}

Tender For Repair Replacement Of Corroded Ci Pipeline By Ppr Pipeline Of Various Sizes, Lt Panels Alonwith Cable And Fire Fighting Equipments At Sevoke Stn Under Ge Sevoke Road, Kalimpong-West Bengal

Military Engineer Services-MES has published Tender For Repair Replacement Of Corroded Ci Pipeline By Ppr Pipeline Of Various Sizes, Lt Panels Alonwith Cable And Fire Fighting Equipments At Sevoke Stn Under Ge Sevoke Road. Submission Date for this Tender is 15-03-2024. Electrical Panel Tenders in Kalimpong West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

42616555
Tender For Repair Replacement Of Corroded Ci Pipeline By Ppr Pipeline Of Various Sizes, Lt Panels Alonwith Cable And Fire Fighting Equipments At Sevoke Stn Under Ge Sevoke Road
Open Tender
Indian
West Bengal
Kalimpong
15-03-2024

Tender Details

Repair Replacement Of Corroded Ci Pipeline By Ppr Pipeline Of Various Sizes, Lt Panels Alonwith Cable And Fire Fighting Equipments At Sevoke Stn Under Ge Sevoke Road

Key Value

Document Fees
INR 500 /-
EMD
INR 82600.0 /-
Tender Value
INR 41.30 Lakhs /-

BOQ Items

Name of Work: REPAIR REPLACEMENT OF CORRODED CI PIPELINE BY PPR PIPELINE OF VARIOUS SIZES,LT PANELS ALONWITH CABLE AND FIRE FIGHTING EQUIPMENTS AT SEVOKE STN UNDER GE SEVOKE ROAD
Sl. No. Item Description
1Excavation in trenches n exc 1.5 mtr wide and depth n exc 1.5 mtr deep for foundation, laying GI pipes and UG cables etc n exc 10 sqmtr on plan, in soft/loose soil and getting out complete all as specified and directed.
2Excavation in trenches n exc 1.5 mtr wide and depth n exc 2.00 mtr deep for foundation, laying GI pipes and UG cables etc n exc 10 sqmtr on plan, in hard/dense soil and getting out complete all as specified and directed.
3Returning filling in with approved excavated soil including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed.
4Removing excavated soils to a distance not exceeding 50 metres and depositing where directed at a level nexc. 1.5 metre above the starting point complete all as specified and directed.
5Materials and labour for PCC (1:3:6) type C2 using (40mm graded crushed stone aggregate) as in foundation for filling in mass concrete for foundation, road PCC or any other works required on site requirement all as directed.
6Taking up or down from any position existing steel water tubing 20 mm bore of any type and connections carefully including cleaning for refixing or removal to E/M store yard or issued as credit complete all as specified and as directed. Note :Excavation/earth work shall be measured and paid separately under respective item of schedule considered here-in-before.
7All same as item No. 6 above but 25 mm bore.
8All same as item No. 6 above but 40 mm bore.
9All same as item No. 6 above but 50 mm bore.
10All same as item No. 6 above but 80 mm bore.
11Relaying/refixing of old serviceable steel water tubingas obtained from item No. 6 to 10 here-in-before, jointing and testingin new or existing position including all new fittings, ISI Marked, such as bends, elbow, tee, reducers, sockets, unions, flange etc as required, laid in trenches or fixed to wall/cellinng or floors including making holes in wall where requiredcomplete all as specified and directed by Engr-in-charge for 20 mm bore pipes.
12All same as item No. 11 above but 25 mm bore.
13All same as item No. 11 above but 40 mm bore.
14All same as item No. 11 above but 50 mm bore
15Supply, laying, jointing & testing 3-layer PP-R (Polypropylene random copolymer) concealed pipes, 90 mm outer dia, SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings such as bends, elbow. tee, socket, reducers, unionsfixed complete to walls, ceilings, trenches or in floors etc as required at site complete all as specified and directed. Note : (i) Contractor shall submit 07 years warranty certificaty from the manufacturer of any manufactureing defect and leakage through the pipeline. (ii)If there is any technical problem regarding PP-R product contractor shall provide support within 2 days.
16All same as item No. 15 above but 63 mm outer dia.
17All same as item No. 15 above but 50 mm outer dia.
18All same as item No. 15 above but 32 mm outer dia.
19All same as item No. 15 above but 25 mm outer dia.
20Supply and fixingin repair gun metal gate/globe valve, 50 mm bore,ISI Marked, with iron wheel headed screwed both ends for pipeincluding taking down unserviceable complete all as specified and as directed.
21All same as item No. 20 above but 40 mm bore.
22All same as item No. 20 above but 25 mm bore.
23Supply and fixing in repair PP-R Gate valves (brass insert), for 63 mm outer dia pipe, as per requirement of the site includingtaking down unserviceable valves complete all as specified and as directed of the following sizes:-
24All same as item No. 23 above but for 50 mm outer dia pipe.
25All same as item No. 23 above but for 32 mm outer dia pipe.
26All same as item No. 23 above but for 25 mm outer dia pipe.
27Supply only 50 mm bore GI Union.
28Supply only 40 mm bore GI Union.
29Supply only 25 mm bore GI Union.
30Supply only 20 mm bore GI Union.
31Supply only 50 mm bore GI Elbow.
32Supply only 40 mm bore GI Elbow.
33Supply only 25 mm bore GI Elbow.
34Supply only 20 mm bore GI Elbow.
35Materials and labour for 50 mm outer dia double wall corrugated(DWC) HDPE pipe, ISI marked for enclosing cable below ground/road surface to a required depth including suitable size couplers for jointing of pipe all as per site requirement etc complete all as specified and directed.
36Materials and labour for 75 mm outer dia double wall corrugated(DWC) HDPE pipe, ISI marked for enclosing cable below ground/road surface to a required depth including suitable size couplers for jointing of pipe all as per site requirement etc complete all as specified and directed.
37Materials and labour for GI tubing of 40 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring as cable protection laid on floor all as specifed and directed.
38Materials and labour for GI tubing of 50 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring as cable protection laid on floor all as specifed and directed.
39Materials and labour for GI tubing of 80 mm bore light grade with all fitting fixed to wall/ceiling/pole or in trench formed by road/PCC cutting/boring as cable protection laid on floor all as specifed and directed.
40Supply and laying in trenches/wall LT UG XLPE insulated ,armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 185sq mm x 3.5 coreincluding taking down old u/s making necessery connections all as specified and as directed.
41All as item no 40 but of size 150 sqmm 3.5 core
42All as item no 40 but of size 120 sqmm 3.5 core
43All as item no 40 but of size 95 sqmm 3.5 core
44All as item no 40 but of size 70 sqmm 3.5 core
45All as item no 40 but of size 50 sqmm 3.5 core
46All as item no 40 but of size 25 sqmm 4 core
47All as item no 40 but of size 16 sqmm 4 core
48All as item no 40 but of size 10 sqmm 4 core
49All as item no 40 but of size 16 sqmm 2 core
50All as item no 40 but of size 10 sqmm 2 core
51Supply and fixingSteel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screws of type 410 SP-31( 9 metre long) complete all as specified and directed.
52Supply and fixing cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5 core XLPE, armoured, aluminium conductor cable of size 70 to 185 Sqmm, Outdoor type, including taking out & relaying damaged UG cable after repair complete all as specified and as directed. (Note:- Excavation and connected items will be measured and paid separately)
53Supply and fixing cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5/4 core XLPE, armoured, aluminium conductor cable of size 16 to 50 Sqmm, Outdoor type, including taking out & relaying damaged UG cable after repair complete all as specified and as directed. (Note:- Excavation and connected items will be measured and paid separately)
54Materials and labour for PCC, type C1, (1:3:6), using 20mm graded crushed stone aggregated) as in coping of poles including formworkincluding demolition of old damaged concrete from pole complete all as specified and as directed
55Materials and labour PCC, type D2, (1:4:8), using 40mm graded crushed stone aggregated) as in PCC/Road cutting /installation area and foundation of pole etccomplete all as specified and as directed.
56Materials and labour for boring holes 1mtr deep in soil under roads/PCC as directed for cable passing through pipes of required size and disposal of soil to a distance not exc. 50m. (Note: Connected items like Pipes is measured and paid seperately under relevant items).
57Supply and fixing in repair Indicator lamp (AC/DC), LED, type for as per existing fitting.complete all as specified and as directed by Engr-in-Charge.
58Supply and fixing in repair 3 Phase LED Ammetercomplete all as specified and as directed by Engr-in-Charge.
59Supply and fixing in repair, 3 phase LED Voltmeter complete all as specified and as directed by Engr-in-Charge.
60Supply and fixing as in repairsMCCB four pole , 415 Volt, 63 Amps,16 KA , fixed thermal &magnetic setting complete all as specified and directed
61Supply and fixing as in repairsMCCB four pole , 415 Volt, 100 Amps,25 KA , fixed thermal &magnetic setting complete all as specified and directed .
62Supply and fixing as in repairsMCCB four pole , 415 Volt, 125 Amps,25 KA , fixed thermal &magnetic setting complete all as specified and directed.
63Supply and fixing MCCB, 160 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. .
64Supply and fixing MCCB, 200 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
65Supply and fixing MCCB, 250 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
66Supply and fixing MCCB, 400 Amps, 4P, 36 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
67Materials and labour for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 3.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron strip of size 25x4 mm connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one end fix with cast iron funnel and wire-mesh, with protection pipe of 32 mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol , bentonite in alternate layers etc all in around of earthing pipe of 600mm dia, complete all as shown in EP number 2 of SSR Part-1 including testing on completion and including taking down old U/S earthing & testing complete all as specified and as directed.
68Materials and labour for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 3.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron strip of size 4 mm connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one end fix with cast iron funnel and wire-mesh, with protection pipe of 32 mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol , bentonite in alternate layers etc all in around of earthing pipe of 600mm dia, complete all as shown in EP number 2 of SSR Part-1 including testing on completion and including taking down old U/S earthing & testing complete all as specified and as directed.
69Materials and labour for water proof, 3core PVC insulated and PVC sheathed, copper conductor cable of size 1.5 sqmm, 1100 Volts grade for electrical connection of street light fittings, complete all as specified and directed.
70Supply and fixing thermoplastic polycarbonate cable junstion box having protection IP 66"dust proof, acid resistant, shock proof, fire retardent self extinguisher" for outside installation with knockout entry for cable of size 16 sqmm and 155x155x100 mm with terminals, brackets for street light pole mounting and provision of one 6A MCB SP all as specified and as directed.
71Materials and labour for painting old painted LT Panel/feeder pillar by two coats of synthetic enamel paint after preparation of surfaces complete all as specified and as directed.
72Servicing of LT Panel after shut downand removing all dust particles and proper layout of LT panel wlth gland packing including 2.5 sqmm copper single core copper cable including repairing/replacing door hinges/door lock etc for necessary connections complete all as specified and directed
73Materials and labour for Preparation of metalic surface with sand paper for street light pole and other steel surface complete all as specified and as directed by Engr- in-Charge
74Materials and labour for one coat of red oxide zinc chrome primer on steel surfaces of street light pole and other steel surface complete all as specified and as directed by Engr- in-Charge
75Materials and labour for aluminium paint two coats on newly primed metalic surface of street light pole and other steel surface complete all as specified and as directed by Engr- in-Charge
76Materials and labour for two coats of yellow/black synthetic enamel paint on Metalic/PCC surfaces complete all as specified and as directed by Engr- in-Charge
77Materials and labour for preparation of old decorated concrete/plastered surfaces and applying two coats of Cement based paint complete all as specified and as directed by Engr- in-Charge
78Supply, installing, testing and commissioning outdoor type stainless steel (SS 304) cubical enclosure compartmentalizedexterior and interior mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc. The enclosure shallbe made of 2 mm thickSS 304 sheet. The fixing of doubledoors shall be on SS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure). All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 304.Sliding handle and locking arrangement front and rear both side . Enclosure shall be suitable for AC supply system 415 volts, 3 phase, 4 wire, 50 Hz. IP-55 class protection and mounted on channel 75 mm welded with panel of SS 304 with 04 Nos foundation bolt of size not less than20mm dia and 300mm long. The enclosure shall have provision of cable alley . Cable entry from bottom side including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size (but not less than 2.5 sqmm). Incoming :- (i) Aluminium busbar rating 150 Amps rating 4 Nos. (ii) MCCB 100 Amps 4 pole breaking capacity 25 KA thermal mag protection with Icu = 100% & rated impulse with stand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation-01 No. Outgoing :-(i) MCCB 40 Amp 4 pole 04 Nos breaking capacity 16 KA thermal mag protection with Icu = 100% & rated impulse withstand voltage (Vimp) 8 KV with over current & short circuitprotection having double insulation & positive insulation, MCB SPN 20Amps - 03 Nos (ii) Current transformer 100/5Amps class-1 15 VA - 2 Nos, Digital Ammeter with inbuilt selector switch -02 No, Digital Voltmeter with in built selector switch -02 No and Modular Indication lamp for main incomer LED type RYB (set of 3)-2 Set (at both incomer MCCB) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. All out going feeder shall be connected by cable through suitable size gland plate / glands.The various feeders shall be indicated by font size not less than 20 mmletters using Acrylic sheet. The minimums clearance of bus bar shall be 32mm phase –phase and 26mm for phase to earth. The bus bar shall have colour coding with insulating tape. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class "B", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Make:- BCH/Schneider/ABB
79Taking down old servicable LT UG Cable and refixing same after making necessary repair complete all as specified and as directed by engineer-in-charge (Note: Excavation shall be paid and measured separately under relevant items).
80Taking out old bricks and relaying after cable repair workcomplete all as specified and as directed.
81Materials and labour for taking out cable loop of LT feeder panel and seperating old insulation and fixing cable end jointing kit for the size of the cableupto 120 Sqmm 3.5 core sizecomplete all as specified and as directed by engineer-in-charge. (Note: Excavation shall be paid extra under relevant items.
82Supply and fixing in repair stainless steel 2 way Fire Brigade Inlet connection ISI marked with inbuilt Check Valve including taking down and removed from site complete all as specified and as directed.
83Supply and fixingin repair stainless steel 63 mm bore Heavy Duty Single Headed Fire Hydrant Landing valve As per IS:5290 type "A" ISI marked with ABS Blank capincluding taking down unserviceablve valve and removing from site complete all as specified and as directed.
84Supply and fixing in repair Hose reinforced rubber lined fire Pipe ofSize 63 mm bore ( 15 Mtr Length ) WithBoth Side SS coupling ISI marked Male & Female connection type including taking down complete all as specified and as directed.
85Supply and fixingin repair Branch Pipe with SS Nozzle as per IS 903 ISI marked including taking and removing from site down complete all as specified and as directed.
86Supply and fixingin repair of Hosebox made of 18 gange MS sheet 800 mm x 600mm x 250 mm with double door with 4 mm thick glasses and door fram made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard complete including taking out old unservicebale Hose box and removing from site compelte all on specified and directed.
87Supply and fixing in repairHose reel Drum ( Wall Mounted) swingingtype as per IS : 884 includingHose pipe Length 30 Mtr Long of Size:- 20 mm bore thermo plastic hose as per IS 12585, ISI markedwith PVC ¾ “ Shutoff Nozzle (Hydraulically Crimped) including taking down and removing from site complete all as specified and as directed.
88Supply and fixingin repair PVC Shut off Nozzle Size 20 mmbore ISI marked including taking down complete all as specified and as directed and removing from site.
89Supply and fixing in repair Hose Clamp including taking down and removing from site complete all as specified and as directed.
90Supply and fixing in repair 100mm Dual Plate Check Valve :- Cast Iron Body , D.I. Doors ,Nitrile /EPDM Seat ,Stainless Steel Shaft and springs P.N. 1.6 including taking down unserviceable and removing from site complete all as specified and as directed.
91Supply & Refilling of Carbon di Oxide Fire Extinguisher 4.5 Kg each complete all as specified and as directed.
92Supply & Refilling of ABC Powder Fire Extinguisher 6 Kg Each complete all as specified and as directed.
93Supply & Refilling of D-Fire Mechanical Foam Extinguisher 9 Ltr capacity each complete all as specified and as directed.
94Supply & Refilling of Watermist baseFire Extinguisher 9 Ltr capacity each complete all as specified and as directed.
95Supply only Fire Extinguisher Hose Pipe ABC Type
96Supply only Fire Extinguisher Hose Pipe CO2 Type
97Supply only valve kit for Fire Extinguisher ABC Type
98Supply only Fire Extinguisher valve for foam type
99Supply only Fire Extinguisher valve forWatertype
100Supply only Pressure Meter
101Supply only Hanging Clip ( Hooke ) for Fire Extinguisher
102Supply only Carbon di Oxide Fire Extinguisher 4.5 Kg each
103Supply only ABC Powder Fire Extinguisher 6 Kg Each
104Supply only D-Fire Mechanical Foam Extinguisher 9 Ltr capacity each
105Supply only Watermist baseFire Extinguisher 9 Ltr capacity each
106Labour only for Control Panel Fault Detection & Rectification by changing Necessary defective Components along with necessary copper wire, Lugs, Terminal etc. including testing complete all as specified and as directed. Note: Spare parts will be measured and paid separately under approprite item
107Supply only 3 Pole 32 A Power Contactor
108Supply only Thermal Overload Relay ,Relay Range 14-23 A
109Supply only Setof 3 Phase Indicating Lamps (Red Yellow & Blue )
110Supply only Push Button Assembly with auxiliary contact BlockStart & Stop
111Supply only 63 Amp TPN MCB10 KA
112Supply only 1 Pole 2 Way Rotary Cum Switch for Auto & Manual selection
113Supply only Single Phase Preventer
114Supply only Danfoss Make KP35 Pressure Switch
115Supply only Ball Valve 15 mm
116Supply only PVC Insulated & PVC Shethed Multi core bright Annealed bare Copper Conductor flexible Round Cables Size 1 Sq mm 2 core FRLSH
117Servicing of motor pump set by disassembling, (i)Motor Front over and back cover part by part dismantling, Internal Coil Heat Varnish, Insulation Testing & refixing. (ii) Pump Part by part Dismantling, ThroughServicing, replacement ofbearing & Gland Packing /Mechanical seal,re assembly with proper alignment complete all as specified and as directed.
118Materials and labour for painting of motor pump set complete all as specified and as directed
119Supply, laying, jointing & testing MS tubing heavy grade 100mm bore with all fittings such as bends, elbow, tee, socket, reducers, unions etc as required at site laid in trenches or fixing complete with clips, wall hooks etc. complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail