| 1 | SH -I ( WIRING ) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required (a) Group- A |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiringforlight/powerplugwith4X4sq.mmFRLSPVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | (b) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.(I/c for fire detection) (a)2 x1.5 Sqmm. |
| 7 | (b)4 X1.5 sqmm. |
| 8 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 20 mm |
| 9 | (b) 25 mm |
| 10 | Dismantling shifting and reinstallation of following electrical accessories from old TE Bldg to new TE bldg sector 28 i/c making connection testing etc complete as reqd (a)2W SPN DB with MCB |
| 11 | (b) SAC controller |
| 12 | (c) 125Amp Main switch |
| 13 | (d) 125 Amp Changeover switch |
| 14 | (e)125 Amp P.D. Panel |
| 15 | (f) 4W TPN DB with MCB |
| 16 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 17 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 18 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. (1) Upto 450 mm sweep |
| 19 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure withcover plate having locking arrangement and watering pipe of 2.7metre long etc. with charcoal/ coke and salt as required. |
| 20 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut, bolt,spring, washer excavation and re-filling etc. as required. |
| 21 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or inrecess for connections etc. as required. |
| 22 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required |
| 23 | Providing and fixing G I earth bus bar section 50mm X 5mm X 300mm length with G I bolts and nuts washers etc as required including providing and fixing porcelain insulators, nuts bolts drilling and fixing etc as required. |
| 24 | Dismantelling, Shifting and ITC of fire detection system comprising 4 zone main panel, All type fire detector, Hooter, response indicator, Manually Call point, including repairing and servicing of panel , replacement of all faulty internal parts i/c charging system ,control cards,zone card,hooter etccomplete as required. (Old TE Dhansura To New TE Dhansura) |
| 25 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 26 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 27 | Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 28 | Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 29 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
| 30 | Dismantelling, Shifting and ITC of fire detection system comprising 4 zone main panel, All type fire detector, Hooter, response indicator, Manually Call point, including repairing and servicing of panel , replacement of all faulty internal parts i/c charging system ,control cards,zone card,hooter etccomplete as required. (Old TE Dhansura To New TE Dhansura) (a) Control Card |
| 31 | (b) Zone Card |
| 32 | (c) Power Card |
| 33 | (d) SMPS Charging Unit |
| 34 | Replacement of defective 1.0 mtr long hose pipe( steel wire breaded pipe ) with brand new pressure tested horn pipe a/w suitable for existing 4.5/3.6 kg CO2 type fire extinguishers etc as required. |
| 35 | Refilling of existing 4.5 kgs. CO2 type fire extinguishers including transportation to authorised service centre including testing, pvdg. data sheet sticker & factory certificate etc as required |
| 36 | Replacement / supply of following rating sealed maintenance free battery in dully charged condition i/c fixing making connection testing etc.as required ( Approved make of BSNL ) (a) 12 Volts, 20 AH |
| 37 | Conducting of Fire drill of the FD & FA system of T E Building as per the department norms i/c minor repairs work if any, cleaning of detectors with blowers etc. complete as required. (a) For Ground floor+ 1 only |
| 38 | Dismantelling ,Shifting and ITC of 1.5/2.0 TR SAC/inverter type split A/C unitcomplete with standard accessories indoor and outdoor unitincluding pump down, laying of existingrefrigerant piping insulating them, brazing,pressure testing,vaccumisation R-22/R-430 gas charging i/c topping up etccomplete as reqd.( from old exchange to new exchange in same station including loading, unloading at both end etc complete as reqquired.) |
| 39 | Supplying and fixing of additional ( other than supplied with split AC) copper pipe of size 1/4\" and 5/8\" and 2.5sqmm PVC insulated PVC sheathed three core copper conductor cable including cutting brazing insulating and other accessories etc as reqd. |
| 40 | Providing and fixing of additional 15mm drainage pipingin recess/surface suitable for water drainage system etc as reqd |
| 41 | Supplying and fixing of 1 no. 3 core 4 Sq.mm PVC insulated PVC sheathed armoured copper conductor cable on surface of wall etc. as reqd (M/s. Finolex/Polycab/Plaza or similar superior make) |
| 42 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. (A) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 43 | (B) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 44 | Installation, testing and commissioning of50 KVA E/A setI/c all accessories i.e. panel, silencer, exhaust pipe including providing insulation with asbesos rope, fuel tank etc.on existing foundation/floor with replacing of lubricating oil, oil and fuel filters,cleaning and servicing of air filterconducting testing for 8 hours as per BSNL norms complete as reqd. |
| 45 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(a) 3 1/2 C X 35 sq. mm |
| 46 | (B) 4C X 10 sq. mm |
| 47 | Replacement of porcelain fuse cutout (Carrier & Base) of following capacity with rewireable fuse wire etc comp as reqd. (One piece) (A) 100 A |
| 48 | Dismantling and Shifting of following Itemswithaccessories etc. within sameSSAat the following stationincluding loading, unloading at both end transportation and laying at the instruction of Bldgincharge TE Dhansura etc. complete as required. (A) 110KVA EA set |
| 49 | (B) 125 KVA MV Penel Board |
| 50 | ( C ) All Electrcal wiring with accessories i/c, Al cable, steel conduite,all type of switch board,fans,lighting etc. |