| 1 | Part A |
| 2 | 1.8.3:Wiring for light point/ fan point/ exhaust fanpoint/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, withpiano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single corecable etc as required.Group C |
| 3 | 1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | 1.23.1:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch |
| 5 | 1.23.3:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.15/16 amp switch |
| 6 | 1.23.4:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet |
| 7 | 1.23.5:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.6 pin 15/16 amp socket outlet |
| 8 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator8 way, Double door |
| 9 | 2.10.1:Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 10 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 11 | 7.6.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing masonry open duct as required.Upto 35 sq. mm |
| 12 | 7.7.1:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 13 | 1.50.1:Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 14 | 5.1:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 15 | 5.12:Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 16 | 5.18:Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 17 | OD28990/2023-2024:supply, installation, testing and commissioning ofSingle/threephase Mono Block P/Set complete with all accessories workable on 240/415 volt. 50 Hz AC supply 1HP (0.75 KW ) Single Phase Pump Set Head frame 12.5 mt upto 25 mt Suction and delivery 25x25 |
| 18 | 19.1:Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 19 | Part B |
| 20 | 122.1.1:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*4 sqmm |
| 21 | 122.2.2: P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. asreqd. |
| 22 | 122.2.27:SITC of 30W LED Flood Light luminaire fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =30 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66 |
| 23 | 122.2.39:S/I/T/C of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95 |
| 24 | 122.1.47:Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |