Military Engineer Services-MES has published Tender For Repair/Maintenance Of Dg Set, Amf Panels, Lt Panels, Refrigerators/ Acs/Deep. Submission Date for this Tender is 12-03-2024. Overhead Line Tenders in leimakhong Manipur. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-Feb-2024 | BOQCORRIGENDUM | BOQ | 05-03-2024 |
2 | 05-Mar-2024 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 12-03-2024 |
Sl. No. | Item Description |
1 | Schedule "A" |
2 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing unserviceable materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc complete all as specified and directed. |
3 | Material and labour for point wiringsurface type with two single core 2.5 Sq mm (nominal area) FRLSPVC insulated and unsheathed,multi-stranded, copper conductor cable in and including suitable size PVC casing capping and requirement of suitable flexible pipe at site with all fittings and fixing accessories and suitable size PVC box for mounting switches, regulatorete includingmulti-strand PVC insulated unsheathed stranded copper cable as earth continuity conductor of size 2.5 Sq mm and connecting to geysers and all specified fittings etc completeall as specified and directed for following : -( colour code to be followed). |
4 | S&F in replacementof modular socket 6/16 Amps ,2/ 3 pin combined 2 module complete all as specified and directed. |
5 | S&F in replacement of modular switch 1 way 16 Amps, one module complete all as specified and directed. |
6 | S&F in replacement of modular white cover plate with frame for fixing of 3 modulecomplete all as specified and directed. |
7 | Taking downold unserviceable main switch/ DBs/ MCB DBs with MCB including making good the disturbed surface complete as directed. |
8 | S&F sheet metal enclosure for MCB’s distribution board, 240 Volts, 4 ways single pole and neutral including 200 Amps rated busbar, neutral link, din rail double door for breaking capacity 10 KAcomplete all as specified and directed. |
9 | S&F MCB single pole and neutral32Amps, ‘C’ series 240 Volts, breaking capacity 10KA complete all as specified and directed. |
10 | S&F MCB single pole 06 to 32Amps, ‘C’ series 240 Volts, breaking capacity 10KA complete all as specified and directed. |
11 | S&F in replacement of PVC Board (30 x 25 x 5) cm depth medium quality ISI marked complete all as directed. |
12 | Taking down old unserviceable sub main wiring of any size complete all as specified and directed. |
13 | M&L of sub main wiring with two single core 2.5 Sqmm PVC FRLS insulated unsheathed cable multi-stranded , unsheathed, copper conductor cables 1100 V grade drawn through & including PVC casing/caping of suitable size fixed to wall/ceiling etc including 2.5 sqmm (nominal area) single core, PVC insulated, multistranded,unsheathed, copper conductor cables green in colour as earth wire and duly connected to earth testpointas specified and directed by Engineer-in-Charge. (Note:- Two run of 2.5 sqmm and one run of 2.5 sqmm earth wire including PVC conduit should be measured & paid as one length) |
14 | Taking down old unserviceable service wire/cable including batten/suspending wires complete all as specified and directed. |
15 | M&L for Service wire PVC insulated and PVC sheathed stranded Aluminium conductor 10 sq mm 2 Core flat fixed to walls or suspended by insulating hanger not more than one meter apart including 4mm dia GI suspension wire and binding with 2mm dia new GI wire with reel insulator completeall as directed |
16 | S&F in repair plug top 16A, 240volts complete all as specified and directed. |
17 | S&F in repair plug top 6A, 240volts complete all as specified and directed. |
18 | Taking down and dismantling of ceiling/exhaust fan any sweep or size from ceiling rose complete all as directed.(Note : Repair / rewinding / over hauling works shall be measured and paid separately ) |
19 | M&L for rewinding of ceiling/exhaust/wall mounted/cabin/table fan with super copper winding wire of suitable size and providing with suitable insulation to fan including replacement of wornout nut,bolt, washers,spit pin, etc. re-assembling abd testing on completion complete all as specified and directed for the type of fans.(a) Ceiling fan of any Make 1200 mm to 1400 mm sweep |
20 | M&L for rewinding of ceiling/exhaust/wall mounted/cabin/table fan with super copper winding wire of suitable size and providing with suitable insulation to fan including replacement of wornout nut,bolt, washers,spit pin, etc. re-assembling abd testing on completion complete all as specified and directed for the type of fans. (b) Exhaust fan of any Make 300mm to 450 mm sweep. |
21 | Hanging only/ Refixing ceiling fan removed under item Srl No 17 here-in-above and connecting upincluding provision of cable from ceiling rose or connector to fan after cleaning of fan and blades & overhauling the fan complete all as specified and directed. |
22 | M&L for overhauling of ceiling/exhaust fan any make and sweep, cleaning internally and externally, oiling, greasing, checking of electric connections, reassembling and testing on completion complete all as specified and directed. |
23 | Supply following components of fan in replacement of unserviceable to the mechanic at the time of overhauling all as specified and directed by Engineer-in-charge:- (22.01)Ball bearing of suitable size for ceiling fan/Exhaust fan of any size and sweep. |
24 | (22.02)Condenser 2.5/3.15 Mfd for ceiling fan/exhaust fan of any size and sweep. |
25 | (22.03)Condenser 4 Mfd capacity 230 volts AC suitable for ceiling fan/exhaust fan |
26 | (22.04)MS Clamps with nut bolts and washers for hanging of ceiling fan of any size. |
27 | Taking down and dismantling of storage type water geysers of 50/25 ltrs capacity any type any make, any model, from its existing location, transportation to work shop forrepairs and transportation back and reinstallation of geyser as per technical instructions and as directed by engr-in-charge and including the following:- (a) Dismantling complete geyser and carrying out complete overhauling i.e; disconnecting electric supply and opening the heating plate, inner assembly, descaling complete assembly including heating element or otherwise. Replacement of defective heating element inlet and outlet tubes and refixing the assembly with gasket of good quality and tightening the nuts properly, reassembling geyser with all safety devices as specified in technical instructions and as directed by Engineer -in- Charge complete. Notes:- (i) Spare parts, safety devices with its required accessories shall be measured and paid seperately . |
28 | Supply only following spare parts of geysers 50/25 Ltrs capacity of make Bajaj/Havells/Usha/Venus/ or equivalent ISI marked .(27.01)Heating element 2 KW suitable for operation on 230V AC 50Hz |
29 | (27.02)Heating element 1.5KW suitable for operation on 230V AC 50Hz |
30 | (27.03)Thermostat 40 to 90 degree centigrade varying capactiy for 25/50 Ltrs capacity Geyser. |
31 | (27.04)Pressure release valve dead weight type for 25/ 50 Ltrs capacity Geyser. |
32 | S&F in replacement of 15 mm dia bore steel water tubing GI medium grade ISI marked with all fittings laid in trenches or fixed to wall etccomplete all as specified and directed. |
33 | S&F in replacement of bib taps cast copper alloy with crutch or butterfly handle screwed down screwed for iron pipe of 15 mm dia or brass ferrule and fixed complete all as specified and directed. |
34 | S&F in replacement ofPVC connections 15 mm size with PTMT nuts of length 450 mm long (Cold type) complete all as specified and directed. |
35 | S&F in replacement ofPVC connections 15 mm size with PTMT nuts of length 450 mm long(Hot type) complete all as specified and directed. |
36 | S&F in replacement of stop valves 15mm cast copper alloy screwed down high pressure with crutch or butterfly handle screwed botyh ends for iron pipe or for unions and fixed complete all as specified and directed. |
37 | S&F in replacement of PVC casing caping of size 25x15mm, of heavy grade including with all fitting accessories required at site complete all as specified and directed. |
38 | M&L for earthing complete with GI earth plate Electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth plate not less than2.25 Metre deep below ground level)with top edge of the plate not less than1.5 metrebelownormal ground levelconnected to galvanished earth wire4.0 mmdia bymeans ofbolts, nuts check and washers ofG I or steel all as shown in electrical plate No. 3 of SSR Pt -Iconnected to earthingtest point all as specified or indicated including GI pipe 15 mm dia light grade for earth wire protection, necessary excavation,earth work in any typeof soil, PCC chamberand RCC cover slab, connecting lead wire from test point to DB complete all as specified and as directed. |
39 | Disconnecting all electrical connections and taking down window type air conditioner of capacity 1.5/2 Ton, transporting to the nearest workshop for repairing including dismantling cleaning,replacement of necessary new spares/items, testing on load and back after repairs, re-installing in its original position, making all required connections and commissioning complete all as specified and directed. Note : (i) Spares parts will be measured separately (ii)The rate considered is inclusive of tools and plants required for carrying out the repairs.complete all as specified and as directed. |
40 | Disconnecting all electrical connections and taking down split type air conditioner of capacity 1.5/2 Ton, transporting to the nearest workshop for repairing including dismantling cleaning,replacement of necessary new spares/items, testing on load and back after repairs, re-installing in its original position, making all required connections and commissioning complete all as specified and directed. Note : (i) Spares parts will be measured separately(ii)The rate considered is inclusive of tools and plants required for carrying out the repairs.complete all as specified and as directed. |
41 | Disconnecting all electrical connections and taking down Refrigerator of any type and capacity or any make, transporting to the nearest workshop for repairing including dismantling cleaning,replacement of necessary new spares/items, testing on load and back after repairs, re-installing in its original position, making all required connections and commissioning complete all as specified and directed. Note : (i) Spares parts will be measured separately (ii)The rate considered is inclusive of tools and plants required for carrying out the repairs.)complete all as specified and as directed. |
42 | Disconnecting all electrical connections and taking down Deep freezer of any type and capacity or any make, transporting to the nearest workshop for repairing including dismantling cleaning,replacement of necessary new spares/items, testing on load and back after repairs, re-installing in its original position, making all required connections and commissioning complete all as specified and directed. Note : (i) Spares parts will be measured separately(ii)The rate considered is inclusive of tools and plants required for carrying out the repairs.)complete all as specified and as directed. |
43 | Supply only the following sparesparts /items of window/split type air conditioner of capacity 1.5/2 Ton complete all as specified and as directed.(Note: Make of spares parts/ items shall be of the same original manufacturer as existing) (42.01)Overload protection relay |
44 | (42.02)Thermostat |
45 | (42.03) Starting capacitor AC 230/415V, 40-60 MFD |
46 | (42.04)Copper capillary Tube of any size |
47 | (42.05) Front grill suitable for any type or capacity for window type AC |
48 | (42.06) Hermitically sealed compressor unit comprising of the compressor coupled with inbuilt AC single phase 230V motor and other standard compressor accessories complete for window type / split type air conditioner of 1.5 Ton capacity. (Make: Shriram / Kirloskar / Usha / Voltas / Godrej) |
49 | (42.07) Hermitically sealed compressor unit comprising of the compressor coupled with inbuilt AC single phase 230V motor and other standard compressor accessories complete for split type air conditioner of 2 Ton capacity. (Make: Usha / Voltas / Godrej). |
50 | (42.08) Blower motor suitable for any make/model/capacity with single shaft/double shaft. |
51 | (42.09) Plastic fan blade suitable for any make/model/ capacity for split type AC. |
52 | (42.10) Compressor mounting rubber set. |
53 | (42.11) Electronic circuit complete suitable for 1.5/2 Ton A/C (PCB) |
54 | (42.12)Cooling coil complete set |
55 | Supply only the following spares parts /items of refrigerator of 165/190/215/310 Ltr of capacity complete all as specified and as directed.(Note: Make of spares parts shall be of the same original manufacturer as per existing) :-(54.01)Box type relay |
56 | (54.02)Thermostat |
57 | (54.03)Drier 1/4 size |
58 | (54.04)Cooling coil |
59 | (54.05)Condenser |
60 | (54.06)Copper capillary Tube size of 1/4 inch outer dia |
61 | (54.07)Copper tubing of size 5/16 inch dia |
62 | (54.08) Magnetic door gasket |
63 | (54.09) Ice tray |
64 | (54.10) Vegetable tray |
65 | (54.11) Aluminium grill rack |
66 | (54.12) Pigmy lamp 15W |
67 | (54.13)Hermitically sealed compressor unit comprising of the compressor coupled with inbuilt AC single phase 230V motor and other standard compressor accessories complete for Refregerator 165/190 ltrs capacity. (Make:Shriram / Kirloskar / Usha / Voltas / Godrej). |
68 | (54.14)Hermitically sealed compressor unit comprising of the compressor coupled with inbuilt AC single phase 230V motor and other standard compressor accessories complete for Refregerator 215/310 ltrs capacity.( Make:Shriram/Kirloskar/Usha/Voltas/Godrej). |
69 | (54.15)Compressor mounting rubber set |
70 | Supply only the following spares/items of Deefrezer 170/298/410 Capacity complete all as specified and as directed.(Note: Make of spares parts shall be of the same original manufacturer as per existing) :-(69.01)Box type relay |
71 | (69.02)Thermostat |
72 | (69.03)Drier |
73 | (69.04)Cooling coil |
74 | (69.05)Condenser |
75 | (69.06)Copper capillary Tube size of 1/4 inch outer dia |
76 | (69.07)Copper tubing of size 5/16 inch dia |
77 | (69.08)Copper tubing of size 3/8 inch dia |
78 | (69.09) Magnetic top door gasket |
79 | (69.10)Hermitically sealed compressor unit comprising of the compressor coupled with inbuilt AC single phase 230V motor and other standard compressor accessories complete for deep freezer 170/298/410 ltrs capacity.( Make:Shriram/Kirloskar/Usha/Voltas/Godrej). |
80 | (69.11)Compressor grouting rubber set |
81 | M&L for flushing out refrigerant pipes, vacuuming the hermitically sealed compressor, charging of refrigerant (Floran-22) in adequate quantity, connecting suction and discharge lines and conducting leakage test for windows/split type air conditioner of 1.5/2 Ton capacity complete all as specified and directed by engr in charge. |
82 | M&L for flushing out refrigerant pipes, vacuuming the hermitically sealed compressor, charging of refrigerant (Gas 134A) in adequate quantity, connecting suction and discharge lines and conducting leakage test for any type/make/capacity of refrigerator complete all as specified and directed by engr in charge. |
83 | M&L for flushing out refrigerant pipes, vacuuming the hermitically sealed compressor, charging of refrigerant (Floran-600A) in adequate quantity, connecting suction and discharge lines and conducting leakage test for any type/capacity of Deep freezer complete all as specified and directed by engr in charge. |
84 | M&L for Shifting of window/split type A/C, any capacity, any make and re-installing in its original position, making all required connections and commissioning complete all as specified and directed by engr in charge |
85 | M&L for Shifting of Split type A/C , any type / any capacity, any make with necessary addition / alteration to window / wall complete all upto entire satisfaction complete all as specified and directed by engr in charge |
86 | Taking out the unserviceable blower motor from AC of any capacity and transporting to workshop for repair, dismantling & removing the burnt winding & rewinding it with samegauge, super enameled copper winding wire, varnishing, heating including replacement of minor hardwares and refixing& testing complete all as specified and directed by Engr-in-charge. |
87 | M&L for disconnecting of existing unserviceable voltage stablizer for repairs including replacement of relays,electronic voltage sensor circut and meter, micro switch, indicating light,RC filters and other connected items for making functional and rewinding of unserviceable transformer with super enameled copper wire of appropriate size, varnishing assembling and testing complete of capacity 1 KVA to 5 KVA upto satisfactory function of any capacity complete all as specified and directed. |
88 | S&F in replacement of plug top 15A, 240 volts, complete all as specified and directed. (Make: ISI marked product of Anchor/Havells/Legrand) |
89 | S&F in replacement plug top 5A, 240 volts, complete all as specified and directed. (Make: ISI marked product of Anchor/Havells/Legrand) |
90 | S&F in repair sheet metal enclosure with metal clad socket & plug top and MCB single pole neutral 32 Amps complete all as specified and directed. (Make: Havells / Indo Asian / HPL) |
91 | Material and labour for conducting ‘B’ check ofDG sets of various capacities installed at the followinglocations to carry out maintenance/servicing { forItem No. 90 to 94 } as given below all as directed:- (i) Change of diesel filter/oil filter,top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, Timer, Contactors ,Meters and others etc. (iii)Tightening of all nuts& bolts of DG set and its accessories. (iv)Check for any diesel lekage from any point and rectify if observed. (v) Check and adjust fan belt tension, replace the fan belts if found damaged. (vi)Check leakage of smoke from exhaust system/silencer,Repair if required. (vii) Check electrical connections of engine .The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order (viii)Check and tighten the AVM pads nuts and bolts,change AVM pads if found damaged.AVM to be provided by contractor. (ix)Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator ,if found OK adjust the same to specified values in case of brush type. (xi)Checking of all hoses and cleanup,change/tighten if required. (xii) Checking of all hoses and cleanup if required.Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (Note :- Spares/parts/ Engin oils/coolant /distilled water etc. will be measured and paid separately .) (a) DG Set 160 KVA capacity Make: Kirloskar at High LiftPump House |
92 | Material and labour for conducting ‘B’ check ofDG sets of various capacities installed at the followinglocations to carry out maintenance/servicing { forItem No. 90 to 94 } as given below all as directed:- (i) Change of diesel filter/oil filter,top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, Timer, Contactors ,Meters and others etc. (iii)Tightening of all nuts& bolts of DG set and its accessories. (iv)Check for any diesel lekage from any point and rectify if observed. (v) Check and adjust fan belt tension, replace the fan belts if found damaged. (vi)Check leakage of smoke from exhaust system/silencer,Repair if required. (vii) Check electrical connections of engine .The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order (viii)Check and tighten the AVM pads nuts and bolts,change AVM pads if found damaged.AVM to be provided by contractor. (ix)Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator ,if found OK adjust the same to specified values in case of brush type. (xi)Checking of all hoses and cleanup,change/tighten if required. (xii) Checking of all hoses and cleanup if required.Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (Note :- Spares/parts/ Engin oils/coolant /distilled water etc. will be measured and paid separately .) (a)DG Set 100 KVA capacity Make: Kirloskar at 183 MH & Signal Centre |
93 | Material and labour for conducting ‘B’ check ofDG sets of various capacities installed at the followinglocations to carry out maintenance/servicing { forItem No. 90 to 94 } as given below all as directed:- (i) Change of diesel filter/oil filter,top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, Timer, Contactors ,Meters and others etc. (iii)Tightening of all nuts& bolts of DG set and its accessories. (iv)Check for any diesel lekage from any point and rectify if observed. (v) Check and adjust fan belt tension, replace the fan belts if found damaged. (vi)Check leakage of smoke from exhaust system/silencer,Repair if required. (vii) Check electrical connections of engine .The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order (viii)Check and tighten the AVM pads nuts and bolts,change AVM pads if found damaged.AVM to be provided by contractor. (ix)Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator ,if found OK adjust the same to specified values in case of brush type. (xi)Checking of all hoses and cleanup,change/tighten if required. (xii) Checking of all hoses and cleanup if required.Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (Note :- Spares/parts/ Engin oils/coolant /distilled water etc. will be measured and paid separately .) (a)DG Set 62.5 KVA capacity Make: Kirloskar at KLP Pump House |
94 | Material and labour for conducting ‘B’ check ofDG sets of various capacities installed at the followinglocations to carry out maintenance/servicing { forItem No. 90 to 94 } as given below all as directed:- (i) Change of diesel filter/oil filter,top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, Timer, Contactors ,Meters and others etc. (iii)Tightening of all nuts& bolts of DG set and its accessories. (iv)Check for any diesel lekage from any point and rectify if observed. (v) Check and adjust fan belt tension, replace the fan belts if found damaged. (vi)Check leakage of smoke from exhaust system/silencer,Repair if required. (vii) Check electrical connections of engine .The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order (viii)Check and tighten the AVM pads nuts and bolts,change AVM pads if found damaged.AVM to be provided by contractor. (ix)Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator ,if found OK adjust the same to specified values in case of brush type. (xi)Checking of all hoses and cleanup,change/tighten if required. (xii) Checking of all hoses and cleanup if required.Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (Note :- Spares/parts/ Engin oils/coolant /distilled water etc. will be measured and paid separately .) (a)DG Set 45 KVA capacity Make: KirloskarMES Complaint Cell |
95 | Material and labour for conducting ‘B’ check ofDG sets of various capacities installed at the followinglocations to carry out maintenance/servicing { forItem No. 90 to 94 } as given below all as directed:- (i) Change of diesel filter/oil filter,top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, Timer, Contactors ,Meters and others etc. (iii)Tightening of all nuts& bolts of DG set and its accessories. (iv)Check for any diesel lekage from any point and rectify if observed. (v) Check and adjust fan belt tension, replace the fan belts if found damaged. (vi)Check leakage of smoke from exhaust system/silencer,Repair if required. (vii) Check electrical connections of engine .The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order (viii)Check and tighten the AVM pads nuts and bolts,change AVM pads if found damaged.AVM to be provided by contractor. (ix)Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator ,if found OK adjust the same to specified values in case of brush type. (xi)Checking of all hoses and cleanup,change/tighten if required. (xii) Checking of all hoses and cleanup if required.Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (Note :- Spares/parts/ Engin oils/coolant /distilled water etc. will be measured and paid separately .) (a)DG Set 30 KVA capacity Make: United Gensets at 27 R&O Flt |
96 | Supply only the following sparesparts/items for DG set capacity 30 KVA complete as specified and as ditected. (Make : Kirloskar)(Note: Make of spares parts shall be of the same original manufacturer as per existing) :- (95.01) Diesel fuel filter assembly (Pre filter & Micro filter) (Set of 02 Nos) |
97 | (95.02) Air filter assembly |
98 | (95.03) V" belt as per existing make/model |
99 | (95.04) Fuel pipe |
100 | (95.05) Radiator hose pipe with clamps for top and bottom |
101 | (95.06) Battery terminal leads copper with lugs |
102 | (95.07) Oil filter assembly |
103 | (95.08) Ignition switch |
104 | (95.09) Self Starter assembly of ISI Marked |
105 | Supply only the following sparesparts/items for DG set capacity 45 KVA complete as specified and as ditected. (Make : Kirloskar)(Note: Make of spares parts shall be of the same original manufacturer as per existing) :- (104.01) Diesel fuel filters assembly (Pre filter & Micro filter) (Set of 02 Nos) |
106 | (104.02) Air filter assembly |
107 | (104.03) V" belt as per existing make/model |
108 | (104.04) Fuel pipe |
109 | (104.05) Radiator hose pipe with clamps for top and bottom |
110 | (104.06) Battery terminal leads copper with lugs |
111 | (104.07) Self Starter assembly of ISI Marked |
112 | (104.08) Ignition switch |
113 | (104.09) Oil filter assembly |
114 | Supply only the following sparesparts/items for DG set capacity 62.5 KVA complete as specified and as ditected. (Make : Kirloskar)(Note: Make of spares parts shall be of the same original manufacturer as per existing) :- (113.01) Diesel fuel filters assembly (Pre filter & Micro filter) (Set of 02 Nos) |
115 | (113.02) Air filter assembly |
116 | (113.03) V" belt as per existing make/model |
117 | (113.04) Fuel pipe |
118 | (113.05) Radiator hose pipe with clamps for top and bottom |
119 | (113.06) Battery terminal leads copper with lugs |
120 | (113.07) Oil filter assembly |
121 | (113.08) Turbo filter assembly |
122 | (113.09)Inlet & Exhaust valve set of 06 Nos |
123 | (113.10) Packing kit |
124 | (113.11) Push rod set |
125 | (113.12) Oil pressure gauge |
126 | (113.13) Rubber coupling |
127 | (113.14) Nozzle |
128 | (113.15) Oil seal set |
129 | (113.16) Piston assembly with piston ring set |
130 | (113.17) Oil pump assembly |
131 | (113.18) Cylinder liner with JT ring |
132 | (113.19) Valve Guide assembly |
133 | (113.20) Valve seat assembly inlet |
134 | (113.21) Valve seat assembly exhaust |
135 | (113.22) Gasket set complete |
136 | (113.23) Set of various sizes nut bolt, washers for joints |
137 | (113.24)Valve collet |
138 | Supply only the following sparesparts/items for DG set capacity 100 KVA complete as specified and as ditected. (Make : Kirloskar)(Note: Make of spares parts shall be of the same original manufacturer as per existing) :- (137.01) Diesel fuel filters assembly (Pre filter & Micro filter) (Set of 02 Nos) |
139 | (137.02) Air filter assembly |
140 | (137.03) V" belt as per existing make/model |
141 | (137.04) Fuel pipe |
142 | (137.05) Radiator hose pipe with clamps for top and bottom |
143 | (137.06) Battery terminal leads copper with lugs |
144 | (137.07) Oil filter assembly |
145 | Supply only the following sparesparts/items for DG set capacity 160 KVA complete as specified and as ditected. (Make : Kirloskar)(Note: Make of spares parts shall be of the same original manufacturer as per existing) :- (144.01) Diesel fuel filters assembly (Pre filter & Micro filter) (Set of 02 Nos) |
146 | (144.02)Air filter assembly |
147 | (144.03) V" belt as per existing make/model |
148 | (144.04) Fuel pipe |
149 | (144.05) Radiator hose pipe with clamps for top and bottom |
150 | (144.06) Battery terminal leads copper with lugs |
151 | (144.07) Oil filter assembly |
152 | S&F in replacement of automotive battery 12V 150AH for DG Sets complete as specified and as ditected. (Make: Exide/Amaron/Amco) |
153 | Supply and filling radiator coolant in 5 Ltrs sealed pack complete as specified and as ditected. (Make: Shell/Castrol/Penzoil) |
154 | Supply and filling distilled water for battery/radiator complete as specified and as ditected. |
155 | Supply and filling engine oil 20 W 40 in 20 ltrs sealed Drums complete as specified and as ditected. (Make:Shell/Castrol/Penzoil). Note-: (i) Old Engine oil will be taken on charge by the Engr-in -charge |
156 | Material& Labour for taking out Radiator of DG set 30 KVA to 45 KVA for repair, welding, brazing, leak testing & refixing to DG set to its original position after cleaning of radiator with soda & acid including replacement ofclamps, fins, vibration pad with alignment of the base, nuts, bolts, packing materials and testing complete as specified and as ditected. |
157 | Material& Labour for taking out Radiator of DG set 62.5 KVA to 100 KVA for repair, welding, brazing, leak testing & refixing to DG set to its original position after cleaning of radiator with soda & acid including replacement of clamps, fins, vibration pad with alignment of the base, nuts, bolts, packing materials and testing complete as specified and as ditected. |
158 | Material& Labour for taking out Radiator of DG set100 to160 KVAfor repair, welding, brazing, leak testing & refixing to DG set to its original position after cleaning of radiator with soda & acid including replacement of hose pipes, clamps, fins, vibration pad with alignment of the base, nuts, bolts, packing materials and testing complete as specified and as ditected. |
159 | Taking out and disconnecting unserviceable self starter assembly of 100 to 160 KVA DG Set,after repair refixing the same in its original position complete as specified and as ditected. |
160 | The self starter assembly of 100 to 160 KVA DG Set, repairs/replacement of the following spares part / items complete as specified and as ditected.(Note: (i) Make of spares parts shall be of the same original manufacturer as per existing) :-Note:(ii) spares/parts replacement will be measured and paid separately. (159.01) supply only Armature |
161 | (159.02) supply only Field Coil |
162 | (159.03) supply only Starter Bearing |
163 | (159.04) supply only Bush |
164 | (159.05) supply only Carbon Brush |
165 | Taking down & opening of cylinder head of 100KVA DG Set and replacement of new piston ring, inlet valves, exhaust valves, oil seal, cylinder gasket and refixing the same in its original position complete all as specified and directed. |
166 | S&F in replacement of aluminium cable lugs for cable size 35 Sqmm complete all as specified and directed |
167 | S&F in replacement of aluminium cable lugs for cable size 50 Sqmm complete all as specified and directed |
168 | S&F in replacement of aluminium cable lugs for cable size 70 Sqmm complete all as specified and directed |
169 | S&F in replacement of aluminium cable lugs for cable size 120 Sqmm complete all as specified and directed |
170 | S&F in replacement of MCCB 4 pole, 415 V, adjustable thermal & fixed magnetic setting type 63 to 100 Amp with breaking capacity 25KA complete all as specified anddirected. (Make: Havells/ L&T/Legrand/Siemens/ABB) |
171 | S&F in replacement of MCCB 4 pole, 415 V, adjustable thermal & fixed magnetic setting type 160 Amp with breaking capacity 25KA complete all as specified anddirected. (Make: Havells/ L&T/Legrand/Siemens/ABB) |
172 | S&F in replacement of MCCB 4 pole, 415 V, adjustable thermal & fixed magnetic setting type 200 Amp with breaking capacity 25KA complete all as specified anddirected. (Make: Havells/ L&T/Legrand/Siemens/ABB) |
173 | S&F in replacement of On Load changeover switch in sheet metal enclosure with front operating handle, 4 pole, 415V, current rating 63 Amps complete all as specified and directed. (Make: Indoasian / L&T/Legrand/) |
174 | S&F in replacement of On Load changeover switch in sheet metal enclosure with front operating handle, 4 pole, 415V, current rating 100 Amps complete all as specified and directed. (Make: Indoasian / L&T/Legrand/) |
175 | S&F in replacement of On Load changeover switch in sheet metal enclosure with front operating handle, 4 pole, 415V, current rating 160 Amps complete all as specified and directed. (Make: Indoasian / L&T/Legrand/) |
176 | S&F in replacement of On Load changeover switch in sheet metal enclosure with front operating handle, 4 pole, 415V, current rating 200 Amps complete all as specified and directed. (Make: Indoasian / L&T/Legrand/) |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail