Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Erection Of Structure & Equipment’S Required For Construction Of 01 No.33 Kv Feeder Bay For M/S Air Force Station (Mes) Chandinagar., (Deposite) At 132 Kv Sub Station Harsiya, Under Etd Baraut.. Submission Date for this Tender is 09-03-2024. Feeder Pillar Tenders in baraut Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 26-Feb-2024 | DATE EXTENSION | Date | 02-03-2024 |
2 | 04-Mar-2024 | DATE EXTENSION. | Date | 09-03-2024 |
Sl. No. | Item Description |
1 | PART -A WORK |
2 | Carriage of Main & Auxiliary structure from Electy., fabrication unit Naini Prayagraj To 132 KV S/S Harsiya. |
3 | Sorting, counting, stacking mark wise and head loading of structure (approx 3.2 MT) on truck at electy., fabrication unit Naini Prayagraj. |
4 | Safe carriage of loaded structurefrom electy. fabrication unit Naini Prayagraj To 132 KV S/S Harsiya, under ETD-Baraut (Distance approx. 730 km) CCM - (1 No.) CGM - (1 No.) CPM - (1 No.) YMM - (1 No.) ALP - (13 No.) ABL - (2 No.) |
5 | Unloading of carriage structure (approx 3.2 MT) from truck its Sorting, Counting and proper Stacking at the S/Ss premises as per direction of supervisioning engineer. |
6 | Erection of 33 KV lattic type main & Auxiliary Structure as ALP-13 Nos (approx weight- 121Kg), ABL-02Nos (approx weight-341 Kg), CCM-01Nos (approx weight-359 Kg), CGM-01Nos (approx weight-315 Kg), CPM-01Nos (approx weight-50 Kg) and YMM-01Nos (approx weight-22 Kg) and 33 KV Circuit Breaker related structure installing as per drawingwith the help of G.I. nut & bolt, flat, spring washer, matching the hole. |
7 | Erection of 33 KV equipments including shifting of equipments and accessories from store to erection site, fixing of required clamps, jumpering and all related cable termination according schedule, welding and other related associated works with testing and commisoning. |
8 | 36 KV Bus Isolator (1250 Amp) |
9 | 36 KV Line Isolatro |
10 | 36 KV CTs (400/200/1A) |
11 | 36 KV CT Junction box |
12 | 30 KV LA |
13 | 33 KV P.Ts. |
14 | 33 KV Junction Box (P.T) |
15 | 33 KV VCB |
16 | 33 KV Tripple feeder control and relay panel (Simplex Type) |
17 | Fixing of metering cubical and ABT meter set and other related associated works. |
18 | Jumpering of all equipments of 33 KV Bay with ACSR Panther conductor in between 33 KV Main Bus to Bus Isolator, BI to CB, CB to CT, CT to CT, CT to PT, PT to LA, LA to LI etc. with the help of suitable clamps and required cutting and bending of conductors and all other works to complete the job seticefectory. |
19 | Earthing of Structure, Equipments, metering cubicle & Panel. a) Cutting, straightening & laying of following MS flat 750 mm below inside ground and above ground of 50 mm x 6 mm size and 25 mm x 6 mm size MS Flats for earthing of main auxiliary structures, equipment and cable trenches including welding with main earthmat and with the object to be earthed excavation of trenches its back filling painting and all other associated work to complete the earthing work satisfactorily as per technical specification. |
20 | Fresh Earthing,Connected With Earthmat 50x6mm |
21 | Fresh Earthing,Connected With Earthmat 25x6mm |
22 | Laying of following size of control cables in the cable trenches/GI pipe for 33 KV CB, CT, PT, Isolator, tripple feeder panel and Metering cubical etc. in switchyard/ control room as per cable schedule including carriage of cable drums from stores to work site and shifting back to store with all other associated works to complete the job satisfactorily as per technical specifications:- |
23 | Laying/terminate,cable,cntrl,2cx2.5sqmm |
24 | Laying/terminate,cable,cntrl,4cx2.5sqmm |
25 | Laying/terminate,cable,cntrl,6cx2.5sqmm |
26 | Making delta earthing for 30 KV LA with the help of 3 Mtr. long electrodes in the shape of triangle with 1.5 mtr.made by 40 mm M.S. rod and 50x6mm M.S. flat to be connected with earthmat grid and as per techincal specification. (MS Flat and rod will be provided the Department) |
27 | Work of 33 KV Bay Integration in SCADA System (M/S Schweitzer Engineering Laboratories, Pvt Ltd, Make) with all associated works & all material supply will be provided by the contractor at his own cost as per requirement for SCADA Intergration. |
28 | PART -B SUPPLY |
29 | 33 KV Isolator clamp for twin panther conductor made of aluminum alloy LM-6. |
30 | 33 KV CT clamp for twin panther conductor made of aluminum alloy LM-6. |
31 | 33 KV PT clamp for panther conductor made of aluminum alloy LM-6. |
32 | 4 Bolted type PG clamp made of Aluminum alloy LM-6 with GI Nuts, Bolts & Washer suitable for Zebra to panther. |
33 | 4 Bolted type PG clamp made of Aluminum alloy LM-6 with GI Nuts, Bolts & Washer suitable for Panther to Panther. |