Council Of Scientific And Industrial Research-CSIR has published Tender For Renovation Of Bio Diesel Plant, Cable Laying To Various Laboratory Buildings And Upgrading Of Ceiling Fans, Exhaust Fans And Pcc Panel At Csir-Iict, Hyderabad.. Submission Date for this Tender is 27-02-2024. Cable Laying Tenders in hyderabad Telangana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
2 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
3 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
5 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
6 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
7 | S/F PVC Conduit: Supplying and fixing of following sizes of PVC conduit along with accessories on Metal Angular frames, pipes with necessary weldings to fix pvc pipe/ surface/recess cutting the wall and making good the same in case of recessed conduit as required. (Make:Sudhakar) 25mm |
8 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) (i) 8 way (4 + 24), Double door |
9 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 250 A tinned copper bus bar, common neutral link, earth bar,din bar for mounting 125 A,MCCB as incomer and MCBs as outgoing. Specifications :- 12 way , Double door VTPNDB with powder coatedbottom and top cable Entry boxes including following switch gear . 1)125A 3pole 36KA MCCB as incomer-1no Make:L&T/Legrand/Schneider |
10 | Supplying & fixing of TP&N sheet steel enclosure MCB DB in recess/surface including painting, earthing etc., as required. Make: Legrand |
11 | Supply of 3.5C x 35 sq.mm Al.Conductor armoured XLPE, PVC sheathed 1.1kV grade cable. |
12 | Supply of 3.5C x 50 sq.mm Al.Conductor armoured XLPE, PVC sheathed 1.1kV grade cable. |
13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
14 | (i) Upto 35 sq. mm (clamped with 1mm thick saddle) |
15 | (ii) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
16 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
17 | (i) 3.5C X 35 sq. mm (32mm) |
18 | (ii) 3.5C X 50 sq. mm (35mm) |
19 | P/F 4mm copper earth wire with conduit/cable: Providing and fixing 4.00mm dia. copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ sub main wiring/cable as required. |
20 | Earthing with copper earth plate 600mmX600mmX3mm thick including brazing of 40mm dia medium class GI Pipe with all accessories, Providing two runs of 25mmx5mm Copper strip from copper plate with proper brazing upto 2.7mtrs lengthand providing masonry enclosure with cover plate having locking arrangement with charcoal/ coke and salt as directed by Engineer incharge. |
21 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
22 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
23 | S/F "C" series MCB: Supplying and fixing of 5A to 32A rating, 240V/415 V, 10 kA, "C" curve. Miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc., as required. |
24 | (i)Single pole |
25 | (ii) Triple pole |
26 | (iii) Triple pole & Neutral |
27 | S/F "C" series MCB: Supplying and fixing of following rating, 240V/415 V, 10 kA, "C" curve. Miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc., as required. Make:Legrand/L&T/Scheinder/ABB |
28 | (i) 3 pole 63A MCB |
29 | (ii) 4 pole 63A MCB |
30 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 12 Module (200mmX150mm) |
31 | S/F Modular type switch / socket / fan regulator / call bell: Supplying and fixing of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc., as required. |
32 | (i) 5/6 A switch |
33 | (ii) 15/16A One way Switch |
34 | (iii) 3 pin 5/6 A socket outlet |
35 | (iv) 6pin 15A/16A power socket outlet |
36 | Disconnecting and removing of oldDB/ Light fittings, Ceiling fans and all electrical Gadgets in pilot plant laboratory: Disconnecting and removing of existing light fittings of all types / Ceiling Fans/ wall mount brackets and Existing Switch boards, MCB Enclosure boxes, Old DB of all types including existing wiring and transporting all the dismantled materials with out any damage from the site to departmental stores/ debries yardas directed by the Engineer in charge. |
37 | Supplyingof flame proof FWL 40 W LED well glass fitting set completely with all accessories as directed by Engineer incharge. Make:Crompton |
38 | Fixing of flame proof LED fixture in pilot plant at a height of about 20 feet with necessary hardware as directed by Engineer Incharge. |
39 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm |
40 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 95 sq. mm and upto 185 sq. Mm |
41 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 95 sq. mm and upto 185 sq. Mm |
42 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
43 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
44 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
45 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (57mm) |
46 | SITC of PCC panel of rating 300 A, 415 V, Three Phase and Neutral, 50 Hz, Outdoor, Double door, Floor Mounted, Fixed type, Compartmentalised type, CRCA Sheet steel of thickness not less than 2 mm for load bearing members and 1.6 mm thick for Doors of LT panels and2 mm for Gland plate, suitable Tinned Copper Busbar of 300 A, neutral bus bar of suitable capacity, earth bar, din bar, interconnections with adequate size of copper strip extended upto the cable alley side, powder coated paintingwith 7tank process of approved color, including earthing etc., MS angle frame pedestal to suit the PCC panel andcovered with duly enamyl paintedG.I. sheets (screw & nut fixed) for three sides of the pedestal, IP65, Dust and Vermin proof, maximum operable height of Panel must not be more than 1.7 metre and maximum vertical height of panel must not exceed 2.5 metre, Top and Bottom provision by Gland plates for Incoming and outgoing cables etc.and making good of floor/base, the general construction shall conform to IS8623:93 with cable and anodized compartments labelling as required by the Engineer incharge and mounting of the following components as per the requirements. The drawing of PCC Panel approval has to be taken before fabrication, PCC panel on site inspection will be done during fabrication and testing by Engineer Incharge, once the final inspection and testing is done the PCC panel can be transported to site. A. INCOMER: (i) 250 A, 4P, 36 kA, MCCBwith Thermal-magnetic release, ROM-Rotary Handle O/C & S/C protection - 01 No. (ii) MCCB Mounting Accessories (Spreaders, Spacers etc.) - 01 set. (iii) Digital Multi-Function Panel meter (Voltage, Current, Hz, kWhr etc.), model Quasar class1, 3PH, 4W IPM 240V (L-N) 5A CL 1FM cat.no.WI 300FC 5300 make:L&T - 01 No. (iv) CT"s 250/5 A, 10/5 VA - 03 No. (v) MCB"s and Fuse set for Control wiring and pilot lamp protection - 01 Set (vi) RYB, LED Pilot lamps -01 set. B. OUTGOINGS: 1) 125 A, FP, MCCB - 05No. Requirements: (i) 125 A, 4P, 25 kA, MCCB with Thermal-Magnetic release, ROM-Rotary Handle, O/C & S/C protection - 01 No. (ii) MCCB Mounting Accessories (Spreaders, Spacers etc.)-01 set. 2) 100 A, FP, MCCB - 03 No. Requirements: (i) 100 A, 4P, 25 kA, MCCB with Thermal-Magnetic release, ROM-Rotary Handle, O/C & S/C protection - 01 No. (ii) MCCB Mounting Accessories (Spreaders, Spacers etc.) - 01 set. 3) 63 A, 4P, "C" Curve, MCB - 06 No. |
47 | Removing of Old Existing PCC Panel complete including removing of pedestal or foundation, disconnection of existing power cables and circuits without any damage and reconnecting the same after installation of new PCC Panel with all necessary hardware required etc., as directed by Engineer Incharge. |
48 | Labelling and Lettering of PCC Panel of required font to suit the equipment with required coloured paint with elegant finishing as required by the department. |
49 | Labelling and Lettering of PDB / LDB of required font to suit the equipment with required coloured paint with elegant finishing as required by the site Engineer. |
50 | Labelling and Lettering of Switchboard/Power board of required font to suit the equipment with required coloured paint with elegant finishing as required by the Engineer. |
51 | Supply of 3.5C x 185 sq.mm Al.Conductor armoured XLPE, PVC sheathed 1.1kV grade cable. |
52 | Supply of 250W, LED Floodlight made up of pressure die cast aluminium housing with toughened glass and high power LED"s and secondary lenses with IP66 protection. System efficacy>110 Lm/w, 10 KV SPD included. Make: Crompton Model: CFS-506-250-57-60D-SL-GL-NSG |
53 | Supply of 26-28watts, 1200mm BLDC ceiling fan sweep: 1200mm (48"),Rated Voltage: 230V, Frequency:48-52 Hz, BEE Rating: 5 Star, Operating Voltage:140-285v single phase AC, Power factor:>0.9, Air Delivery:235 CMM Rated power: 26-28 watts, Motor Speed: 340-380 RPM with speed control, Bearing: Double Ball Bearing, Down rod size with rubber bushes: 300mm, Operating temperature with in 2 degree of ambient, warranty: 3 yrs on site, Speed control: Remote/Regulator control and as directed by Engineer Incharge. Model:EFFICIO/Aria Sweep:1200mm (48") Colour:White Make: Atomberg/ Crompton / Usha/ Orient/ HAWA |
54 | ITC ceiling fan: Installation, testing and commissioning of ceiling fan, including down rods oflength (upto 8 feet) with all mechanical supports if necessary, connections, paintings etc; should be done as directed by Engineer incharge. |
55 | Supply of single phase, 230 V, 50Hz, 230 mm sweep, 1400 RPM Heavy duty exhaust fan complete set as directed by Engineer incharge. Make:Crompton/Havells/Almonard |
56 | Supply of single phase, 230 V, 50Hz, 305mm sweep, 1400 RPM Heavy duty exhaust fan complete set as directed by Engineer incharge. Make:Crompton/Havells/Almonard |
57 | Supply of single phase, 230 V, 50Hz, 450 mm sweep, 900 RPM Heavy duty exhaust fan complete set as directed by Engineer incharge. Make:Crompton/Havells/Almonard |
58 | Supply of BLDC Pedestal fan of 400mm sweep with remote control operation etc; complete set as directed by Engineer incharge. Make:Atomberg/Crompton/Havells/Hawa |
59 | Installation, testing and commissioning of flood light fittings/ wall decorative fittings with controllers, lamps and all interconnected accessories like drivers, bridge, dimmer as required. The work includes wiring in recess / surface as required complete and as directed by the engineer incharge. |
60 | Disconnection and removing of old existing end terminations of all size cables from existing PCC Panel without any damage and as directed by Engineer incharge. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail