Bhabha Atomic Research Centre-BARC has published Tender For Supply, Installation, Testing And Commissioning Of 3.3 Kv And Lt Power Supply For Helium Screw Compressors And Internal Electrification Works For Crtd Shed, Cfb, North Site, Barc, Trombay, Mumbai-85. Submission Date for this Tender is 27-03-2024. Electrification Work Tenders in Mumbai Suburban Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 14-Mar-2024 | revised pre-bid MoM | Other | 19-03-2024 |
2 | 18-Mar-2024 | revised dates | Date | 27-03-2024 |
Sl. No. | Item Description |
1 | SITC of 3.3 KV HT, 800 KW rated vaccum contactor panel as per TSS01 |
2 | SITC of LT PCC Panel with 800A MCCB as incomer and 1 no. 400A MCCB, 4 nos. 63A MCCB, 4 nos. of 32A MCCB as outgoings as per TSS02 |
3 | Only installation of 3.3KV grade HT, armoured, AL conductor cable of size 3C x 400/300/240 sq. mm as per TSS03 |
4 | Only installation of 1.1 KV grade XLPE insulated 3.5C x 300/400 sq.mm. armoured, Al conductor cableas per TSS04 |
5 | Only installation of 3.3KV grade HT, armoured, AL conductor cable of size 3C x 150/95/70 sq. mm as per TSS05 |
6 | SITC of 1.1 KV grade FRLS, XLPE insulated 4C x 25 sqmm Al Conductor as per TSS06 |
7 | SITC of 1.1 KV grade FRLS, XLPE insulated 4C x 16 sq.mm. Al. Conductoras per TSS07 |
8 | SITC of 1.1 KV grade FRLS, XLPE insulated 4C x 2.5 sq.mm. Cu. Conductoras per TSS08 |
9 | SITC of 8 pair, FRLS, 1.1 KV grade, 1 sq. mm, copper conductor, XLPE insulated, armoured instrumentation cable as per TSS09 |
10 | SITC of 4 pair, FRLS, 1.1 KV grade, 1 sq. mm, copper conductor, XLPE insulated, armoured instrumentation cable as per TSS10 |
11 | SITC of 500V, 2Cx 1.5 sq. mm PE insulated, twisted Annealed Copper Cable for PA&FAas per TSS11 |
12 | SITC of End termination of HT, 3.3 KV, 3C x 400/300/240 sq mm of Al conductor armoured XLPE cableas per TSS12. |
13 | SITC of End termination of 1.1 KV grade XLPE insulated 3.5C x 300 sq.mm. armoured, Aluminium conductor cable as per TSS13 |
14 | SITC of End termination of HT, 3.3KV, 3C x 150/70 sq mm of Al conductor, armoured XLPE cableas per TSS14. |
15 | SITC of End termination of 1.1 KV grade XLPE insulated 4CX25 sqmm Al Conductor as per TSS15 |
16 | SITC of End termination of 1.1 KV grade XLPE insulated, 4C x 16 sq.mm. Al. conductor as per TSS16 |
17 | SITC of End termination of 1.1 KV grade XLPE insulated, 4C x 2.5 sq.mm. Cu. conductor as per TSS17 |
18 | SITC of End termination of 8 pair, 1.1 KV grade, 1 sq. mm, copper conductor, XLPE insulated, armoured instrumentation cable as per TSS18 |
19 | SITC of End termination of 4 pair, 1.1 KV grade, 1 sq. mm, copper conductor, XLPE insulated, armoured instrumentation cable as per TSS19 |
20 | End termination of 2Cx 1.5 sq. mm PE insulated, twisted Annealed Copper Cable as per TSS20 |
21 | SITC of 3-ph, 5 KVA UPS with battery bank for one(1) hour power back up as per the TSS21 |
22 | SITC of internal electrification of CrTD shed including power point wiring, lighting point wiring, data, telephone point wiring, exhaust point wiring etc in MS conduit on wall/cable tray/MS structure etc as per the detailed specifications and drawingas per TSS22. |
23 | SITC of CAT-6 cable for telephone and Data pointsas per TSS23 |
24 | SITC of HDPE pipe of 50 mm dia for laying existing CAT6 cableas per TSS24 |
25 | SITC of 12way/ph, TPN Distribution Board with 63A4P MCB & 3 nos of 63A 2P ELCB(30 mA) as incomer and 30 nos. of 16/20A SP MCB as outgoing feeders along with PPI isolation kit as per technical specificationsas per TSS25 |
26 | SITC of 10way/ph, TPN Distribution Board with 32A4P MCB and 3 nos. of 40A, 2PELCB(30 mA) as incomer and 24 nos. of 10A SP MCB and 18 nos. of 20 A SP MCB as o/g feeders along with PPI isolation kit as per technical specificationsas per TSS26 |
27 | SITC of 10 way/ph, TPN Distribution Board with 32A4P MCB and 3 nos. of 40A, 2PELCB(30 mA) as incomer and 24 nos. of 10A SP MCB and 18 nos. of 20 A SP MCB as o/g feeders along with PPI isolation kit as per technical specificationsas per TSS27 |
28 | SITC of 25 x 6mm tinned copper strip as per TSS28 |
29 | SITC of 25 x 3mm tinned copper strip as per TSS29 |
30 | SITC of earthing stations with Copper earth plate of size 60 cm x 60 cm x 3.15 mm thick, buried vertically in the specially prepared earth pit 2.5 Mtr. below ground complete with all required materials. Masonry chamber and excavation in all type of soil, back filling and disposal of excess earth and as instructed by EIC as per TSS30 |
31 | SITC of Lightening Arrester as per TSS31 |
32 | SITC of Test link Box for lightning arrestor as per TSS32 |
33 | MS Items:Fabrication, supply, installation ofvarious type of cable supports/framework made out of m.s. flats/rods/ angles/ channelsetc. including fixing material/welding to existing structure etc. including painting as per TSS33 |
34 | SITC of LED weather proof outdoor flood lighting fixture of atleast 8000 lumen output as per TSS34 |
35 | SITC of LED medium Bay lighting fixture of atleast 16000 lumen output as per the TSS35 |
36 | SITC of batten type industrial wall mount LED lighting fixture with lumen output of atleast 3600 lumens as per TSS36 |
37 | SITC of weather proof cable termination box along with termination glands on both sides for outdoor fixtures as per TSS37 |
38 | SITC of weather proof switchboard along with termination glands on both sides for outdoor fixtures as per TSS38 |
39 | SITC of Smoke detectors with optical and thermal element(I e capable of detecting fire type TF2 to TF8 reliably as defined in EN-54) with base and mounting on MS box as per TSS39 |
40 | SITC of Hooter Cum strobe along with all mounting accessories in MS box as per TSS40 |
41 | SITC of Manual Call Point Call pointalong with all mounting accessories in MS box as per TSS41 |
42 | SITC of Fire Alarm Terminal Box having 10 nos. of 2.5 sqmm ELMEX connector with front door hinged and having door lock systemas per TSS42. |
43 | Excavation for laying of power cables and back filling of normal soil including removal of excess earth and as directed by Engineer-in-Charge as per TSS43 |
44 | Supply installation of cable brick work/tiles, sand for LT and HT cable laying as per TSS44 |
45 | SITC of metal clad socket and plug and 20A, 2P MCB in separate MS boxes as per TSS45 |
46 | SITC of GI coated perforated Cable tray of 300 mm width as per TSS46 |
47 | SITC of heavy duty Wall mount, air circulatory industrial fan as per TSS47 |
48 | Supply and installation of 300 mm dia size NP2 class RCC hume pipe sleeves with collars as per TSS48 |
49 | Supplying and fixing of nominal 2.5mm +/- 10% thick insulated Synthetic Mat suitable for Class – B upto 11 KV as per TSS49 |
50 | Supplying and fixing of nominal 2 mm +/- 10% thick insulated Synthetic Mat suitable for Class – B upto 3.3 KV as per TSS50 |
51 | Removal and rerolling of cables of dia 20-30 mm from trench/cable tray etc as per the TSS51 |