Tender For Spl Repair/Replacement Of Starter Panels Alongwith Connected Works At Water Pump House And Filter Media And Connected Works At Abhera At Mil Stn Kota, kota-Rajasthan

Military Engineer Services-MES has published Tender For Spl Repair/Replacement Of Starter Panels Alongwith Connected Works At Water Pump House And Filter Media And Connected Works At Abhera At Mil Stn Kota. Submission Date for this Tender is 12-03-2024. Starter Tenders in kota Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42271449
Corrigendum : Tender For Spl Repair/Replacement Of Starter Panels Alongwith Connected Works At Water Pump House And Filter Media And Connected Works At Abhera At Mil Stn Kota
Open Tender
Indian
Rajasthan
kota
12-03-2024

Tender Details

Spl Repair/Replacement Of Starter Panels Alongwith Connected Works At Water Pump House And Filter Media And Connected Works At Abhera At Mil Stn Kota

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Mar-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 12-03-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 53200.0 /-
Tender Value
INR 26.60 Lakhs /-

BOQ Items

Name of Work: SPL REPAIR/REPLACEMENT OF STARTER PANELS ALONGWITH CONNECTED WORKS AT WATER PUMP HOUSE AND FILTER MEDIA AND CONNECTED WORKS AT ABHERA AT MIL STN KOTA
Sl. No. Item Description
1Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth or n exc 10 Sqm on plan and n exc 1.5 m in depth & getting out, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes or for layingunderground cable, pipe lines etc. in soft/ loose soil, complete all as specified & directed.
2Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed.
3Removing excavated material (soil) n exc. 50m distance and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed.
4M&L dry clean sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover complete all as specified and directed. Note:- Thickness after punning shall be considered for payment.
5M&L for pulverized fuel Ash-lime bricks (Fly ash bricks - non modular size), class 10, laid dry and flat adjoining each other over sand cushion in trenches as protection to UG cable, complete all as specified and directed.
6M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 25x4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: -(a) Irrespective of whatever is shown in plate No 5 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b)Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m.
7S&F in renewal of 50 mm bore Steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
8Supplying, laying, jointing, testing and commisioningXLPE insulated, screened, PVCbedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade (ISI marked), laid in trenches / ducts / encased in GI pipe / fixed to pole/wall with necessary angle iron support, clamp, nut , bolts etc and including taking down old unserviceable existing XLPE LT UG cables complete all as specified and directed for following cross sectional areas of cables :- Cross Sectional area of cable 120 Sqmm, 3.5 core
9Cross Sectional area of cable 70 Sqmm, 3.5 core
10Cross Sectional area of cable 50 Sqmm, 3.5 core
11Cross Sectional area of cable 16 Sqmm, 4 core Notes for Srl item Nos. 8.10 to 8.40 :-(i) Excavation, earth work, sand cushioning, cable protection cover & GI pipes shall be measured and paid for separately under respective items of BOQ. (ii) Rate deemed to be inclusive of connecting up with control gear including cable glands and cable lugs.
12Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made automatic control LT Panel of PLC based of approx size 1.0x1.8x0.5m(OR as per Indian Electricity Rules), protection class IP-54 & made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated copper bus bar of 200 Ampere capacity and including all connection with copper busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including MS channel frame of ISMC 75 at the base of panel only for grouting purpose &necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing for automatic control of two pumps as main and standby of the capacity up to 15/20 HP load and including dismantling of old u/s existing panel, comprising of the following:- (a) PLC programme logistic control panel suitable for 15 HP two pumps - 01 Set (b) Star delta starter suitable for 15 HP pump - 02 Nos (c) Selector switch for auto/manual - 02 Nos (d) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three. (e) Push button for pump on/pump off - 04 Nos (f) CT coil as required (g) Over load relay for 15 HP pumps - 02 Nos (h) Automatic Phase sequence changer - 02 Nos (j)Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 01 No. (k)Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No. (l) Coductive type level switch - 01 No (m) MCCB, TPN, 415 volts 50 Hz, AC, 100 Amp rating with rupturing capacity 35 KA adjustable thermal and adjustable magnetic setting–01 No. (n) MCCB, 415 volts, AC,TP, 63 Ampere, breaking cap 25 KA adjustable thermal and adjustable magnetic setting–02 Nos.
13Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of approx size 1.0x1.2x0.5m (OR as per Indian Electricity Rules), protection class IP-65 made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated copper bus bar of 250 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including 40x40x6mm thick angle iron frame work at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) Copper bus bar of rating 250 Amps for four pole & including PVC heat shrink sleeves (RYB&N) - 01 Set (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 160 Amp rating with rupturing capacity 36 KAmicroprocessor control type– 01 No. (B) OUTGOING :- (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KAconfirming thermal magnetic release and adjustable over load setting– 02 Nos. (b) MCB, 230 volts, AC, two pole, 16 Amp, "C" curve,10 KA– 02 Nos. (c)Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 02 Nos. (d)Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 02 Nos. (e) Star / Delta starter suitable for 30 HP motor pump & including all connected accessories and over/under current protection relay and automatic phase changer - 02 Nos. Note :- (i) Necessary approval of drawings of LT feeder Pillars shall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
14Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of approx size 1.0x1.2x0.5m (OR as per Indian Electricity Rules), protection class IP-65 made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated copper bus bar of 300 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with FRLS cable, IS-694 marked of adequate size but not less than 4 Sqmm with new lugs, gland to be provided at cable entries and including 40x40x6mm thick angle iron frame work at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) Copper bus bar of rating 300 Amps for four pole & including PVC heat shrink sleeves (RYB&N) - 01 Set (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 200 Amp rating with rupturing capacity 36 KAmicroprocessor control type– 01 No. (B) OUTGOING :- (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA confirming thermal magnetic release and adjustable over load setting– 03 Nos. (b) MCB, 230 volts, AC, two pole, 16 Amp, "C" curve,10 KA– 02 Nos. (c)Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 03 Nos. (d)Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 03 Nos. (e) Star / Delta starter suitable for 25 HP motor pump & including all connected accessories and over/under current protection relay and automatic phase changer - 03 Nos. (f) Astronomical timer - 01 No Note :- (i) Necessary approval of drawings of LT feeder Pillars shall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
15Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of approx size 1.0x1.2x0.5m (OR as per Indian Electricity Rules), protection class IP-65 made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated copper bus bar of 150 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with FRLS cable, IS-694 marked of adequate size but not less than 4 Sqmm with new lugs, gland to be provided at cable entries and including 40x40x6mm thick angle iron frame work at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) Copper bus bar of rating 150 Amps for four pole & including PVC heat shrink sleeves (RYB&N) - 01 Set (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA confirming thermal magnetic release – 01 No. (B) OUTGOING :- (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 10 KA confirming thermal magnetic release and adjustable over load setting– 02 Nos. (b) MCB, 230 volts, AC, two pole, 16 Amp, "C" curve,10 KA– 02 Nos. (c)Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 02 Nos. (d)Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 02 Nos. (e) Star / Delta starter suitable for 15 HP motor pump & including all connected accessories and over/under current protection relay and automatic phase changer - 02 Nos. (f) Astronomical timer - 01 No Note :- (i) Necessary approval of drawings of LT feeder Pillars shall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
16Supplying, installation, commissioning and testing of cubical type LT panel board outdoor type, weather proof, manufactured by a CPRI approved factory, made of MS angle iron 50mmx50mmx6mm frame work and 3.15 mm thick CRCA sheet duly powder coated, totally enclosed dust & vermin proof, double leaf door shutter in front side with necessary locking arrangement made and with four side projected slanting roof of approved shade &including mounting on PCC plateform made out of PCC 1:2:4, type B-1, 200mm thick all round the panel board (15cm deep in ground and 5 cm above ground). The size of panel boards shall be suitable for housing the accessories given here under and also suitable for operation on AC 500 Volt, 3 Phase, 50 Hz, supply system and shall be complete with and including suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glandsand connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 500 Amp rating with rupturing capacity 50 KAmicroprocessor control type– 01 No. (b)Electronic digital type Ampere meter, 0-250 Amp with selector switch upto 250 Amp & 3 Nos CT"s ration 250/5 copper wound, square 96x96 mm - 01 No. (c)Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No. (d) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three. (B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 160 Amp rating with rupturing capacity 36 KA, adjustable thermal and adjustable magnetic setting– 03 Nos. (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 250 Amp rating with rupturing capacity 36 KA, adjustable thermal and adjustable magnetic setting– 01 No. (c) MCB, 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 10 KA– 03 Nos. (d) on load change over 200 Amp, 415 Volt type CO2-200, 4 Pole - 01 No (e) Astronomical time switch 110-240 volt 1C/O-2 Mod - 01 No Note :- (i) Necessary approval of drawings of cubical type LT panel boardshall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
17M & L for filling gravel of size 20mm to 40mm inside existing rapid gravity filter/ pressure filter at different locations complete all as directed.
18M & L for filling gravel of size 12mm to 20mm inside existing rapid gravity filter/ pressure filter at different locations complete all as directed.
19M & L for filling gravel of size 6mm to 12mm inside existing rapid gravity filter/ pressure filter at different locations complete all as directed.
20M & L for filling gravel of size 3mm to 6mm inside existing rapid gravity filter/ pressure filter at different locations complete all as directed.
21M & L for filling coarse sand of size 0.35mm to 0.50mm inside existing rapid gravity filter/ pressure filter at different locations complete all as directed.
22M & L for filling Magnese dioxide (FERRIMENIX COMPOUND) inside Activated carbon filter chamber complete all as directed.
23M & L for filling activated carbon pure coconut based IV 1200 (granular form 4mm - 8mm)/Anthracite cole media inside existing activated carbon filter chamber complete all as directed.
24Supply, installed, connecting and testing of 80mm bore butterfly valve, class PN 1.6 double flanged, long type, lever operated, ISI marked (IS-13095:1991, reaffirmed 2003) including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc, fixed to water mains, and including taking down old u/s butterfly valve complete all as specified and directed.
25Supply, installed, connecting and testing of 50mm bore butterfly valve, class PN 1.6 double flanged, long type, lever operated, ISI marked (IS-13095:1991, reaffirmed 2003) including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc, fixed to water mains, and including taking down old u/s butterfly valve complete all as specified and directed.
26Supply and installed, connecting and testing of sluice valve, class PN 1.6 double flanged CI body, wheel and brass spindle and nuts, non rising type, IS-14846 ISI marked including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc & including taking down old unserviceable existing sluice valve complete all as specified and directed of the following sizes :- 150mm bore
27100 mm bore
2880 mm bore
29Supply, installing, testing and commissioning high pressure single head gear motorised adjustable dozing pump 0 to 100 PSI, AC, 230 Volt, 50 Hz, 1 HP, LPH (0-25 LPH) complete with lead tubing, connecting nut, injection check valve, clay weight, ferrules along with Altoch/Alum dosing syatem consisting of 50 Ltr PE/FRP tank with lid & level gauge and agitator (1280 RPM) with shaft and blade in SS-316 on tank complete all as specified and directed. Note:- LId shall have part hole for pouring Altoch and water when necessary and provision for mounting decrine dosing pump on Lid/wall.