}

Tender For Comprehensive Maintenance Of Dg Sets, Amf Panels And Connected Misc Items At No 2Afsb Mysore, bangalore-Karnataka

Military Engineer Services-MES has published Tender For Comprehensive Maintenance Of Dg Sets, Amf Panels And Connected Misc Items At No 2Afsb Mysore. Submission Date for this Tender is 15-03-2024. Diesel Generators Tenders in bangalore Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

42555641
Tender For Comprehensive Maintenance Of Dg Sets, Amf Panels And Connected Misc Items At No 2Afsb Mysore
Open Tender
Indian
Karnataka
bangalore
15-03-2024

Tender Details

Tender For Comprehensive Maintenance Of Dg Sets, Amf Panels And Connected Misc Items At No 2Afsb Mysore

Key Value

Document Fees
INR 300 /-
EMD
INR 9000.0 /-
Tender Value
INR 4.50 Lakhs /-

BOQ Items

Name of Work: Comprehensive Maint of DG sets, AMF panels and connected Misc items at No 2AFSB Mysore
Sl. No. Item Description
1Maintanance and servicing of Diesel Generator set of cap 100 KVA - No. 1 installed at Sub Station by carrying out routine "A" check of the engine complete for smooth functioning all as per manufacturer"s instructions and as directed :- NOTES:- (i) Control switches , MCCB"s, contactors, multi display meters , Engine control unit shall be out of scope of the item of work and the rate quoted shall be exclusive for servicing/ maintenance of the above item of work.(ii) Servicing of DG set alongwith connected Alternator and Panel Board including "A" check of the Engine shall be carried out once in 2 months (Except during the month when "B" check is carried out) as directed by the Engineer-in-Charge and the Contractor shall carry out periodical inspections during the maintenenace period and shall be responsible for the smooth functioning of the DG set for a period of 60 days from the date of service and shall also attend all the maintenence / breakdown repairs as and when required in that period except in case of major repairs. (iii) Spare parts required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares shall be deemed to be inluded in the rate quoted.(iv) Cost of all consumables required during the maintenance period shall be deemed to be included in the rate quoted for this item.(v) List of checks to be carriedout under "A" check is attached as Appendix "A" to the Particular specifications.
2All as per item No.1 above but 100 KVA - No 2installed at Sub Station
3All as per item No.1 above but 100 KVAinstalled at CPSS Sub Station
4All as per item No.1 above but 82.5 KVAinstalled at CPSS Sub Station
5All as per item No.1 above but 62.5 KVA installed at Sub Station
6All as per item No.1 above but 35 KVA installed Station HQ
7All as per item No.1 above but 30 KVA installed at Candidate Billet
8All as per item No.1 above but 20 KVA installed at Pump House
9All as per item No.1 above but 10 KVA installed for Immols Server Room
10All as per item No.1 above but 10 KVA installed near WCDMA Tower
11Maintanance and servicing of Diesel Generator set of cap 100 KVA by carrying out routine "B" check of the engine including items covered in "A" check complete for smooth functiuning all as per manufacturer"s instructions and as directed.NOTES:- (i) Control switches , MCCB"s, contactors, multi display meters , Engine control unit shall be out of scope of the item of work and the rate quoted shall be exlusive for servicing/ maintenance of the above item of work.(ii) "B" check shall be carried out once in every six months or 250 hours of running of DG Set whichever is earlier. Servicing of DG Set alonwith connected Alternator and Panel Board including items covered in "A" check of the Engine shall also be carried out in that month as directed by the Engineer-in-charge and the Contractor shall carry out periodical inspections during the maintenance period and he shall be responsible for the smooth functioning of the DG Set for a period of 30 days from the date of service and shall also attend all the maintenance / breakdown repairs as and when required in that period except in case of Major repairs. (iii) Spare parts , engine oil and radiaton coolant oil required for replacement during the maintenance period shall be measured and paid seperatly at supply only rates and cost of labour for fixing these spares/filling of oil shall be deemed to be included in the rate quoted for this item. (iv) Cost of all consumables, diesel / oil filters etc., required during the maintenance period shall be deemed to be included in the rate quoted for this item.(v) List of checks to be carriedout under "B" check is attached as Appendix "A" to the Particular specifications.
12All as per item No.11 above but 100 KVA - No 2installed at Sub Station
13All as per item No.11 above but 100 KVAinstalled at CPSS Sub Station
14All as per item No.11 above but 82.5 KVAinstalled at CPSS Sub Station
15All as per item No.11 above but 62.5 KVA installed at Sub Station
16All as per item No.11 above but 35 KVA installed Station HQ
17All as per item No.11 above but 30 KVA installed at Candidate Billet
18All as per item No.11 above but 20 KVA installed at Pump House
19All as per item No.11 above but 10 KVA installed for Immols Server Room
20All as per item No.11 above but 10 KVA installed near WCDMA Tower
21Supply only Engine Oil SAE 15W-40W.Make :-(VOLVOLINE/IOC )
22Supply only radiator coolant.Make :-(VOLVOLINE/IOC )
23S & F battery 12 volts, 150 AH suitable for DG sets including battery terminals complete all as specified and directed.Make : Exide/Amaron/Tata
24All as per item No.23 above but 92/100 AH
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail