Tender For Special Repair/ Replacement Of Acsr Conductor With Ug Cable, Electric Distribution Panel And Allied Works, Provn Of Flood Lights, Cooling Appliances, 01 X 10 Kva Ups With Batteries And 1 X Ro Plant With A Capacity Of 500 Ltr Filteration Per
Tender Overview
Project Description
Tender For Special Repair/ Replacement Of Acsr Conductor With Ug Cable, Electric Distribution Panel And Allied Works, Provn Of Flood Lights, Cooling Appliances, 01 X 10 Kva Ups With Batteries And 1 X Ro Plant With A Capacity Of 500 Ltr Filteration Per
BOQ
| Sl. No. | Item Description |
| 1 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 185 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 2 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 3 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 4 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 5 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 35 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 6 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 16 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 7 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 8 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 2 core, nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 9 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. |
| 10 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 11 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 12 | Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point |
| 13 | Supply & spreading in trenches sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly. |
| 14 | M & L for laying of bricks locally available sub class \"B\" bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed. |
| 15 | Supplying & laying in trenches 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 16 | Supplying & laying in repair in trenches 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 17 | Supply and fix time switch digital type 415 volt three phase of 65 amps rating with contactor fitted inside and MCB TPN 63A,Max load of 6KW within steel enclosure complete including connecting items complete all as specified and directed.Make-Havells /Philips or equivalent make given in APPX B |
| 18 | Supply installation, commissioning and testing including providing all necessary electrical connection, LT Junction box, outdoor type CPRI approvedfactory made out of3.15 mm thick MS sheet of size 0.60mx 0.60 mx 0.60 m deep having hinge opening arrangement in front and back side and bottom frame made out of angle iron of size 50x50x6mm thick and 04 Nos legs 0.5 meter length with cable entry and exit circular hole with cable gland & gasket at bottom including painting to all internal and external exposed steel surfaces with powder coating paint (5 stage process) with duly fixed in ground with necessary PCC foundation (1:2:4) type B1, with danger notice plate, street light panel of 1.6mm thick mild steel sheet, vitereous enamelled (white), with letters, figures and conventional skull and bones in signal red colour, fixing lugs, bolts, screws etc and comprising of the following accessories including taking down Old unserviceable box:-(a) Copper bus bar of size 25 x 2.5 mm suitable for 200 Amp 0.5 mtr long fixing on suitable capacity and size insulators ---04 nos complete all as directed by the Engr-in-Charge |
| 19 | Supply installation, commissioning and testing including providing all necessary electrical connection, LT Junction box, outdoor type CPRI approvedfactory made out of3.15 mm thick MS sheet of size 0.60mx 0.60 mx 0.60 m deep having hinge opening arrangement in front and back side and bottom frame made out of angle iron of size 50x50x6mm thick and 04 Nos legs 0.5 meter length with cable entry and exit circular hole with cable gland & gasket at bottom including painting to all internal and external exposed steel surfaces with powder coating paint (5 stage process) with duly fixed in ground with necessary PCC foundation (1:2:4) type B1, with danger notice plate, street light panel of 1.6mm thick mild steel sheet, vitereous enamelled (white), with letters, figures and conventional skull and bones in signal red colour, fixing lugs, bolts, screws etc and comprising of the following accessories including taking down Old unserviceable box:-(a) Copper bus bar of size 40 x 5mm suitable for 400 Amp 0.5 mtr long fixing on suitable capacity and size insulators ---04 nos complete all as directed by the Engr-in-Charge |
| 20 | Supply installation, commissioning and testing including providing all necessary electrical connection, LT feeder panel board of size 1.5x1.0x0.5 m Outdoor type double door, CPRI approved, factory made powder coated out of 3.15 mm thick MS sheethaving hinge opening arrangement in front and back side and bottom frame made out of angle of size 50 x 50 x 6mm thick and 04 Nos legs 0.6 meter length with cable entry and exist circular hole with cable gland & gasket at bottom complete including painting to all internal and external exposed steel surfaces with power coating paint ( 5 stage process) with duly fixed in ground with necessary PC foundation (1:2:4) type B1, with danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled (white), with letters, figures and conventional skull and bones in signal red colour, fixing lugs/glands for incoming and out going cables , bolts , screws ete complete all as specified and directed by Engr-in-charge and comprising of the following accessories.(Note : All the internal connection connectedthrough 50 x 2.5mm of copper bus bar)..(a) Copper bus bar of suitable size for 400 Amp (TPN) including insulator.(b) 315 Amp, 4 Pole MCCB , 50 Hz ,415 V with rupturing capacity 50 KA - 01 No. (In coming).(c) Indicator lamp LED type (set of three Red,Yellow,Blue)----01 Nos.(d)Digital Multifunction meter, Model C, class 1, with relay - 01 No. Make AE/L&T/ABB/HPL.(e) 63 Amp, 4 Pole MCCB , 50 Hz ,415 V with rupturing capacity 36 KA - 06 No complete all as directed by the Engr-in-Charge |
| 21 | Supply installation, commissioning and testing including providing all necessary electrical connection, LT feeder panel board of size 1.5x1.0x0.5 m Outdoor type double door, CPRI approved, factory made powder coated out of 3.15 mm thick MS sheethaving hinge opening arrangement in front and back side and bottom frame made out of angle of size 50 x 50 x 6mm thick and 04 Nos legs 0.6 meter length with cable entry and exist circular hole with cable gland & gasket at bottom complete including painting to all internal and external exposed steel surfaces with power coating paint ( 5 stage process) with duly fixed in ground with necessary PC foundation (1:2:4) type B1, with danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled (white), with letters, figures and conventional skull and bones in signal red colour, fixing lugs/glands for incoming and out going cables , bolts , screws ete complete all as specified and directed by Engr-in-charge and comprising of the following accessories.(Note : All the internal connection connectedthrough 50 x 2.5mm of copper bus bar)..(a) Copper bus bar of suitable size for 400 Amp (TPN) including insulator.(b) 250 Amp, 4 Pole MCCB , 50 Hz ,415 V with rupturing capacity 50 KA - 01 No. (In coming).(c) Indicator lamp LED type (set of three Red,Yellow,Blue)----01 Nos.(d)Digital Multifunction meter, Model C, class 1, with relay - 01 No. Make AE/L&T/ABB/HPL.(e) 63 Amp, 4 Pole MCCB , 50 Hz ,415 V with rupturing capacity 36 KA - 05 No complete all as directed by the Engr-in-Charge |
| 22 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1500 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 160 Amps, 4 pole, 50 kA, 415 Volt- 02 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 30 x 5 mm with capacity 200 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(e) Change over switch 160 Amp - 01 No(ii) Out going(a) MCCB, 100Amps, 4 pole, 36 kA, 415 Volts-04 Nos (with thermal magnetic release)(b) MCCB, 32 Amps, 3 pole, 25 kA, 415 Volts-01 Nosduly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 23 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1700 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 320 Amps, 4 pole, 50 kA, 415 Volt- 02 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 40 x 5 mm with capacity 400 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(e) Change over switch 400 Amp - 01 No(ii) Out going(a) MCCB, 250Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release)(b) MCCB, 160Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(c) MCCB, 100Amps, 4 pole, 36 kA, 415 Volts-01 Nosduly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 24 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1500 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 250 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 30 x 5 mm with capacity 300 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 200Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release)(b) MCCB, 100Amps, 4 pole, 36 kA, 415 Volts-04 Nos (with thermal magnetic release)(c) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-07 Nosduly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 25 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1200 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 100 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 25 x 5 mm with capacity 200 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(b) MCCB, 40 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(c) MCCB, 32 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release) (d) MCB, 32 Amps, 2 pole, 415 Volts-04 Nos (with thermal magnetic release)as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 26 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1700 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 250 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 30 x 5 mm with capacity 300 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 250 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(b) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release)(c) MCCB, 40 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release) (d) MCB, 40 Amps, TPN, 415 Volts-02Nos (e) MCB, 32 Amps, TPN, 415 Volts-01Nos (with thermal magnetic release)as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 27 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1500 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 160 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 25 x 5 mm with capacity 300 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-03 Nos (with thermal magnetic release)(d) MCB, 40 Amps, TPN, 415 Volts-03 Nos (e) MCB, 32 Amps, TPN, 415 Volts-03 Nos (with thermal magnetic release)as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 28 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1200 mm X 1000 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 63 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 30 x 6 mm with capacity 100 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 40 Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release)(d) MCB, 40 Amps, SPN, 415 Volts-02 Nos (with thermal magnetic release)as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 29 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1700 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 250 Amps, 4 pole, 50 kA, 415 Volt- 02 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 30 x 5 mm with capacity 300 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(e) Change over switch 250 Amp - 01 No(ii) Out going(a) MCCB, 160 Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release)(b) MCCB, 100 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(c) MCCB,63 Amps,4 pole, 36 kA, 415 Volts-03 Nos (with thermal magnetic release)as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 30 | Supply , installation, commissioning and testing of indoor type, LT panel board of size 1500 mm X 1700 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 400 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 40 x 10 mm with capacity 450 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 250 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(b) MCCB, 100 Amps, 4 pole, 36 kA, 415 Volts-03 Nos (with thermal magnetic release)(c) MCCB,80 Amps,4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(d) MCCB, 32Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release)(e) MCB, 40 Amps, TPN, 415 Volts-02 Nos (c) MCB,32 Amps,SPN,415 Volts-02 Nos as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 31 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1700 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB, 400 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 40 x 10 mm with capacity 450 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 200 Amps, 4 pole, 36 kA, 415 Volts-03 Nos (with thermal magnetic release)(b) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-01 Nos (with thermal magnetic release) as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 32 | Supply , installation, commissioning and testing of outdoor type, LT panel board of size 1500 mm X 1200 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB,250 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size30 x 5 mm with capacity 300 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 100 Amps, 4 pole, 36 kA, 415 Volts-02 Nos (with thermal magnetic release) as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 33 | Supply , installation, commissioning and testing of indoor type, LT panel board of size 1500 mm X 1200 mm X 500 mm, CPRI approved factory made, double door, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15mm thick CRCA sheet with using 50 mm X 50 mm X 6 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable / openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs andalike complete including fixing of undermentioned MCBs and alike as under: -(i) Incoming: -(a) MCCB,200 Amps, 4 pole, 50 kA, 415 Volt- 01 No(with thermal magnetic release)(b) Change over switch 200 Amp - 01 No(c) LED Indicator lamp RYB - 01 (set of three)(d) Digital multifuction meter with relay model C class 1- 01 nos(e) Copper bus bar of size 25 x 5 mm with capacity 250 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 63 Amps, 4 pole, 36 kA, 415 Volts-03 Nos (with thermal magnetic release) (b) MCB, 40 Amps, TPN, 415 Volts-01 Nos as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 34 | Supply, installation, testing and commissioning in replacement of outdoor LT panel front and back openable, lockable/ openable lay keys totally enclosed ( but not less than 1.5m x 1.5m x 0.4m) weather and vermin proof, suitable ventilated, 440 volts, 50 HZ, AC supply, facctory made out of 3mm thick CRCA sheet steel for load bearing and 2mm thick for non load bearing portions, protection of enclosure IP-54 complete with pretreatment and powder coating of approved colour including suitable angle iron/ flat iron frame work supports, excavation and earthwork, PCC foundation etc necessary electric connections with existing cable with new double compressed cable glands of required size cables, cubical type as required with and including the following.(i) Incoming: -(a) MCCB,320 Amps, 4 pole, 36 kA, 415 Volt- 01 No(with thermal magnetic fixed type)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 40 x 5 mm with capacity 400 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 250 Amps, 4 pole, 25 kA, 415 Volts-01 Nos (with thermal magnetic fixed type) (b) MCCB, 200 Amps, 4 pole, 25 kA, 415 Volts-01 Nos (with thermal magnetic fixed type)(c) MCCB, 160 Amps, 4 pole, 25 kA, 415 Volts-01 Nos (with thermal magnetic fixed type)(d) MCCB, 100 Amps, 4 pole, 16 kA, 415 Volts-01 Nos (with thermal magnetic fixed type) as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 35 | Supply, installation, testing and commissioning in replacement of outdoor LT panel front and back openable, lockable/ openable lay keys totally enclosed ( but not less than 1.5m x 1.5m x 0.4m) weather and vermin proof, suitable ventilated, 440 volts, 50 HZ, AC supply, facctory made out of 3mm thick CRCA sheet steel for load bearing and 2mm thick for non load bearing portions, protection of enclosure IP-54 complete with pretreatment and powder coating of approved colour including suitable angle iron/ flat iron frame work supports, excavation and earthwork, PCC foundation etc necessary electric connections with existing cable with new double compressed cable glands of required size cables, cubical type as required with and including the following.(i) Incoming: -(a) MCCB,400 Amps, 4 pole, 36 kA, 415 Volt- 01 No(with thermal magnetic fixed type)(b) LED Indicator lamp RYB - 01 (set of three)(c) Digital multifuction meter with relay model C class 1- 01 nos(d) Copper bus bar of size 40 x 5 mm with capacity 400 Amps PVC insulated in step way for 3 phase 4 strip system fixed on hygroscopic base insulator(ii) Out going(a) MCCB, 200 Amps, 4 pole, 25 kA, 415 Volts-01 Nos (with thermal magnetic fixed type)(b) MCCB, 160 Amps, 4 pole, 16 kA, 415 Volts-01 Nos (with thermal magnetic fixed type)(c) MCCB, 100 Amps, 4 pole, 16 kA, 415 Volts-01 Nos (with thermal magnetic fixed type) as outgoing feeder duly prewired with appropriate size of copper bus bar thimbled ( for accomodating outgoing cable connection ) suitable size busbar chamber in order to accommodate all accessories with proper insulation with inlet and outlet cable provisions(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |
| 36 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through outdoor type joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½core XLPE,armoured, Al conductor cable of size 120 to 150 sqmm, Outdoor typecomplete all as specified and directed |
| 37 | M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 38 | M & L for cement concrete M15 (Nominal Mix) using 40 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed by Engineer-in-charge. |
| 39 | M&L for cutting the road /hard standing and making good disturbed surface by using PCC type C2 (1:3:6) by using 20 mm graded stone aggregate for the fixing the pipe complete all as directed by Engrr-In-Charge. |
| 40 | M & L for boring under road, pavement, hard standing by trenchless technology using latest boring technique/ or by mechanical means for insertion of GI/CI/PP-R/PVC pipe/cable of any dia/ bore/size complete all as specified and as directed. Note- Pipes shall be measured and paid separtely. |
| 41 | Supplying & laying, repair, in trenches 25 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 42 | Supplying & laying, in repair, in trenches 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 43 | S&F in repairs modular junction box made of SMC/FRPof size 240x130x110mm with provision of MCB SP, and connector terminal 4 pole indicating RYB Phase Colour and Neutralcolour complete fixedto street light pole with suitable sizeofmild steel/ flat iron clamps, nuts and bolts complete all as specified and as directed. |
| 44 | M&L for PVC insulated three core 1.5 sqmm multi strand copper conductor for connection of security light from Junction Boxto security light with including PVC Conduit medium class which is inclusive in the quoted rate complete all as specefied and as directed. |
| 45 | Taking down of old unsv over head line including ACSR conductor(R,Y,B, N and Earthing-05 Nos complete) ,insulator,Stay,cross arms etc.of any size and any capacity complete all asspecified and directed. |
| 46 | M & L for steel tubular swaged pole 410 SP-31 (9.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed. |
| 47 | S & F LED street lights nominal power 90 Watt LED, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 70%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with polyster powder coated, life span of minimum 50000 working hours of Make including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed. |
| 48 | Disconnecting & Taking down/out unserviceable LT Cable/Service wire of any size and any description from trenches, floors, walls, GI Pipes, etc including serviceable cables, bricks etc keep in safe custody for re-use complete all as specified and as directed. NOTE : Nesessary earth works will be measured & paid seperately under appropriate items. |
| 49 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through outdoor type joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4core XLPE,armoured, Al conductor cable of size 25 to 50 sqmm, Outdoor typecomplete all as specified and directed |
| 50 | M & L for concealed point wiring for one 3 pin/ 5 pin 6 Amps socket outlet on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC pipe of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 51 | M & L for concealed point wiring for one 3 pin/ 5 pin 15 Amps socket outlet on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 2.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC pipe of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 52 | S & F switch socket combination with (3 pin and 2 pin) combined socket outlets, 6A, 240 V, AC, 50 Hz with earthing contact, rewirable, pillar type terminal, normal protection, unenclosed, without Shutter, Flush type, Design B and switch, 6 A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. |
| 53 | S & F sheet metal enclosure with socket plug top and MCB single pole and neutral enclosure with two pin & earth plug and socket complete with MCB SP 20 Amps 240 volts complete all as specified and as directed. |
| 54 | Supplying, installing, testing and commissioning water cooler partially stainless steel having approximate storage and nominal cooling capacity of 80 litres and 40 litres per hour, using non CFC refrigerant suitable for single phase 230 volts complete all as specified and as directed. |
| 55 | Supplying, installing, testing and commissioning BEE five star rated refrigerator of capacity 300 to 310 litres suitable for single phase 230 volts complete all as specified and as directed. |
| 56 | Supply and installed deep freezer hard top 320 litre capacity having single door with Aluminium inner liner for Improved hygiene, UV grade plastic material for long lasting appearance; Temperature Range: <-18°C ; Castor Wheels for Easy Transportation ; Power Features: AC 230 V/50 Hz, Inside Cladding / liner: Aluminum/PCM complete all as Specified and directed. (Make : Voltas, Blue star,LG,Panasonic/Godrej/Samsung/ equivalent make given in Appx B) |
| 57 | Supply & fixing voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 130V to 280V with output voltage stabilizer at 230 with accuracy ± 2.5% and capacity 2.0 KVA complete all as specified and as directed. |
| 58 | Supply & fixing voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 130V to 280V with output voltage stabilizer at 230 with accuracy ± 2.5% and capacity 5.0 KVA complete all as specified and as directed. |
| 59 | Supply and fix of 3 Ph/ 3Ph 10 KVA UPS PF-1 true online IGBT based invertor and IGBT based rectifier 240 volt DC phase sequence corrector, three phase of capacity 10 KVA complete with MS rack, interlink cables of suitable size complete all as specified and directed. |
| 60 | Supply and fixing 12 V SMF 34AH battery 20 Nos for minimum 30 Minute backup with MS stand and interconnection cables complete all as specified and directed. |
| 61 | Supply and fix sub main wiring complete with and including four Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 6 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including medium mechanical stresses class PVC conduit as per IS 9537 (Part-III): 1983 of suitable nominal size as required at site dia but not less than 20 mm nominal size including all accessories and fixed on walls and 6 sqmm two Nos single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Four runs of 6 sqmm cable, two runs of6 sqmm cable and one run of conduit shall be measured and paid as one unit length. |
| 62 | S & F double door MCB Distribution board of sheet metal enclosure, single pole and neutral, 4 way with 200 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 63 | Supply, installation, testing and commissioning of LED floodlight with pressure diecast aluminium housing and high efficiency glass cover having system wattage 200 W, lumen output more than 22000 lumens, colour rendering index (CRI) greater than 70, colour temperature (CCT) equals to 5700° K ± 300°K, power factor more than 0.95, THD less than 10%, driver efficiency more than 85%, beam angle equals to 25°, lumen efficacy more than 110 lumen per watt, life equals to 50000 hours as per L70, protection class equals to or greater than IP66, surge protection 5kV (internal) /10kV (external) including necessary connecting materials as per Product Name turbo, product code 169783, catalogue reference BARFEG 200W of Bajaj or equivalent of Make mentioned under Appendix \"B\" complete all as specified and as directed. (Note:- The contractor shall provide LM80 and LM79 test reports from NABL accredited LAB before supplying the luminaires.) |
| 64 | S & F pole mounted decorative LED post top with IP-65 protection as per Bajaj luminaire type BLPTSP 25W WH LED, product code 111741 or equivalent of Philips or Crompton Greaves including necessary wirings and testing commissioning complete all as specified and as directed. |
| 65 | S & F new 18/20 watt surface and wall mounted LED batten with polycarbonate housing and integrated driver complete all as specified and as directed (Make : Havells Cat No. LUMILINEBS18WLED865SPCWH or equivalent make) |
| 66 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 20 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. |
| 67 | S & F double door MCB Distribution board of sheet metal enclosure, triple pole and neutral, 4 way with 200 Amps rated bus bar, 415 volt, IP42 protection grade and fixed with MS hold fast and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 68 | S&F MCB 40 to 100 Amp TPN \"B\" Series 50 Hz 10KA 240 Volt and connection complete all as specified and as directed. |
| 69 | S&F MCB SP, 10KA, 230V, C-curve, 6-32 amps complete all as specified and as directed. |
| 70 | M & L for concealed point wiring for one light or one fan or one exhaust fan or bell point controlled by one switch complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC pipe of suitable size as required as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 71 | S & F switch, 6A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. |
| 72 | S & F switch socket combination with (3 pin and 3 pin) having two earthing pins combined socket outlets, 6A & 16A, 240 V, AC, 50 Hz with earthing contact, rewirable, pillar type terminal, normal protection, unenclosed, without Shutter, Flush type, Design B and switch, 16 A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A and indicator and fuse complete all as specified and as directed. |
| 73 | M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 74 | Preparation of newly or previously untreated steel surface of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed by Engineer-in-Charge |
| 75 | S and F roof plates with sleeve pieces riveted or welded thereto, and similar roof and ceiling connections complete all as specified and and directed |
| 76 | S & F for steel work of grade-3 as per IS 10748 in tubular trusses including special shaped washer etc. complete using ERW or HRIW welded tubes conforming to IS 1161: 2014 (Yst 240 Grade) complete all as specified and directed. |
| 77 | M & L for pre-painted hot-dip aluminium-zinc alloy metallic coated corrugated steel sheet, any pattern corresponding to IS 15965:2012 of durability class 3, atmospheric classification category 3, coating class AZ150, 0.50 mm thick, of an approved colour and having yield strength of 550 MPa as in roof covering/ wall clading fixed with self tapping screws as specified including necessary scaffolding and safety measures at any floor complete all as specified and as directed. |
| 78 | M & L for hardcore (broken stone or boulders) of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed. |
| 79 | M & L for cement concrete M15 (Nominal Mix) using 40 mm nominal size graded crushed stone aggregate 100 mm thick in flooring finished even and smooth without using extra cement complete all as specified and as directed. |
| 80 | Supply fixing testing and commissioning of fully automatic 01 x RO plant 500 lPH comprising of following:RO Treated water Quality : Temperature <30 deg /c,PH - 7.0 -8.0ppm,Colour - Nil, Turbidity - Nil,Total Suspended Solids - Nil,Total Alkanity <50ppm,Total Hardness <50ppm,Total Dissolved Solids <100ppm Ecoli - Nil1)Filter Feed Pump -1no of capacityMin 1500 LPH2) Multi Grade Filter - 1no for removing TSS and turbidityVessel Dia: 325mm (Min) Vessel height :1300mm (Min)Filter capacity : 1000 to 3000 lph, Valve Type : Auto SM MPVMedia Qty 200kg, Media Depth 900mmMedia Type Gravels ,Treated Sand,Anthracite(3) Activated Carbon Filter : 01 No Function : Remove order,colourVessel Dia : 325mm (Min), Vessel Height : 1300mm (Min)Filter Capacity Min &Max 1000 LPH to 3000lphValve Type Auto SM/ MPVMedia Quantity : 200 kg, Media Depth : 900mmMedia type : Gravels, Activated Carbon IV9003)SMBS /PH Dosing System -1no Function : Take care of RO Membrane& increasemembrane life, MOC : PVC /PP, Capacity : Min 4LPH, Dosing Tank Capacity Min 100 Ltrs4)AntiScalant Dosing System -1no,Function : Scaling Resistance for membrane &Increase membrane life, Capacity 4LPH Min, Type Electronic DiaphrameS/D Tube LDPE Tube, Dosing Tank Capacity 100 Ltrs Min, MOC of Tank HDPE5)Micron Catridge Filter -1no, Housing Size 100mm Min , Max flow Rate 3000LPHHousing Bowl Head MOC : UPVC /PVC /PP, Suitable Cartidge : 1 no of standardCartidge Type : Double open end, Filtration Rating : 5 microsemens |
| 81 | Contd/--- Item No 80 :- (6)Reverse Osmosis System -1no Function : Remove TDS and E.Coli Capacity : 500LPH, High Pressure Housing size : 4”Number of Elements : 2 Nos, Elements size : 4040Stabilized Salt Rejection : 95 to 99.5%, Feed Water Max TDS : 2500 PPMHigh Pressure pump ofcapacity 2000LPH(Min)High Pressure pump HP/RPM : 2/2900, Volt / Phase 420/3,RO Control Panel Auto logicDischarge Pipe- SS, High Pressure pipe - SS, Inter conecting P/W - CPVC,Low /High Pressure Switch DanfosPressure Switch Type : InLineOpertaing Pressure Low 0-5 .High 5-10kg/cm27)UV System -1no of Capacity 500 lph 8) SS RO Water Storage tank -1no of capacity 1000 Ltrs9)CIP Cleaning System - 1no, Function Cleaning&Sanitization for membraneCleaning Pump Capacity : 2000LPH(Min) Pressure 3 -4 MWCChemical Storage Tank : 200LTRStorage Tank : MOC HDPE, Quantity : 1No, Micron CartidgeFilter 1NoMCF MOC : PVC /PP, Cartidge Type : Spun /String WoundMicron Rating <5 micronInter Conecting P/W CPVC10)Inter Conecting Pipe -1lotMake : ION Exchange or equivalent Make as per E-in-c Approval listNote : (i) Contractor has to submit design of RO plant for approval of same before placing the order for RO plant.(ii) Installation and commissioning shall be done by rep of OEM(iii) Consumables required for period of 01 year shall be provided by contractor and cost for the same shall be included in the quoted rate. |
| 82 | S & F rotational moulded polyethylene double layer water tanks (vertical cylindrical with close top) as per IS 12701: 1996 of 1000 litres capacity hoisted and fixed in position including provision of 20 mm /15 mm dia medium grade GI pipe for connecting inlet, outlet, over flow and washout pipes all as specified and as directed. |
| 83 | M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed. |
| 84 | S & F ball valves high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe of 25 mm size, minimum weight 455 grams complete all as specified and as directed by the Engineer-in-Charge. |
| 85 | Cutting galvanised mild steel pipe of nominal bore 40 mm or 50 mm for alterations or additions (each cut measured) complete all as specified and as directed. |
| 86 | M & L for 3- layer PP-R (Polypropylene random copolymer) pipes 25 mm dia outer dia ,SDR 7.4 (PN-16) pipes UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including fittings PP-R plain & brass threaded type polypropylene random fixed complete to walls, ceilings or in floors etc. complete all as specified and directed. |
| 87 | M & L for 3- layer PP-R (Polypropylene random copolymer) pipes 20 mm dia outer dia ,SDR 7.4 (PN-16) pipes UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including fittings PP-R plain & brass threaded type polypropylene random fixed complete to walls, ceilings or in floors etc. complete all as specified and directed. |
| 88 | S & F PP-R Gate valves (brass insert), 20 mm nominal size complete all as specified and as directed. |
| 89 | S & F PP-R Gate valves (brass insert), 32 mm nominal size complete all as specified and as directed. |
| 90 | S & F 15 mm nominal size, screw down bib taps, cast copper alloy body and body components with crutch handle, bright finished complete all as specified and as directed. |
| 91 | M & L for construction of new valve chamber of size 600 mm X 600 mm X 600 mm with burnt brick (Sub class B) including necessary earth work in any type of soil, PPC foundation (1:4:8) type D-2 20 mm grade stone aggregate as in base concrete, brick work in CM 1:4 with 10 mm thick plaster internally and 15 mm thick externally in CM 1:4, 4 mm thick MS cover with hinges and locking arrangement fixed to angle iron frame made out of 40 mm X 40 mm X 6 mm MS angles complete with 2 coats of synthetic enamel paint over one coat of red oxide prime on all metal works & three coats of white wash on all plastered surfaces of valve chambers complete all as specified & directed by Engineer-in-Charge. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender