Tender For Augmentation Work Of Shifting Of Existing 33Kv Switchyard At 220Kv Gss Nph Jaipur, jaipur-Rajasthan

Rajasthan Rajya Vidyut Prasaran Nigam Ltd-RRVPN has published Tender For Augmentation Work Of Shifting Of Existing 33Kv Switchyard At 220Kv Gss Nph Jaipur. Submission Date for this Tender is 14-03-2024. Switch Yard Tenders in jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42686075
Corrigendum : Tender For Augmentation Work Of Shifting Of Existing 33Kv Switchyard At 220Kv Gss Nph Jaipur
Open Tender
Indian
Rajasthan
jaipur
14-03-2024

Tender Details

Tender For Augmentation Work Of Shifting Of Existing 33Kv Switchyard At 220Kv Gss Nph Jaipur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Mar-2024 Date extension Date 14-03-2024

Key Value

Document Fees
INR 1180 /-
EMD
INR 16860.0 /-
Tender Value
INR 8.42 Lakhs /-

BOQ Items

Name of Work:Augmentation work of shifting of existing 33 KV swicthyard at 220 KV GSS NPH to new location due to settlement of soil at old location
Sl. No. Item Description
1EARTH MESH WORK
2Laying of earth mesh with 25mm/28 mm.dia M.S Rod at a depth of .80 meter from top level of foundations including excavation of trench of required depth and backfilling of the same transportation of M.S. Rod from site store to locations,welding of M.S.Rod along the length at crossing and with earth electrodes as per drawing application of btumen compound and covering with bitumen impregnated tap on all welded joints,for the type of soil prevent at .80 merter below top level of foundations(M.S. Rod of above sizes&M.S. Flate as rquired shall be made available by RVPNL. (a) In case elecricty is made available by RVPNL without charges ( i) Any soil soft rock other than hard rock
3Laying of earthing risers of 50x12 mm upto 50x6 mm size M.S. Flate at a depth of .80 meter from top level of foundation including excavation of trench of required depth and backfilling of the same transportation of M.S. Rod from site store to locations,preparation of risers bendinf as per requirement (after heating if nccessary(,fixing on and welding /bolting to equipment/structure and peacks of structures layinf in the trench welding to the earth mesh of M.S Rodas per drawing, including welding of extra length of M.S.Flate required application of btumen compound and if covering with bitumen impregnated tap on all welded joints,paiting of all surface of risers above ground level with red oxide and green paint, for the type of soil prevalent at0 .80 metre below top level level of foundatios(M.S.Rod of above sizes&M.S. Flate as rquired shall be made available by RVPNL).a)In cash electricity is made available by RRVPNL without charges. ( i) Any soil soft rock other than hard rock
4Placing/Drawing of earth electrode of 28 mm dia.M.S.Rod of length 3.30 meters(approx) to a depth of 3.80 meters from the top level of foundations, including excavation of pit as required and backfilling of the same transportion of M.S. Rod from site to locations,cutting of M.S. Rod to desired length preparation of one end as spike if necessary ,welding of earth electrode to earth mesh.OF M.S. Rod as per drawing,application of btumen compound and covering with bitumen impregnated tapon all welded joints,for the type of soil prevalent at 3.80 metres below top level of foundation (M.S.Rod of above sizes&M.S.Flat as required shall be made available by RVPN. a)In cash electricity is made available by RRVPNL without charges.( i) Any soil soft rock other than hard rock
5ERECTION OF SUB-STATION STEEL :Structures colums,beams,lighting mastand equipment structures(excluding circuit breaker andcapicator bank) of all types including transportation of structure
6BUS BAR WORK:-Erection of 220KV,132KV,33KV bus bar of ACSR & Tarantulla conductor,disc insulators and tension hardware from site store to locatoins,laying and cutting required length of conductor, cleaning and assemly of disc insulators as required along with fitting of bollted type or compression type tension H/W as made availlable(compression machine shall be providedby RVPNon rent free basis),making up at one end,stringing of conductors between the beams with specified sag and tension, also equalizing sag and fitting spacers spacer T clamps for twin conductors,for three phase of conductor in each bus section.(Per Jumper Basis)
7i)Single ACSR zebra
8ii)Double ACSR zebra
9JUMPERSof ACSR conductor(3nos Y type)between equipment or between bus to bus,including transportion of conductor,disc insulators and hardware from site stores to locations ,cleaning and assembly of disc insulators as along with fitting of suspension hardware and erectoin as reqired, cutting reqired length of conductor, making connections,fixing of spacers & spacer T-clamps as reqired,tightiening of clamps/ connectors, dressing ect. For three phases (Per Jumper Basis)
101)Any conductor
11STRINGING of earth wire (size7/3.15mm7/4 mm ) including transportion of earth wire,tensions hardware etc.from site store to loctions, laying and cutting requiredlength of earth-wire ,fitting of bolted type or compression type hardware as made available(compression machine shall be provided by RVPN on rent free basis),making up at one end, stringing of earthwire between structure peaks with speci- sag and tension,jumpering and connecting earth bonds,for single earth wire
12ERECTION OF SUB-STATION EQUIPENTS:-Erection of Current Transformer/Potencial Transformer/Capcitive Voltage Transformer with clamps & connectors on already erected steel structure including transportion from site store to locations, fabrication of base fram,fixing of terminal connectors lightening of nuts& bolts etc.complete in all rsepects
13ii) 33 KVCT/PT
14Erection of lightening Arrestor on already erected steel structure including transportion of lighting Arrestor,clamps&connectors,surge counter etc. from site store to locations fabrication of base frame, fixing of terninal connectors surge counter, tighting of nuts&bolts etc. complete in all respect.
15i) 33 KVLA
16Erection of isolarors on already erected steel structure including transportion of base fame,P.I."s contacts,mechanim box,clamps&connectors etc. from the site store to locations,minor fabrication as required and fixing of terminal connectors etc adjustment/aligment of isolator and its earth blade, if provided for their smooth opertion and final adjustment if required after jumpering. i)33KV
17a) without Earth Blade
18a) with Earth Blade
19Erection of 33 Circuit Breaker including transportation of equipment structure members nurts& bolts,clamp & connectors, accessories etc from sitestore to location,assembly of support structure their placing on foundation,levelling and preparing for grouting as required but excluding gouting, assembly placining of support columns/poles mechanim box/control cubicle and other accessories as per bmanufacture,s drawings filling of sf6 gas pipeline,fabrication og air/oil pipeline as required,electrical wing from pole to control cubicle. fixing of terminal connectors as required but excluding commissiong of CB .
20i) 33 KV CB
21Erection of marshaling kiosk/line matching unit(LMU)/line matching &distribution unit (LMDU)complete in all respectincluding transportion from site store to loction,placing on foundation/cable trench as per layout ,preparing for grounting on foundation bolts but excluding grouting etc.
22ii) 33 KV or 11 KV marshalling box
23LAYING AND TERMINATION OF CABLES. :-i)Laying of PVC insulated unarmored /armored control cables of 1.1 kv grade with copper condutor in cable trenches as per sepecification as required, including transportion of cable drum from site store to locations,cutting to required length,placing them on cable racks/cable trays/ cable batten and dressing,including removing and re-fixing trench covers as required, making necessary connections testing,cable marking on both termimating ends,ets. as required for all size from 2cx2.5 sq.to 20x2.5sq mm & 4x4 sq mm
24a)Unarmored control cable
25ii) Fixing of control cable in position with single compression nickle plated brass cable glands confirming to IS 12943 & having three metal washers and one rubber ring including preparion of cables and drilling of corresponding holes in gland plated etc as reuired & including cost of cable glands,for each gland sizes.
26a) 19 mm Unarmored control cable
27b) 25 mm Unarmored control cable
28c) 32 mm Unarmored control cable
29iii) Termination of wires of cables with copper conductor using copper terminal ends (pin or ring type as required of Dowell,s or equivalent make as approved by the Engineer-In-charge) duly clamped with crimping tool,including making wire ends ready for crimping ferruling & dressing of wire etc as required including cost of terminal ends for all wires for each cable al lboth ends for cables of the following sizes
30a) 2.5 sq.mm for any number of core
31b) 4 sq.mm for any number of core
32c) 6 sq.mm for any number of core
33PART "B" FOR DISMENTALING WORK :-Laying of earthing risers of 50x12 mm upto 50x6 mm size M.S. Flate at a depth of .80 meter from top level of foundation including excavation of trench of required depth and backfilling of the same transportation of M.S. Rod from site store to locations,preparation of risers bendinf as per requirement (after heating if nccessary(,fixing on and welding /bolting to equipment/structure and peacks of structures layinf in the trench welding to the earth mesh of M.S Rodas per drawing, including welding of extra length of M.S.Flate required application of btumen compound and if covering with bitumen impregnated tap on all welded joints,paiting of all surface of risers above ground level with red oxide and green paint, for the type of soil prevalent at0 .80 metre below top level level of foundatios(M.S.Rod of above sizes&M.S. Flate as rquired shall be made available by RVPNL).a)In cash electricity is made available by RRVPNL without charges.
34( i) Any soil soft rock other than hard rock
35ERECTION OF SUB-STATION STEEL
36Structures colums,beams,lighting mastand equipment structures(excluding circuit breaker andcapicator bank) of all types including transportation of structure members,nut&bolts washers etc. from site store to locations their assembly, placing on foundation,fixing template,with foundation bolts as required,levelling andpreparing for grouting as required,but excluding grouting erection after grouting and toghtehing&punching of nut&bolts. (maximun height of structures up to 20 meters)
37BUS BAR WORK :- 26-02-2024 26-02-2024-Dismantling of 220KV,132KV,33KV bus bar of ACSR & Tarantulla conductor,disc insulators and tension hardware from site store to locatoins,laying and cutting required length of conductor, cleaning and assemly of disc insulators as required along with fitting of bollted type or compression type tension H/W as made availlable(compression machine shall be providedby RVPNon rent free basis),making up at one end,stringing of conductors between the beams with specified sag and tension, also equalizing sag and fitting spacers spacer T clamps for twin conductors,for three phase of conductor in each bus section.(Per Jumper Basis)
38i)Single ACSR zebra
39ii)Double ACSR zebra
40JUMPERSof ACSR conductor(3nos Y type)between equipment or between bus to bus,including transportion of conductor,disc insulators and hardware from site stores to locations ,cleaning and assembly of disc insulators as along with fitting of suspension hardware and erectoin as reqired, cutting reqired length of conductor, making connections,fixing of spacers & spacer T-clamps as reqired,tightiening of clamps/ connectors, dressing ect. For three phases (Per Jumper Basis)
411)Any conductor
42DISMENTALINGOF SUB-STATION EQUIPENTS :-Erection of Current Transformer/Potencial Transformer/Capcitive Voltage Transformer with clamps & connectors on already erected steel structure including transportion from site store to locations, fabrication of base fram,fixing of terminal connectors lightening of nuts& bolts etc.complete in all rsepects
43ii) 33 KVCT/PT
44Erection of lightening Arrestor on already erected steel structure including transportion of lighting Arrestor,clamps&connectors,surge counter etc. from site store to locations fabrication of base frame, fixing of terninal connectors surge counter, tighting of nuts&bolts etc. complete in all respect.
45i) 33 KVLA
46Erection of isolarors on already erected steel structure including transportion of base fame,P.I."s contacts,mechanim box,clamps&connectors etc. from the site store to locations,minor fabrication as required and fixing of terminal connectors etc adjustment/aligment of isolator and its earth blade, if provided for their smooth opertion and final adjustment if required after jumpering. i)33KV
47a) without Earth Blade
48b) with Earth Blade
49Erection of 33 Circuit Breaker including transportation of equipment structure members nurts& bolts,clamp & connectors, accessories etc from sitestore to location,assembly of support structure their placing on foundation,levelling and preparing for grouting as required but excluding gouting, assembly placining of support columns/poles mechanim box/control cubicle and other accessories as per bmanufacture,s drawings filling of sf6 gas pipeline,fabrication og air/oil pipeline as required,electrical wing from pole to control cubicle. fixing of terminal connectors as required but excluding commissiong of CB .
50i) 33 KV CB
51Dismantling of Post insulator on already erected structures including transporation of P.I"s, nuts & bolts, clamp and coonectors etc from location to site store.
52iii) 33KV or 11KV
53Erection of marshaling kiosk/line matching unit(LMU)/line matching &distribution unit (LMDU)complete in all respectincluding transportion from site store to loction,placing on foundation/cable trench as per layout ,preparing for grounting on foundation bolts but excluding grouting etc.
54ii) 33 KV or 11 KV marshalling box
55LAYING AND TERMINATION OF CABLES Control Cables.i)Laying of PVC insulated unarmored /armored control cables of 1.1 kv grade with copper condutor in cable trenches as per sepecification as required, including transportion of cable drum from site store to locations,cutting to required length,placing them on cable racks/cable trays/ cable batten and dressing,including removing and re-fixing trench covers as required, making necessary connections testing,cable marking on both termimating ends,ets. as required for all size from 2cx2.5 sq.to 20x2.5sq mm & 4x4 sq mm
56a)Unarmored control cable