operation Theatre.Mcb For Circuits For Criticalequipments And Outlets Shall Be Clearly Marked For Ups Connection-Operating Light, Monitor, Ot Panel, Ot General Light And Other Critical Equipments ( 4 Out Of 10 On The Pendant ) 123 Ot Light ( Indigenous ) : 124 Description:Dual Dome Led Surgical Lighting System.Operating Room Surgical Lighting System Will Provide Anideal Combination Of Brightness, Manoeuvrability, And Shadow Resolution Without Sacrificing Colour Accuracythrough A Consistent Led Technology With A Faceted Reflector Design Technology, Such Lighting System Will Havethe Following Technical Specifications: 125 Field Size Diameter ( Variable ) - Minimum 120Mm At Minimum, 126 Maximum 200Mm At Maximum 127 Depth Of Field-Minimum 650Mm For All Field Diameters. 128 Illumination Level At No Dimming-Minimum 120000 Lux 129 Colour Rendition Index-General Ra 94 Or More, Enhanced Red ( R9 ) 130 97 Or More 131 Minimum Floor Clearance-1.5 Mt For Ceiling Height Of 2.75 Mt. Vertical Adjustment Range-+450Mm To-600Mm W.R.T Main Arm Position ( Minimum ) 132 Secondary Arm Tilt Angle ( Z ) Range-+ / -30 Degree Minimum 133 Sterilizable Handle-Yes 134 Mounting Type-Ceiling 135 Supply Voltage Range-140-270 Vac 50 / 60 Hz 136 Bulb Type-Led 137 Protection-Ip54 138 Maximum Power Consumption-Dimming Range ( Mir.Mum ) -10%-100% 139 Operating / Storage Humidity-10-95%- 140 Life Of Light Source->20, 000 Hrs 141 Ups System With Isolation Transformer 10Kva 142 Gst Extra As Per Applicable

Key Value

Document Fees
INR 17700 /-
EMD
INR 938000.0 /-
Tender Value
INR 4.69 Crore /-

BOQ Items

Name of Work: Modular Operation Theater, Semi Modular Operation TheaterWork For Kaili Hospital Basti
Sl. No. Item Description
1MODULAR OT (04 NOS)
2Pre-fabricated Walls & Ceiling Panel
3Pre-fabricated modular constructin shall be designed and constructed for exact size. The prefabricated Operating Room will be free standingstructure from composite free-standing insulated steel wall panels.The wall will be constructed using 1.0mm SS 304 sheet panel in the front panels&0.8mm SS 304at the back panel. The core between two panels will consist of rigid polyurethane foam which has been injected under highpressure,with a minimum, density of 40 kg/m3.The individual wall panels shall use the tongue and groove technology for joining two panels,nowelding will be allowed.The gaps between panels be suitably filled with metal filler/epoxy and sanded flush.
4The external walls of the room shall be constructed with solid bricks and mortar by the hospital as part of its scope of work.The inner surface wallsshall be fixed to the brick wall with essential supports.There shall be minimum possible cavity/gap in between the masonry and steel walls.Thetotal distance between inside and outside surface of OR shall be variable to suit architects" layout,but shall be sufficient for flush mounting of theequipments.The cavity between inner and outer walls shall be left with minimum obstructions for possible addition of equipment at a later date andto enable services,pipes, conduits etc, to be run within the cavity.All wall-mounted equipment shall be flush mounted and sealed into theatre.Thewall panel design and construction shall allow for installation and suppor of all equipment and provision of openings required for the installations, without affecting rigidity and strength.Access boxes shall be fitted to the rear of all the wall-mounted equipments to enable maintenance to becarried out from outside the operating room.All the sharp edges and corners shall be smoothened to avoid bacterial contamination.
5Anti Bacterial/ Anti Fungal-Paint
6The internal surfaces of the SS-304 OT walls should be sprayed with water based,non-reflective liquid plastic,to a colour approved be the architecta minimum dry film thickness of 300 microns.These plastic coatings should overlap the floor covering,ceiling system and door frames by 25mm toprovide a continuous sealed surface.Sterile Coating applied should be water resistant,does not support bacteriological or fungal growth and isresistant to most chemicals commonly used in hospital departments.The sterile coating should remain unaffected by radiation and other ionizingradiation at levels in excess of 1000 mrad and is classified to class I when tested in accordance with the requirements specified under BS.476:part7 1971,Surface spread of flame Test for Materials.The coating system should be easily maintained and can with stand repeated cleaning withalkaline detergents,antiseptics and fumigation agents without any degradation to the surface finish or performance.
7Laminar Air Flow Ceiling
8Each modular OT shali have Plan Air Ceiling.The Plan Air Ceiling shall be constructed out of 2 mm thick extruded aluminium profiles,overall size2400x2400 mm or larger as per actual layout,having six nos HEPA filters with MPPS efficiency of 99.995% and spot efficiency of 99.99% @0.3 micron.The plenum should provide the required air volume to achiee the temperature,pressure (15-30Pa) and humidity specified,and terminalvelocity 90 to 120 FPM at the diffuser face.Air and light diffuser made of two layer of mono filament precision woven polyester for plan air ceiling togive a laminar flow of filtered air.It shall also provide a shadow less lighting system with control of the intensity of luminance by using highefficiency electronic fluorescent tubes.All HEPA filters shall be factory tested and certified in accordance with international standards.All ceilingshall include integral lighting and composite air/light diffuser.Air shall be diffused into the after uniformly over the total area.The laminar flowceiling should also have illumination across its total area.
9Automatic Hermetically Sealing Door
102100x1500mm
11Automatic door shall be provided at the main entry of the OT.Door frames shall be made of aluminium extrusion profile to carry any door weight. The core door size is of 60mm size built of high density PUF(density 40kg/m3) of 52mm and 1.5mm consist of Solid Stainless Steel (SS-304) onboth side of the door.Door blade is made with 3-tier specially designed 3 slide heavy duty replaceable EPDM gasket against wall frame.Bottomsealing with 2-tier heavy duty EPDM gasket to flush with finished floor.Stainless Steel lever handle on both side of the door blade for smooth andeasy door opening and closing.The thickness of aluminium extrusion for door frame & door panel surfaces shall not less than 1.5mm.There shallnot be any visible screws or similar other uneven surfaces on the door panel. A lock shall be provided. Door shall have vision panels(viewingwindow)at least 300mmx 300mm.Automation of the door has Digilal Controlier,Motor and suitable switches to open the door thru hands,foots etc. The door size shall be as per BOQ.
12Surgeon Control Panel
13The control panel will be user friendly and operation and maintenance will be easy.The control panel shall be "Tiled Membrane" type;can beconfigured to incorporate all the services that operating theatre staff required.The fascia shall be made with superior quality UV resistant. sterilisable membrane.The membrane backing is made of 2.5 mm thick aluminium that is rust resistance.The connection between the surgeoncontrol panel and the distribution board will be by a mutiplexed system. The panel will contain 6 servicestiles for: (a)Time day clock(b) Time elapsed clock(c) Temperature/humidity indicator(d)General Lighting System(e) Medical gas alarm panel(1)Hand free phone.
14LED TWIN Plate X-ray Viewer
15The operation theatre shall be equipped with a X-ray Viewing LED Screen, designed to provide a high level of control luminance without flicker.Itshall be equipped with loaded clips to secure the X-ray negative when in use.
16Pressure Relief Dampers
17Pressure relief dampers to be provided in theatre to prevent cross contamination of air from clean and dirty areas. Suitably sized air pressure reliefdamper will be strategically placed,enable differential room pressure to be maintained and ensure that when doors are opened between clean anddirty area.Counter weight balancing system will be provided in the PRD to maintain positive pressure inside the operation theatre.Air pressurestabilizers will have unique capability of controlling differential pressure to close tolerance.The PRD will remain closed at pressure below the setpressure and will open fully at pressure only fractionally above the threshold pressure. The body will be epoxy powder coated as per standard BScolours and meets international quality and safety requirements. First class electrolyzed steel plate will be used for body and with high-grade SS304 Stainless steel for blades.
18Anti-Static Flooring
19Anti-Static Flooring (Static conductive tiles):The floor finishing the operating room will be imported 2 mm statics conductive PVC tiles,laid on asemi conductive adhesive base.The floor finish will terminate at the room perimeter passing over a concealed cove former and continuing up thewall for 100 mm.Flooring will fulfil EN.It will have chemical resistance as per EN 423. It will have electrical resistance conforming to EN 1081/IEC613404-1.All joints will be welded and the plastic wall finish will overlap the floor coving by 25mm,to provide a continuous sealed surface. The self- levelling compound will be of the type that does not promote bacteriological growth. Copper grounding strips (0.05mm thick,50mm wide) will be laidflat on the floor in the conductive adhesive and connect to copper wire of grounding.
20Storage Cabinets
21Providing,Fixing,Supply and Installation of storage unit will be made with the wall cladding material i.e. SS-304.The unit will be divided into 2 equalparts and each part will have individual glass doors with locking system.Each part will have glass racks to keep surgical medicines etc.
222-Bay Scrub Sink
23Compact Surgical Scrub sink will be designed for use in Operation theatre complex providing surgeons with a convenient sink for pre-up scrub up. Each fixture will be fabricated from heavy gauge type 304 stainless steel & will be welded construction polished to a satin finish.The scrub sink willbe provided with a front access panels,which will be easily removed for access to the water control valve, waste connections" stoppers &strainers. Handsfree operation will include infrared sensor with built in range of adjustment.Thermotic Mixing Valve Control will be located behind the accesspanel& maintain constant water temperature. User defined settings of 1 to 3 minaret available.This timing will be adjustable to meet individualapplication requirement,provided with infrared sensor thermostatic controlled taps with fail-safe Temperature controls.
24Writing List Board
25The writing unit shall comprise of flush mounted 1.5mm thick,white laminate board,bonded to a 40mm high density lire board sheet for aoditionalrigidity.The unit shall be opened to create a wall mounted writing surface within operating room.The white board shall be constructed from 1.6mmthick,white laminate board.
26Peripheral Lights (LED)
27Eight sets of double peripheral lights shall be with stepped finish aluminium with reflectors.Peripheral lights shal be clean room compatible.Ratingof peripheral lighting shall be IP 54.Control equipment for the peripheral lighting shall be provided in the theatre control panel to allow independentcontrol of the lighting levels by the surgical team.Recessed mounted.
28Hatch Box
29The Hatch Box should be provided in each operation theatre to remove waste materials from the operation theatre to dirty Linen area just adjacentto operation Theatre.Each Hatch should be equipped with two doors and the door should be opened one at a time. The Hatch should be designedin such a way that only one door should be opened at one time.The UV light should be so installed that it is kept on while both the doors areclosed,this UV light"has to be automatically turned off in case of opening of either of the doors.There shall be indicators on both side of OT so thatdoor open / close status can be monitored from both ends.
30Surgeon"s Double Arm Pendant(US FDA and European CE Certified):
31Pendant should be Double arm(1000mm+800mm)with load carrying capacity of 80Kg.The arm should rotate upto 330°-340° with adjustablestopper.Dampened stoppers and very low hand forces for horizontal movements should contribute to an ergonomically optimized workplace.Thelarge interior cross-section for supply lines offers should completely new applications with 120mm diameter.The stoppers should be infinitelyvariable from 0-330°-340°.
32The service head should be of modular design to achieve maximum location efficiency with minimum required space.Service head should designto host,Base,Gas Module (Upto 8 Gas outlets), Electrical Module (10 Electrical outlets) and two shelves and one Infusion pump rack.
33The total length of the manager should be 800mm Surgeon pendant
34should have 2 arms with shelves as per following details:
35Horizontal arm system-2
36Weight carrying capacity-80 Kg
375/15 Amp. Electrical sockets without switches-10 Nos.
38Shelves with slide rails-2 Nos
39Provision to fix Gas Outlets (i.e.) Oxygen-2,Vacuum-2,Air 4 Bar-1,
40Air 7 Bar-1,C02-1 AGSS-1
41Ceiling mounting system up to 1000mm-1
42Ceiling cover for false ceiling-1
43Anaesthetist"s Single Arm Pendant (US FDA and European CE Certified):
44Pendant should be Single arm (900mm)withload carrying capacity of 80 Kg. Dampened stoppers and very low hand forces for horizontalmovements should contribute to an ergonomically optimized workplace.The interior cross section available for supply lines shall be minimum120mm diameter.The stoppers should be infinitely variable from 0-330°-340°.The service head should be provided with the modular design toachieve maximum supply with minimum required space.Service head should be designed to host,Gas Module,Electric Module and shelves. Upto8 Gas outlets & 10 Electrical Outlets.Racks & shelves should be provided to mount the equipments like monitor etc.The total length of themanager should be 800mm.Anaesthesia pendent should be have 1 arm with shelves as per following details:
45Horizontal arm system-1
46Weight carrying capacity-80 Kg
475/15 Amp.Electrical sockets without switches-10 Nos.
48Shelves with slide rails-2 Nos
49Provision to fix Gas Outlets (8 Nos.) Oxygen-2, Vacuum-2, Air 4 Bar-
501,N20-1,AGSS-1.Spare-1
51Ceiling mounting system up to 1000mm-1
52Ceiling cover for false ceiling-1
53Electrical Work inside the OT
54All high voltage equipment is installed in a separate enclosure.The remote cabinet houses the operating lamp transformers main failure relays, electrical for all circuits within the operating theatre.All internal wiring is terminated in connectors with screw and clamp & spring connections of theclip-on type mounted,on a DIN rail labelled with indelible proprietary labels. Individual miniature circuit breakers shall be provided to protect allinternal circuits with 5/16-amp switch Sockets for the Modular Operation Theatre.MCB for Circuits for Critical equipments and outlets shall beclearly marked for UPS connection-OPERATING LIGHT,MONITOR,OT PANEL,OT GENERAL LIGHT and other critical equipments(4 out of 10 on the pendant)
55OT Light with provision of camera(US FDA and European CE Certified):
56Description:Dual Dome LED Surgical Lighting System with one dedicated Spring-Arm Suspension flat pane and Progressive Scan HD Flat Panelwith an Integrated In-Light Camera System (OR Only provision for installation of camera,flat panel and suspension arm in future,as may bespecified in the BOQ)The OT light should be European US FDA and European CE certified OT Light. Operating Room Surgical Lighting Systemwill provide an ideal combination of brightness,manoeuvrability, and shadow resolution without sacrificing colour accuracy through a consistentLED technology with a faceted reflector design technology,such Lighting system will have the following technical specifications:
57Colour Temperature range-4000-5000 K adjustable,minimum range
58Field Size Diameter(Variable)-minimum140mm at minimum,
59maximum 300mm at maximum
60Depth of Field-minimum 650mm for all field diameters.
61lllumination Level at no dimming-minimum 160000 Lux
62Colour rendition index-General Ra 94 or more,Enhanced red(R9)
6397 or more
64Control-Wall Control, Touch panel Rotation-Around "X-360 degrees,around "Y-290 degrees Location Positioning (C/1 of light)-Within a minimumradius of 15 Mts from mount (both lights)
65Minimum floor clearance-1.5 Mt for ceiling height of 2.75 Mt. Vertical Adjustment Range-+450mm to-600mm w.r.t main arm position(minimum)
66Secondary Arm Tilt Angle(Z) range-+/-30 degree minimum
67Sterilizable Handle-Yes
68Mounting Type-Ceiling
69Supply Voltage range-140-270 VAC 50/60 Hz
70Bulb Type-LED
71Protection-IP54
72Maximum Power consumption-Dimming Range (Minimum)-10%-100%
73Operating / Storage Humidity- 10-95%-
74Life of Light Source->40,000 Hrs
75Camera System WITH MONITOR (COMPATIBLE FOR O.T.LIGHT)
76Description:Integrated In-Light Camera System will be integrated at the centre of one of the domes of this lighting system in order to captureimages & video sequences of the open cases.The camera and mount should be such that the camera can be removed and fixed to different lightsas per need,without any special tools or training. Such a camera will have the following specifications:
77Signal to Noise Ratio (S/N Ratio)-<50dB
78Minimum lllumination-<3lx
79Optical Zoom-25-30x
80Digital Zoom-21-15x
81Power Suppy-max.12W.
82Relative Humidity-upto 90%
83Video Output-DVI, S-Video & Composite Video
84White Balance & Gain-Automatic I Manual
85Such Surgical Light System will be complaint with relevant European/US standards Such Light and Integrated Camera wil have control throughTouch Panel of the control equipment placed inside the operating room and at the documentation station/nurse works station.
86Flat Panel Monitor
87Will be 26"High Definition Progressive Scan Flat-panel Monitors with ceiling mounted spring arm suspension to support high-definition/HDTV progressive Scan images and will be able to support and display DVVHDTV, RGBHV, S-Video, Composite video signals.
88The flat Panel suspension will be ready with the cables for integration of High Definition Digitl (DVI/HDTV), RGBHV (High Resölution), SVHS (S- Video), Composite video signals to travel from the various sources of video like endoscopic camera,room camera,inflight camera,high definition flat panel monitors,while assuring native resolution/signal.
89Such Monitor will at least meet the following technical criteria:
90Resolution-1600 dots x1200 dots,Progressive Scan Display Colors-16 Million Colours Inputs-DVI, RGBHV, S-Video, Composite Video Synchronization-2.5-5.0 VPP separated sync Response Time-<25 ms
91Cable kit for Integration-DVI,fibre Optic, RGBHV, S-Video,Composite
92UPS System with isolation transformer 10KVA
93SEMI MODULAR OT (07 NOS)
94Pre-fabricated Ceiling Panel
95Pre-fabricated modular construction shall be designed and constructed for exact size.The ceiling will beconstructed using 1.0mm SS 304 sheet panel in thefront panels & 0.8mm SS 304 at the back panel.The corebetween two panels will consist of rigid polyurethane foam which has been injected under high pressure, with aminimum,density of 40 kg/m3.The individual wall panels shall use the tongue and groove technology forjoining two panels,no welding will be allowed. The gaps between panels be suitably filled with metalfiller/epoxy and sanded flush.
96Anti-Bacterial/Anti-Fungal Paint
97The internal surfaces of the SS-304 OT walls should be sprayed with water based,non-reflective liquid plastic,toa colour approved be the architect a minimum dry film thickness of 300 microns. These plastic coatings shouldoverlap the floor covering, ceiling system and door frames by 25mm to provide a continuous sealed surface. Sterile Coating applied should be water resistant,does not support bacteriological or fungal growth and isresistant to most chemicals commonly used in hospital departments.The sterile coating should remainunaffected by radiation and other ionizing radiation at levels in excess of 1000 mrad and is classified to class lwhen tested in accordance with the requirements specified under BS.476:part 7 1971,Surface spread of flame Test for Materials.The coating system should be easily maintained and can with stand repeated cleaning withalkaline detergents, antiseptics and fumigation agents without any degradation to the surface finish orperformance.
98Laminar Air Flow Ceiling
99Each modular OT shall have Plan Air Ceiling.The Plan Air Ceiling shal be constructed out of 2 mm thick extrudedaluminium profiles, overall size 2400x 2400 mm or larger as per actual layout,having six nos HEPA filters withMPPS efficiency of 99.995% and spot efficiency of 99.99%@0.3 micron.The plenum should provide therequired air volume to achieve the temperature, pressure(15-30Pa) and humidity specified, and terminalvelocity 90 to 120 FPM at the diffuser face.Air and light diffuser made of two layer of mono filament precisionwoven polyester for plan air ceiling to give a laminar flow of filtered air. It shall also provide a shadow lesslighting system with control of the intensity of luminance by using high efficiency electronic fuorescent tubes. All HEPA filters shall be factory tested and certified in accordance with international standards.All ceiling shallinclude integral lighting and composite air/light diffuser.Air shall be diffused into the after uniformly over thetotal area.The laminarflow ceiling should also have il umination across its total area.
100Automatic Hermetically Sealing Door
1012100x1500mm
102Automatic door shall be provided at the main entry of the OT.Door frames shall be made of aluminiumextrusion profile to carry any door weight.The core door size is of 60mm size built of high density PUF (density40kg/m3)of 52mm and 1.5mm consist of Solid Stainless Steel (SS-304) on both side of the door.Door blade ismade with 3-tier specially designed 3 slide heavy duty replaceable EPDM gasket against wall frame. Bottomsealing with 2-tier heavy duty EPDM gasket to flush with finished floor.Stainless Steel lever handle on both sideof the door blade for smooth and easy door opening and closing. The thickness of aluminium extrusion for doorframe & door panel surfaces shall not less than 1.5mm. There shall not be any visible screws or similar otheruneven surfaces on the door panel. A lock shall be provided.Door shall have vision panels (viewing window) atleast 300mmx 300mm.Automation of the door has Digital Controller,Motor andsuitable switches to open thedoor thru hands,foots etc.The door size shall be as per BOQ.
103Pressure Relief Dampers
104Pressure relief dampers to be provided in theatre to prevent cross contamination of air from clean and dirtyareas. Suitably sized air pressure relief damper will be strategically placed,enable differential room pressure tobe maintained and ensure that when doors are opened between clean and dirty area.Counter weight balancingsystem will be provided in the PRD to maintain positive pressure inside the operation theatre.Air pressurestabilizers will have unique capability of controlling differential pressure to close tolerance.The PRD will remainclosed at pressure below the set pressure and will open fully at pressure only fractionally above the thresholdpressure.The body will be epoxy powder coated as per standard BS colours and meets international quality andsafety requirements.First class electrolyzed steel plate will be used for body and with high-grade SS 304 Stainless steel for blades.
105Anti-Static Flooring
106Anti-Static Flooring(Static conductive tiles):The floor finishing the operating room will be imported 2 mmstatics conductive PVC tiles, laid on a semi conductive adhesive base. The floor finish will terminate at the roomperimeter passing over a concealed cove former and continuing up the wall for 100 mm. Flooring will fulfil EN.Itwill have chemical resistance as per EN 423. It will have electrical resistance conforming to EN 1081/IEC 613404- 1. All joints will be welded and the plastic wall finish will overlap the floor coving by 25mm,to provide acontinuous sealed surface.The self-levelling compound will be of the type that does not promoteSactenological growth.Copper grounding suips (0.05mm thick,5umm wide) will be laid flat on the floor in theconductive adhesive and connect to copper wire of grounding.
1072-Bay Scrub Sink
108Compact Surgical Scrub sink will be designed for use in Operation theatre complex providing surgeons with aconvenient sink for pre-up scrub up. Each fixture will be fabricated from heavy gauge type 304 stainless steel & will be welded construction polished to a satin finish.The scrub sink will be provided with a front access panels, which will be easily removed for access to the water control valve, waste connections" stoppers & strainers. Handsfree operation will include infrared sensor with built in range of adjustment. Thermotic Mixing ValveControl will be located behind the access panel & maintain constant water temperature.User defined settingsof 1 to 3 minaret available.This timing will be adjustable to meet individual application requirement,providedwith infrared sensor thermostatic controlled taps with fail-safe Temperature controls.
109Peripheral Lights(LED)
110Eight sets of double peripheral lights shall be with stepped finish aluminium with reflectors.Peripheral lightsshall be clean room compatible.Rating of peripheral lighting shall be IP 54. Control equipment for theperipheral lighting shall be provided in the theatre control panel to allow independent control of the lightinglevels by the surgical team.Recessed mounted.
111Anaesthetist"s Single Arm Pendant (Indigenous):
112Pendant should be Single arm (900mm)with load carrying capacity of 80 Kg.Dampened stoppers and very lowhand forces for horizontal movements should contribute to an ergonomically optimized workplace.The interiorcross section available for supply lines shall be minimum 120mm diameter. The stoppers should be infinitelyvariable from 0-330°-340°.The service head should be provided with the modular design to achieve maximumsupply with minimum required space. Service head should be designed to host,Gas Module, Electric Moduleand shelves.Upto 8 Gas outlets & 10 Electrical Outlets. Racks & shelves should be provided to mount theequipments like monitor etc.The total length of the manager should be 800mm.Anaesthesia pendent shouldbe have 1 arm with shelves as per following details:
113Horizontal arm system-1
114Weight carrying capacity-80 Kg
1155/15 Amp. Electrical sockets without switches-10 Nos.
116Shelves with slide rails-2 Nos
117Provision to fix Gas Outlets (8 Nos )Oxuren-2,Vauum-2 Air 4 Bar-
1181,N20-1,AGSS-1.Spare-1
119Ceiling mounting system up to 1000mm-1
120Ceiling cover for false ceiling-1
121Electrical Work inside the OT
122All high voltage equipment is installed in a separate enclosure. The remote cabinet houses the operating lamptransformers main failure relays,electrical for all circuits within the operating theatre.All internal wiring isterminated in connectors with screw and clamp & spring connections of the clip-on type mounted,on a DIN raillabelled with indelible proprietary labels. Individual miniature circuit breakers shall be provided to protect allinternal circuits with 5/16-amp switch Sockets for the Modular Operation Theatre.MCB for Circuits for criticalequipments and outlets shall be clearly marked for UPS connection-OPERATING LIGHT, MONITOR, OT PANEL, OT GENERAL LIGHT and other critical equipments (4 out of 10 on the pendant)
123OT Light (Indigenous):
124Description:Dual Dome LED Surgical Lighting System.Operating Room Surgical Lighting System will provide anideal combination of brightness, manoeuvrability, and shadow resolution without sacrificing colour accuracythrough a consistent LED technology with a faceted reflector design technology,such Lighting system will havethe following technical specifications:
125Field Size Diameter (Variable)- minimum 120mm at minimum,
126maximum 200mm at maximum
127Depth of Field-minimum 650mm for all field diameters.
128Illumination Level at no dimming-minimum 120000 Lux
129Colour rendition index-General Ra 94 or more,Enhanced red (R9)
13097 or more
131Minimum floor clearance-1.5 Mt for ceiling height of 2.75 Mt. Vertical Adjustment Range-+450mm to-600mm w.r.t main arm position (minimum)
132Secondary Arm Tilt Angle(Z) range-+/-30 degree minimum
133Sterilizable Handle-Yes
134Mounting Type-Ceiling
135Supply Voltage range-140-270 VAC 50/60 Hz
136Bulb Type-LED
137Protection-IP54
138Maximum Power consumption-Dimming Range (Mir.mum)-10%-100%
139Operating/Storage Humidity-10-95%-
140Life of Light Source->20,000 Hrs
141UPS System with isolation transformer 10KVA
142GST Extra As per Applicable