Tender For Repair And Maint To Capacitor Bank And Misc Works At Dholewal, Doraha, Cg Complex, Phillaur, Baddowal And Moga Under Ge Ludhiana
Tender Value
10 Lakhs
Estimated cost
Bid Submission
01 Mar 2024
0 days left
EMD
20000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
doraha → Punjab
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Repair And Maint To Capacitor Bank And Misc Works At Dholewal, Doraha, Cg Complex, Phillaur, Baddowal And Moga Under Ge Ludhiana
BOQ
| Sl. No. | Item Description |
| 1 | Sch \"A\" |
| 2 | Supply & fixingin replacement current transformer CT 25/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed. |
| 3 | Supply & fixingin replacement current transformer CT 50/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed. |
| 4 | Supply & fixingin replacement current transformer CT 75/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed . |
| 5 | Supply & fixingin replacement power factorcontroller relay latest micro controller based tech with true RMS sensing alarm available , delay adjustment , LCD display range 08 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified and as directed. |
| 6 | Supply & fixingin replacement power factorcontroller relay latest micro controller based tech with true RMS sensing alarm available , delay adjustment , LCD display range 12 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified and as directed. |
| 7 | Supply & fixingin replacementheavy duty cylindrical capacitor 1 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 8 | Supply & fixingin replacementheavy duty cylindrical capacitor 3 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 9 | Supply & fixingin replacementheavy duty cylindrical capacitor 5 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 10 | Supply & fixingin replacement heavy duty cylindrical capacitor 10 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 11 | Supply & fixingin replacement heavy duty cylindrical capacitor 15 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 12 | Supply & fixing in replacement heavy duty cylindrical capacitor 20 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 13 | Supply and fix in replacement capacitor duty contactor3P,AC3 , 12 amp (2NO, 2NC) of suitable up to 5 KVAR APFC panel ratings for APFCPanels complete all as specified and as directed. |
| 14 | Supply and fix in replacement capacitor duty contactor 3P,AC3 , 20 amp (2NO, 2NC) of suitable up to 10 KVAR APFC panel ratings for APFCPanels complete all as specified and as directed. |
| 15 | Supply and fix in replacement capacitor duty contactor 3P,AC3 , 32 amp (2NO, 2NC) of suitable up to 15 KVAR APFC panel ratings for APFCPanels complete all as specified and as directed. |
| 16 | Supply and fix in replacement capacitor duty contactor 3P,AC3 , 40 amp (2NO, 2NC) of suitable up to 20 KVAR APFC panel ratings for APFCPanels complete all as specified and as directed. |
| 17 | Supply and Fixingin replacement 4 Pole MCCB 63 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and as directed. |
| 18 | Supply and Fixingin replacement 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and as directed. |
| 19 | Supply and Fixingin replacement 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed by Engr-in-charge |
| 20 | Supply and Fixingin replacement 4 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed by Engr-in-charge |
| 21 | Supply and Fixingin replacement 4 Pole MCCB 250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed. |
| 22 | Supply and Fixingin replacement C Curve 3 Pole MCB 32 TO 63 Amp, 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and as directed. |
| 23 | Supply and fix in replacement wiring complete 6.0 Sqmm single core PVC insulated FR LS cable 1100 volts grade multistranded copper conductor cable with multistranded copper conductor cable as earth continuity conductor,all as specified and as directed . |
| 24 | Supply & fixing in replacement panel mounted voltmeter three phase incl with CTs/ PT ratio 4 digit display , class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and as directed. |
| 25 | Supply & fixingin replacement panel mounted Ammeter three phaseincl withCTs/ PT ratio 4 digit display, class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and as directed |
| 26 | Material and labour in replacement of indicator lamp in red, yellow and blue colour with lamp holder multi LED type complete including wiring with copper conductor cable of suitable size all as specified . |
| 27 | Material and labour in replacement of selector switch complete including wiring with copper conductor cable of suitable size all as specified . |
| 28 | M&L for painting of panel board inner & outer completewith synthetic enamel paint by spraying including filling cavaties with filler one coat after cleaning all dust/rust including writing the Distribution/Panel Numberand panel details all as directed .. Note: The Quoted rates are inclusive of white wash to fountation of Panel Board/ Painting to Angle Frames complete |
| 29 | Supplying and laying synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006,(supersending IS 5424) suitable for electrical shock safety of size 2mx1 m all as specified |
| 30 | Supplying and laying synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006,(supersending IS 5424) suitable for electrical shock safety of size 2mx1 m all as specified |
| 31 | Supply & fixingin replacement current transformer CT 400/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed. |
| 32 | Supply & fixingin replacement current transformer CT 160/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed. |
| 33 | Supply & fixingin replacement current transformer CT 100/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and as directed . |
| 34 | Supply & fixing heavy duty cylindrical capacitor 25 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed. |
| 35 | Supply and Fixingin replacement 3 Pole MCCB 63 TO 100 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and as directed. |
| 36 | Supply and Fixingin replacement 3 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed by Engr-in-charge. |
| 37 | Supply and Fixingin replacement 3 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed. |
| 38 | Supply and Fixingin replacement 3 Pole MCCB 400 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and as directed. |
| 39 | Supply and Fixing C Curve TPN MCB 16 to 32 Amp, 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and as directed by Engr-in-charge |
| 40 | Supply and Fixing C Curve TPN MCB 40 to 100 Amp, 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and as directed by Engr-in-charge |
| 41 | Supply & fix PVC exhaust fans (8\") AC single phase 150 mm sweep with louver all as specified. |
AI Tender Summary
Tender Timeline
Feb 10, 2024
11:30 IST
Tender Published
Tender notice published.
CompletedMar 01, 2024
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedMar 04, 2024
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender