Tender For Sitc Of 02 Nos. 160 Kva Ups And Lt Panel At New Atc Complex, S.V. Airport, Raipur, raipur-Chhattisgarh

Airports Authority Of India has published Tender For Sitc Of 02 Nos. 160 Kva Ups And Lt Panel At New Atc Complex, S.V. Airport, Raipur. Submission Date for this Tender is 21-03-2024. UPS Tenders in raipur Chhattisgarh. Bidders can get complete Tender details and download the document.




Tender Notice

42523974
Tender For Sitc Of 02 Nos. 160 Kva Ups And Lt Panel At New Atc Complex, S.V. Airport, Raipur
Open Tender
Indian
Chhattisgarh
raipur
21-03-2024

Tender Details

Tender For Sitc Of 02 Nos. 160 Kva Ups And Lt Panel At New Atc Complex, S.V. Airport, Raipur

Key Value

Document Fees
INR 1120 /-
EMD
INR 159770.0 /-
Tender Value
INR 79.88 Lakhs /-

BOQ Items

Name of Work: SITC of 02 nos. 160 KVA UPS and LT Panel at New ATC Complex, S.V. Airport, Raipur.
Sl. No. Item Description
1Supply, Installation, Testing and Commissioning of true online UPS with minimum 160 KVA capacity, 3 phase in and 3 Phase out with double conversion PWM IGBT technology, in built isolation transformer before static switch suitable to drive constant current regulators with 100% unbalanced load at output at fullload condition as per technical specifications/data sheet enclosed. The UPS shall have standard features like in built automatic 100% rated static by pass,maintenance by pass, active input power factor correction, phase sequencecorrector, pure sine wave output, input-output isolation, compatibility with generator supply, cold start capability, EMI/RFI noise filter, advanced communication-RS485 port, user friendly LCD display, provision of auto loadsharing / parallel operation, suitable to operate at 415V, 50Hz, 3 Phase AC supply and delivering 2 phase & single phase loads with 3 phase output of theUPS and necessary safety protection. The job also includes supply and connecting the suitable required number of 12V, SMF batteries of suitable amp hour, for each UPS separately/Individually to give a backup time of minimum 30 minutes for each UPS separately/Individually at the rated full load along with battery management feature integrated with UPS, battery rack, connectors, wiring, cabling between battery bank and UPS with insulated copper conductor of required size, termination as per site condition etc. complete as required.
2Design, Fabrication & Supplyof TotallyTypeTestedAssembly Panel (Form - 4B Construction)complyingtoIEC : 61439-1 & 2cubicle type LTpanel, withinternalarc withstand as per IEC : 61641 for 50 KA for minimum 0.3 sec and minimum impact resistance lK09 / lK10 as per IEC : 62262, cubicle type body made out of 2 mm thick CRCA sheet,totally enclosed,IP 42,floor/wallmountedwith channel base frame,dustandverminproof indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50 Hz AC,50 kA / 1 sec.systemwithextensiblebus-barsonbothsides,makingelectrical & mechanical interlocking arrangement between incomers & bus-coupler beakers includingcontrol wiringwith 2.5 sq mm size wires/cable,interconnection, duly powder coatedpaintingetc.indudingsupply&installationoffollowingswitchgears,metering instrumentsand accessories as perspecifications. Entire panel shall have a common Copper earth bar of size 25 mm x 6 mm at the rear with 1 Nos earth stud.
3Incomer
42 Nos. 630 A, 4P MCCB,Microprocessor based release (lcs = lcu = 36 kA) with inbuilt O/L , S/C & E/F protectionas per specificationand each incommershall be provided with following accessories.
5Extended Rotary operating Mechanism
6Spreader Terminals (Set of 8) with Phase Barriers
7Auxiliary 1 C/O + TAC 1 C/O
81 Set of ON/OFF/TRIP indicating LED lamps with 2 amp back up MCB.
91 Set of phase indicating LED lamps with 2 amp back up MCB.
101 No. Digital MFM meter and 3 Nos. Cast resin CTs of ratio 630/5 A, Class 0.5 accuracy and10 VAburden digitalmultifunctionmetersuitableto measurevoltage, Ampere Frequency, Power Factor, Measurement of KVA/KW/kVAH/MDI, Individual Odd Hamonics for voltage and current including THD with RS-485 port.
11Busbars
124P aluminiumbus bars of630 Acapacitywith heatshrinkablecolouredsleevesincl SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec.
13The electrical panel shall be fully ventilated to maintain internal body temp. < 40 deg C when room amb. temp. is equal of less than 35 deg. C. Required ventilation fans shall be provided and tested.
14Outgoings
154 Nos - 250 A, 4P MCCB with builtin themal magneticrelease with adjustable themal setting (Ics= lcu =36 KA)
16Extended Rotary operating Mechanism
17Spreader Terminals (Set of 8) with Phase Barriers
18Auxiliary 1 C/O + TAC 1 C/O
191 Set of ON/OFF/TRIP indicating LED lamps with 2 amp back up MCB.
20Design, Fabrication & Supply of cubical type LTpanel, made out of 2 mm thick CRCA sheet, totally enclosed,IP 42,floor/wallmountedwith channel base frame,dustandverminproof indoor, compartmentalized, suitable for operation on 3 phase and neutral, 415 V, 50 Hz AC,50 kA / 1 sec.systemwithextensiblebus-barsonbothsides,duly powder coatedpaintingetc.including supply&installationofmetering instrumentsand indicating lamps having4P aluminiumbus bars of630 Acapacitywith heatshrinkablecoloredsleevesincl SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec. Size of Panel 1000 X1000X500 mm. Length of each Bus Bar shall not be less than 800mm. All spacing between bus bar shall be as per IS Standards.
21Supply of3.5 Core x 300 Sqmm size XLPEinsulated PVC sheathed, aluminium conductor,armoured, power cable of 1.1 KV grade conforming to IS 7098 (Part I), 1988 amended upto date.
22Supply and installation of 300 mm width X 62.5 mm depth X 2.0 mm thickness size perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thikness not less than 50 micron) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts etc as required.
23Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size above 185 sq. mm and upto 400 sq. mmon cable tray (clamped with 40x3mm MS flat clamp) as required.
24Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size above 95 sq. mm and upto 185 sq. mmon cable tray (clamped with 25x40x3 mm) required.
25Supply and making end termination with brass compression gland and aluminium and/copper lugs as per cable for 3.5 Core x 300 (70mm) sizePVC insulated PVC sheathed aluminium conductor cable of 1.1 KV grade complete as required.
26Supply of1 Core x 120 Sqmm size XLPEinsulated PVC sheathed, stranded copper conductor,unarmoured power cable of 1.1 KV grade conforming to IS 7098 (Part I), 1988 amended upto date.
27Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
28Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
29Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
30Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
31Providing and fixing 25mm X 5 mm GI strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
32Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.