Rural Water Supply And Sanitation Division has published Supplying Of All Materials, Labour, T&P For Erection , Installation, Testing & Commissioning Of 11 / 0.4Kv, 63Kva Dp Mounted S / S = 1 No. ( Handed Over To Tpsodl ) , Construction Of3ph - 3W, 11 Kv Line With 3Cx35mm2 Xlpe Cable = 0.02 Kms ( 1Spa. Submission Date for this Tender is 22-02-2024. Bolts Tenders in Ganjam Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Commissioning ofConstruction of3ph - 3w, 11 KV Line With 3Cx35mm2 XLPE Cable = 0.02 Kms including Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
2 | 10 mtr long, 330 KG, PSC pole. |
3 | HT stay set complete |
4 | HT Stay Insulator |
5 | HT Stay clamp ( 1.9Kg/Pair) |
6 | 7/10 SWG GI stay wire |
7 | 3Cx35mm2 11 KV XLPE Cable |
8 | Heat Srinkable Jointing Kit 3 Core 35 mm2 11KV XLEP Cable (out door type) ( Double) |
9 | Conductor dead End Clamp Suitable for bare massanger |
10 | Eye Hook for XLEP Cable |
11 | Pole Clamp for Eye Hook for XLEP Cable |
12 | 7/12 SWG Stay wire for Support of XLEP Cable |
13 | XLEP Cable Clamp to hold Support Wire |
14 | GI Pipe Earthing Device 40mm dia medium gauge 3mtr long |
15 | No. 6 GI Wire for earthing |
16 | 12KV 5KA 11KVLightening Arreser |
17 | 75x40x6 mm Channel for LA (6.80 kg/mtr.) |
18 | Danger Plate 1 No. |
19 | Back Clamp for danger Plate (25x3 mm flat, 0.59kg/mtr) Flat of 510mm 1 No. |
20 | G.I. Barbed Wire anticlimbing Device 3Kg per Support |
21 | Back Clamp for anticlimbing devices 25x3 mm Flat (0.6kg/mtrs) Flat of 510 mtrs Length = 4 Nos. |
22 | G.I. Bolts, Nuts & Washers of assorted size. |
23 | Sundries (Al Binding Tape, Insulation Tape,GIS Numbering, Etc.,) |
24 | Supplying of all materials, labour, T&P for Construction of LT line With 4x50+1x501x16 mm2 AB Cable = 0.45Kms. 3ph S/C - 01 Nos. (18KW) including Stock, Storage & Insurance, Transporation (as per REC Standard) and as per requirement of TPSODL |
25 | 8 mtr long, PSC pole. |
26 | 8 mtr long, PSC pole( For Stud) |
27 | (4x50+1x501x16) mm2 AB Cable |
28 | LT stay set complete |
29 | LT Stay Insulator |
30 | LT Stay clamp |
31 | 7/12 SWG GI stay wire |
32 | Suspension Clamp With I Hook |
33 | Dead End Clamp Suitable for XLEP Cable |
34 | Pole Clamp for I Hook (For AB Cable) |
35 | Danger Plate 1 No. |
36 | Back Clamp for danger Plate (25x3 mm flat, 0.59kg/mtr) Flat of 510mm 1 No. |
37 | G.I. Barbed Wire anticlimbing Device 3Kg per Support |
38 | Back Clamp for anticlimbing devices 25x3 mm Flat (0.6kg/mtrs) Flat of 510 mtrs Length = 4 Nos. |
39 | Earthingsupport (coil type) |
40 | G.I Nut & Bolt |
41 | Sundries (Al Binding Tape, Insulation Tape,GIS Numbering, Etc.,) |
42 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Construction of 11/0.4KV 63KVA DP Mounted S/S = 1 No. ( Handed Over To TPSODL)including Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
43 | 9 mtr long, 300 KG, PSC pole. |
44 | RCC Base Plate. |
45 | Top Pressure Channel (100X50x6) mm. 2.80 mtr. Long 2 Nos (9.20Kg/mtr) |
46 | Transformer Mounting Channel 100x50X6mm 2.80 mtr.Long 2 Nos(9.20Kg/mtr.) |
47 | HG Fuse & AB Switch Mounting Channel (75x40X6)mm 2.8 Mtr long 4Nos (6.8 Kg./Mtr.) |
48 | Transformer Belting angle (50X50X6)mm 2.8 Mtr long 2Nos (4.5 Kg./Mtr.) with side angle (Total 7mtr Long) |
49 | Angle for mounting LT distribution (35x35x5)mm 1 Mtrs. Long, 2 Nos. (3.5 Kg./Mtr.) |
50 | Galvanisation of all RS & MS Materials |
51 | 11KV AB Switch 3 pole (200 Amp)HZ |
52 | 11KV HG Fuse 3 pole (200 Amp) |
53 | GI Pipe Earthing Device 40mm dia medium gauge 3mtr long |
54 | 25X6 mm GI Flat (for others) |
55 | 25X4 mm GI Flat (for Lightening Arrester) |
56 | HT stay set complete |
57 | Stay Insulator |
58 | Stay clamp |
59 | 7/10 ( 3.25mm dia per stand) SWG GI stay Wire (2.19Mtrs./Kg) |
60 | Disc Insulator (T & C) 45 KN POLYMER |
61 | HW Fitting (T&C) 45KN |
62 | 12KV 5KA 11KVLightening Arreser |
63 | 63KVA11/0.4KV (AL) transformer BIS Energy Level-II |
64 | LT distribution box with MCCB, Alluminium Buster of single bay with Kit Kat fuse for 63KVA S/S |
65 | 3Cx95mm2 LT PVC Cable |
66 | Danger Plate 1 No. |
67 | Back Clamp for danger Plate (25x3 mm flat, 0.59kg/mtr) Flat of 510mm 1 No. |
68 | G.I. Barbed Wire anticlimbing Device 3Kg per Support |
69 | Back Clamp for anticlimbing devices 25x3 mm Flat (0.6kg/mtrs) Flat of 510 mtrs Length = 4 Nos. |
70 | G.I. Bolts, Nuts & Washers of assorted size. |
71 | Sundries. |
72 | Supplying of all materials, labour, T&P for Erection, Installation, Testing, Commissioning etc. of 3 phase service connection For 18 KW Loadincluding Stock, Storage & Insurance,Transporation (as per REC Standard) and as per requirement of TPSODL |
73 | 35 mm sq 31/2 Core PVC Cable |
74 | No. 8 SWG 4.06mm dia Wire |
75 | Alluminium Binding Wire |
76 | 63 Amp kitkat fuse |
77 | Sundries. |
78 | Supplying of all materials, labour, T&P for Construction of Civil works. |
79 | Cement concreting for STUD & Stay Anchor plat C.C. 1:3:6 by using 4cm size hard granite metal = (0.45Mx0.45Mtrx1.5) M = 0.3cum @ 4158.84 =0.3037xRs.4158.84 = Rs.1263.03 or Rs.1270.00 |
80 | Padding & Concreteingfor supportC.C. 1:3:6 by using 4cm size hard granite metal = (0.45Mx0.45Mtrx1.5) M = 0.3cum @ 4158.84 =0.3037xRs.4158.84 = Rs.1263.03 or Rs.1270.00 |
81 | Materials for earthing including masonry work for earth pit & Cement Plate Cover With Salt, Charcoal, Etc., |
82 | Supplying of all materials, labour, T&P for Construction of Fencingworks. |
83 | Brick Wall boundary (Size = 10"x12"x5") with fixing of Iron Grill GateEtc., |
84 | Sand & Metal Sprading |
85 | Supplying of all materials, labour, T&P forInstallation, Fitting, Fixing, Testing, Commissioning etc. of Internal wing toRWSS Pump House including Stock, Storage & Insurance ,Transporation (as per REC Standard) and as per requirement of TPSODL & RWSS. |
86 | Iron frame of size 3-0"x4"-6" made out of flat angle wall mounted for fixing of bus bar, kit-kat, 63A and 32A and control pannel etc., |
87 | Supply & fixing of 38/40 mm dia Gi pipe of required length as per I.E. Rule with perforated holes from bottom to top and upper end threaded and fitted with suitable flange for making connection of earth continuity wire fixed by G.I. nut and bolt and the earth pit have an altimate layer of charcoal and salt & replastering the grooved , cutted walls of pump house with cement mortar after laying the wire from main switch to earth electrode. |
88 | Supply & fixing of 63A, 415V I.C. TPN main switch with fuse unit, 2 nos of 63Amp, 415V kit kat fuse mounted on the iron frame and 2 phase bus bar mounted on the iron frame for distribution of power supply with surface wiring to phase indicator point fixing on suitable size of metalic box with 3mm thick laminated plate with all accessories and connection. |
89 | Supplying and fixing of 32A, 415V, TPN main switch with double fuse unit fixed on MS frame with all accessories etc., complete. |
90 | Supply , fitting, fixing ofsuitable wiringupto single phase motor 2 nos with 63Amp main switch, 32 Amp main switch 2 nos with suitable bus bar and 63Amp. Kit kat unit indicator with provision of light point 3 nos, plug point-1no, fan point-1no, and 2 nos earthing device by providing 16Amp, 230V D.P. main switch fixed on frame with nut and bolt etc., complete |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy