Rural Water Supply And Sanitation Division has published Supplying Of All Materials, Labour, T&P For Erection , Installation, Testing & Commissioning & Construction Of 3Ph - 3W, 11 Kv Line With 3C 35 Mm2 Xlep Cable = 0.18Kms. (Double Circuit), Construction Of 11/0.4Kv 100Kva Plinth Mounted S/S (Handed Over To T. Submission Date for this Tender is 28-02-2024. Labour Work Tenders in hinjilicut Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Commissioning & Construction of 3ph - 3w, 11 KV Line with 3C 35 mm2 XLEP Cable = 0.026Kms. (Double Circuit) including Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
2 | 10 mtr long, 330 KG, PSC pole. |
3 | RCC Base Plate. |
4 | GI 11KV V Cross Arm (10.20kg. Each) |
5 | GI 11KV "F" Clamp (Pole Top Bracket) (2.9 Kg. Each) |
6 | Back Clamp for "V" Cross Arm (11KV) (0.85 Kg. Each) |
7 | 100X50x6 mm. Channel St Cross Arm 1.45Kg. @ 9.20Kg/mtr 4 Nos. Including Top Piece. |
8 | Galvanisation of all RS & MS materials. |
9 | 11 KV Pin Insulator POLYMER |
10 | HT stay set complete |
11 | HT Stay Insulator |
12 | HT Stay clamp ( 1.9Kg/Pair) |
13 | 7/10 SWG GI wire (Grade 2) |
14 | Earthing (coil type) for support |
15 | 3 Core 35 mmsq 11 KV XLEP Cable (Armoured) |
16 | Heat Srinkable Jointing Kit 3 Core 35 mm2 11KV XLEP Cable (out door type) |
17 | Conductor Dead End Clamp Suitable for bare massenger |
18 | Eye Hook for XLEP Cable |
19 | Pole Clamp for Eye Hook for XLEP Cable |
20 | 7/12 GI stay wire for supporting XLEP Cable |
21 | XLEP Cable clamp to hold support wire |
22 | GI Pipe Earthing Device 40mm dia medium gauge (3.25 mm thickness) 3mtr. long |
23 | No. 6 GI Wire for earthing |
24 | 12KV 5 KA 11 KV Lightening Arrester |
25 | 75x40x6 mm, Channel for LA(6.80 Kg./Mtr) |
26 | Danger Plate 1 No. |
27 | Back Clamp for danger Plate (25x3 mm flat, 0.59kg/mtr) flat of 0.510mtr. 1 No. |
28 | GI Barbed wire for antyclimbing Device 3 Kg. per support |
29 | Back Clamp for anticlimbing devices 25x3 mm Flat, 0.59kg/mtrs Flat of 0.510 mtrs Length = 4 Nos. |
30 | G.I Bolts, Nuts. & Washers of assorted size |
31 | Sundries. |
32 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Commissioning of 11/0.4KV 100KVA Plinth Mounted S/S (Handed Over To TPSODL) with brick boundary wall = 1 No. including Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
33 | 9 mtr long, 300 KG, PSC pole. |
34 | RCC Base Plate. |
35 | Top Pressure Channel GI (100X50x6) mm. GI 2.80 mtr. Long 2 Nos (9.20Kg/mtr) |
36 | Transformer Mounting Channel GI 100x50X6mm (9.20Kg/mtr.) x 2.80 mtr. each x 2 Nos |
37 | HG Fuse & AB Switch Mounting Channel (75x40X6)mm GI 2.8 Mtr long 4Nos (6.8 Kg./Mtr.) |
38 | Transformer Belting (50X50X6)mm GI angle 2.80mtrs. Long 2 Nos. (4.5 Kg./Mtr) with side angle total 7mtrs. Long. |
39 | Cantilever Channel for supporting HG Fuse (75x40x6) mm GI 1.00mtr. Long 2 Nos. (6.80 Kg./Mtr) |
40 | Cantilever angle for supporting HG Fuse(50x50x6) mm GI 1.50mtr. Long 2 Nos. (4.50 Kg./Mtr) |
41 | Angle for mounting LT distribution box (35x35x5) mm GI 1.00mtr. Long 2 Nos. (3.5Kg./Mtr) |
42 | Galvanisation of all RS & MS materials. |
43 | 11 KV AB Switch (200 Amp,,3 pole, 50Hz) |
44 | 11 KV HG Fuse (200 Amp,,3 pole) with PI |
45 | 25X6 mm GI Flat (for others) |
46 | 25X4 mm GI Flat (for Lightening Arrester) |
47 | 12KV 10 KA 11 KV Lightening Arrester |
48 | Earthing (coil type) for support |
49 | HT stay set complete |
50 | HT Stay Insulator |
51 | HT Stay clamp ( 1.9Kg/Pair) |
52 | 7/10 SWG GI wire (Grade 2) |
53 | 80 mmsq AAA conductor |
54 | 3.5 Core 120 mmsq LT PVC Cable (UN-Armoured) |
55 | LT distribution box with MCCB alluminium busbar for two bay Kit Kat fuse for 100 KVA S/S. |
56 | 100KVA11/0.4KV (AL) transformer BIS Energy Level-II |
57 | GI Pipe Earthing 40mm dia medium gauge (3.25mm Thickness) 3mtr long |
58 | Danger Plate 1 No. |
59 | Back Clamp for danger Plate 25x3 mm flat 0.59kg/mtr flat of 0.510mtr. length 1 No. |
60 | GI Barbed wire for antyclimbing Device 3 Kg/Device. |
61 | Back Clamp for anticlimbing devices 25x3 mm Flat (0.059kg/mtrs) Flat of 0.510 mtrs Length = 4 Nos. |
62 | G.I. Bolts, Nuts & Washers |
63 | Sundries (Al Binding Tape, Insulation Tape,GIS Numbering, Etc.,) |
64 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Commissioning etc. of 3 phase service connection For 48 KW Loadincluding Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
65 | 35 mm sq 31/2 Core PVC Cable |
66 | No. 8 SWG 4.06mm dia Wire |
67 | Alluminium Binding Wire |
68 | 200 Amp. Kit Kat Fuse |
69 | Sundries. |
70 | Supplying all materials, labour, T&P for construction of Civil Works. |
71 | Cement concreting for STUD & Stay Anchor plat C.C. 1:3:6 by using 4cm size hard granite metal = (0.45Mx0.45Mtrx1.5) M = 0.3cum @ 4158.84 =0.3037xRs.4158.84 = Rs.1263.03 or Rs.1270.00 |
72 | Padding & Concreteingfor supportC.C. 1:3:6 by using 40mm size hard granite metal = (0.45Mx0.45Mtrx1.5) M = 0.3037cum @ 4158.84 =0.3037xRs.4158.84 = Rs.1263.03 or Rs.1270.00 & Coupling C.C. 1:3:6 by using 12mm size hard granite chips = (0.30Mx0.30Mtrx0.45M) = 0.0405 Cum @ Rs 4718.80/Cum. = 0.0405 x Rs 4718.80 =Rs.191.11 = Rs.1270.00+Rs.190.00 = Rs.1460.00. |
73 | Materials for earthing including masonry work for earth pit & Cement Plate Cover With Salt, Charcoal, Etc., |
74 | Brick Wall boundary (Size = 10"x12"x5") with fixing of Iron Grill GateEtc., |
75 | Sand & Metal Sprading |
76 | Supplying of all materials, labour, T&P forInstallation, Fitting, Fixing, Testing, Commissioning etc. of Internal wing toRWSS Pump House including Stock, Storage & Insurance ,Transporation (as per REC Standard) and as per requirement of TPSODL & RWSS. |
77 | Iron frame of size 3-0"x4"-6" made out of flat angle wall mounted for fixing of bus bar, kit-kat, 63A and 32A and control pannel etc., |
78 | Supply & fixing of 38/40 mm dia Gi pipe of required length as per I.E. Rule with perforated holes from bottom to top and upper end threaded and fitted with suitable flange for making connection of earth continuity wire fixed by G.I. nut and bolt and the earth pit have an altimate layer of charcoal and salt & replastering the grooved , cutted walls of pump house with cement mortar after laying the wire from main switch to earth electrode. |
79 | Supply & fixing of 63A, 415V I.C. TPN main switch with fuse unit, 2 nos of 63Amp, 415V kit kat fuse mounted on the iron frame and 2 phase bus bar mounted on the iron frame for distribution of power supply with surface wiring to phase indicator point fixing on suitable size of metalic box with 3mm thick laminated plate with all accessories and connection. |
80 | Supplying and fixing of 32A, 415V, TPN main switch with double fuse unit fixed on MS frame with all accessories etc., complete. |
81 | Supply , fitting, fixing ofsuitable wiringupto single phase motor 2 nos with 63Amp main switch, 32 Amp main switch 2 nos with suitable bus bar and 63Amp. Kit kat unit indicator with provision of light point 3 nos, plug point-1no, fan point-1no, and 2 nos earthing device by providing 16Amp, 230V D.P. main switch fixed on frame with nut and bolt etc., complete |