Tender For Miscellaneous Repairs To Electric Supply System, Capacitor Panel, High Mast, Amf Panel And Allied Works At Zone Iid And Adjoining Area Under Age Emno-Ii Of Ge(Utility)Secunderabad, secunderabad-Telangana

Military Engineer Services-MES has published Tender For Miscellaneous Repairs To Electric Supply System, Capacitor Panel, High Mast, Amf Panel And Allied Works At Zone Iid And Adjoining Area Under Age Emno-Ii Of Ge(Utility)Secunderabad. Submission Date for this Tender is 05-03-2024. Electrical Panel Tenders in secunderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

42119055
Corrigendum : Tender For Miscellaneous Repairs To Electric Supply System, Capacitor Panel, High Mast, Amf Panel And Allied Works At Zone Iid And Adjoining Area Under Age Emno-Ii Of Ge(Utility)Secunderabad
Open Tender
Indian
Telangana
secunderabad
05-03-2024

Tender Details

Miscellaneous Repairs To Electric Supply System, Capacitor Panel, High Mast, Amf Panel And Allied Works At Zone Iid And Adjoining Area Under Age Emno-Ii Of Ge(Utility)Secunderabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Feb-2024 AMENDMENT Other 27-02-2024
2 27-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 05-03-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

BOQ Items

NAME OF WORK : MISCELLANEOUS REPAIRS TO ELECTRIC SUPPLY SYSTEM, CAPACITOR PANEL, HIGH MAST, AMF PANEL AND ALLIED WORKS AT DIV UNIT AREA , IDSR, ASC BN, EME BN, ASSAY LINE, MAP JCO/OR ACCN, TA BN AND ADJOINING AREA UNDER AGE EM NO-II OF GE(UTILITY) SECUNDERABAD
Sl. No. Item Description
1M&L for attending, repair and rectification of external LT electric supply complaints on up to 1100Volts grade, over head/underground system alongwith necessary T&P, safety devices as per site requirement for the following type of complaints complete all as specified and directed:-
2Replacement of worn out jumpers, jointing and tightening with new ACSR conductor. Note:- Single phase/two wire or 3 phase/4 wire system will be considered as one job for payment purpose.
3Disconnecting from over head conductor, cutting worn out portion of LTcables of any type and size, carry out repairs including taking out cables from under ground loop line and rejoining the same to restore electric supply. Note :- (i) LT Jointing Kits, Cable protection Pipe if required at site will be measured and paid separately. (ii) Quoted rate is deemed to be inclusive of cutting and removing the pole coping and inserting the cable alongwith protection pipes.
4Taking down old unsv Street light / flood lightfittings in any position of any capacity forRepair by replacement of unsv spares ( SPD / Driver / Mcpcb etc ) and re-fixing the same in existing location. Note:- Spares for repair of street light fittings will be measured and paid under respective items. Notes for Item Nos 1.01 to 1.03 :- (a)The contractor will be allotted complaints at MES complaint cell on daily basis on all working days and sufficient resources will be deployed by him/her for completion of day to day complaint within 24 Hrs from the time of reporting. Any delay beyond above mentioned time limit without intimation of sufficient cause, penalties will be recovered twice of the quoted rate for each un-attended complaint. (b)A detailed log of complaints with completion/non-completion remarks from users/MES will be maintained by the contractor and the same will be updated on daily basis in consultation with Engr-in-Charge or JE E&M as detailed. (c)The contractor will make suitable arrangement for emergency complaints and will notify auth rep/Engr-in-Charge about extraordinary circumstances for probable non-completion or delay in rectification of complaints beyond stated time limit set for disposal of complaint.In case of any dispute the decision of accepting officer will be final and binding in this regard. (d)The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e)The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station at Secunderabad. (f)The contractor will maintain location wise record of each spare utilized as per inventory format given by AGE E/M, Secunderabd and the same shall be submitted to E/M No II store on daily basis.
5M&L for ACSR conductor, steel reinforced for LT over head lines on poles including streching tightining of poles insulator with binding wire of suitable size with insulator/streching of ACSR conductor including disconnecting/taking out old existing unsv ACSR conductors complete all as specified and directed.
6M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, including disconnecting/taking out old existing unsv insulators complete all as specified and directed.
7M&L for Shackle type,Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts of size 100 mm height, 115 mm dia for 1100 Volt grade, section of straps 31x5 mm, including disconnecting/taking out old existing unsv insulators complete all as specified and directed.
8S&F Stay assembly comprising of 7/10 SWG galvanised MS stranded stay wire of required length, minimum tensile strength 70 Kg/mm (grade-2 quality) fixed to pole with and including FIclamps, bolts, nuts, washers, galvanised steel stay rod 16mm dia 180 cm long bow 400 x 14 mm nuts/bolts, washers, loop type insulator of size 65 x 90 mm vitreous, clearance dia of hole 16mm, stay plate of size 230 x 230 x 6 mm including necessary excavation and earth work PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in foundation and disposal of surplus soil, upto 50m including disconnecting/taking out old existing unsv stay assembly complete all as specified and directed.
9S&F of Galvanised steel wire (GI) 4mm dia including disconnecting/taking out old existing unsv GI wire complete all as specified and directed.
10M/L for cross arms, bracing, supports clamps and back plates fabricated from structural steel section incl nuts, bolts washers, welding, bending cold or hot drilling holes for bolts in any shapes or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including disconnecting/taking out old existing unsv cross arms complete all as specified and directed.
11Supply & Replace MCCB along with both side spreader link and nut bolts of appropriate size(Conforms to IEC:60947-II/IS:13947-II) in exisitng LT Panel box/Feeder Pillar boxes (KIOSK),in MCCB DBsof capacity 630 Amps, 4 Pole, 50 KA, 415 Volt microprocessor based including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed.
12All as per item No-8 here in before but of capacity 315-400 Amps, 4 pole, 25 KA
13All as per item No-8 here in before but of capacity 250 Amps, 4 pole, 25 KA
14All as per item No-8 here in before but of capacity 200 Amps, 4 pole, 25 KA
15All as per item No-8 here in before but of capacity 160 Amps, 4 pole, 16KA
16All as per item No-8 here in before but of capacity 125 Amps, 4 pole, 16 KA
17All as per item No-8 here in before but of capacity 100 Amps, 4 pole, 16 KA
18All as per item No-8 here in before but of capacity 63 Amps, 4 pole, 16 KA
19Supply and fixing of automatic street light switch using infrared sensor based nature switch for automatic switching of street lights.Nature switch operation should bebased on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off >10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs.The sensor along with suitable power contactors incoming outgoing MCBS SP andand automanual (sensor bypass selection option should be enclosed in a pole /wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 8 KW with circuit wiringmin 10 sq mm copper wire 63 Ampscontactorans suitable MCBs atboth positions at incoming and out goings of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt(4 nos)for fixing on pole / walllcomplete all as directed including taking down old one .Model no Swadeep-02 EC 8KW 1P DUALor equivalent from Havells/Legrand .
20Supply and replace contactor single pole 20/25/32 ampsin stret light timer boxcoil operating voltage 230 volt complete all as specified and directed
21Supply and replace contactor single pole 40/63 ampsin street light timer boxcoil operating voltage 230 volt complete all as specified and directed .
22Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through jointwith jointing material and accessories suitable forLT UGcable of size16 to 50 Sqmm, 3.5 Core complete all as specified and directed.
23All as per item No 23 above but suitable foraluminium conductor cable of sizefrom 70 sqmm, 3.5 Coreto 95 Sqmm, 3.5 Core
24All as per item No 23 above but suitable foraluminium conductor cable of sizefrom 120 sqmm, 3.5 Coreto 150 Sqmm, 3.5 Core
25All as per item No 23 above but suitable foraluminium conductor cable of sizefrom 185 sqmm, 3.5 Coreto 240 Sqmm, 3.5 Core
26Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size16 to 50 Sqmm, complete all as specified and directed.
27All as per item No 26 above but suitable foraluminium conductor cable of sizefrom 70 sqmm, 3.5 Coreto 95 Sqmm, 3.5 Core
28All as per item No 26above but suitable foraluminium conductor cable of sizefrom 120 sqmm, 3.5 Coreto 150 Sqmm, 3.5 Core
29All as per item No 26 above but suitable foraluminium conductor cable of sizefrom 185 sqmm, 3.5 Coreto 240 Sqmm, 3.5 Core
30Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testingand commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 4 Core 10 Sqmm complete all, as specified and directed Note :- Earth work excavation, sand cushioning and brick protection shall be measured and paid separately.
31All as per item no:30 above but 2 Core 10 Sqmm
32All as per item no:30 above but 4 Core 16 Sqmm
33All as per item no:30 above but 4.0 Core 25 Sqmm
34All as per item no:30 above but 3.5 Core 35 Sqmm
35All as per item no:30 above but 3.5 Core 50 Sqmm
36All as per item no:30 above but 3.5 Core 70 Sqmm
37All as per item no:30 above but 3.5 Core 95 Sqmm
38All as per item no:30 above but 3.5 Core 120 Sqmm
39All as per item no:30 above but 3.5 Core 150 Sqmm
40All as per item no:30 above but 3.5 Core 185 Sqmm
41All as per item no:30 above but 3.5 Core 240 Sqmm
42All as per item no:30 above but 3.5 Core 300 Sqmm
43Taking out and Relaying of LT cable of size 10sq mm to 50 Sqmm 2/3.5 coreafter carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugsall as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
44Taking out and Relaying of LT cable of size 70 sq mm to 150 Sqmm 3.5 coreafter carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugsall as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
45Taking out and Relaying of LT cable of size 185 sq mm to 300Sqmm 3.5 coreafter carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugsall as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
46Supplying, erecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 mtrs long)including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellowpaint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
47Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed. Notes: (i) The distance between pole to pole in one span (contains 2/4/6 runs) i.e one span will only be considered for payment purpose. (ii) No Extra conductor will be measured for binding to insulators / jumpering etc.
48Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in Hard / Densesoil complete all as specified and directed.
49All as per item No 36above but depth exc 1.5 mtr but not exc 3 mtr.
50Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
51Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
52Spreading riddled earth ( after preparation of excavated earth) inCable duct forcushioning of cable laid in trenches complete all as directed by Engineer-in-ChargeNote:- Punned thickness 18 CM( 6.25 Cm below cale and 11.75 cm above cale)will be measured for payment purpose. The earth removed during excavation to be used as rddled earth after crushing and sieving. Quoted rate inclusive of all arrangement as mentioned.
53Supply and Laying bricks, common burnt clay building bricks, sub class "B" of size 210 x 110 x 70 mm laid across in trenches for cable protection complete all as specified and directed.
54Laying only old Brick in trenches for Under Ground Cable Protection (Serviceable Materials obtained from Item No. 1 here-in-before), complete all as directed.
55Supplying and laying reinforced precast concrete cable cover class LV , Type 1 flat with size 250mmx150 mm x 40mm all asspecified and directed by Engr-in-Charge.
56M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate for filling & foundation of pole & mass complete all as directed
57M&L PCC 1:3:6 type C2 using 40 mm graded stone aggregate for filling & foundation of pole & stay complete all as directed
58M&L PCC 1:2:4 type B1 using 20 mm graded stone aggregate for coping of pole complete all as directed
59Cutting the existing road/PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed.
60M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE / GIpipe medium dutyduty of size 100 mm diain any length including jointing materials to carry LT UG cables of size upto 240 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed.nOTE ; PIPE WILL BE MEASURED AND PAID SEPARATELY UNDER RELEVANT ITEMS
61M&L for replacement of broken earth pit made out of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, 20 mm thick and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia MS deformed bars @ 100 mm centre to centre both ways with hook made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers etc as required at site complete all as specified and directed.
62M&L repair/maintenance of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified and directed.
63M&L for painting the existing LT steel poles of 9.0 Mtr long including cross arms, clamps, street light junction boxes etc with 1 coats of aluminium paintincluding throughly cleaning the existing surface, writing of pole numbers in yellow circle 15 cm with black paint on poles. Painting the poles up to 1.5 Mtr height with alternate bands 30 cm height (3 Nos black and 2 Nos Yellow) from ground level, complete all as specified and directed.
64M&L for Painting the existing LT PCCpoles with 1 coats of synthetic enamole base paintincluding painting of cross arms, clamps, etc with one coat of aluminium paint and providing alternative band of 30 cm width (3 black and 2 yellow) from bottom of pole to 1.5 metres height , writing of pole numbers in yellow circle15 cm with black paint on poles complete all as specified and directed.
65Advance Maintenance Free G.I. SAFE EARTHINGElectrodewith PIPEof not less than 50 mm outer dia) and two meterlength, The electrode should be ofgalvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compoundto provide maximum contact between the electrode and Back Fill Compound. The earting pitcover should be factorty built (sizeTOP- 10 Inch, Bottom -13 Inch, Height 10.25 Inch ) made of heavy duty Polypropylenecomplete all as specified and directedmakeASHLOK/INDELEC/JMV /TERCEL/TRUE POWER
66S&F galvasised steel strip 32X6 mm with saddles and fixing screws on poreceling insulator/ spacer fixed at every 1 mtr length as lightening conductor on roof/wall of explosive building and joining the same with existing earth test point all as directed by Engr-in-Charge.
67Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P and safety equipments to complete the job.
68Cutting unaxious green growth and grass by manual labour or by machine at all 11 KV Electric Installation premisses/around 2/4 Pole structure/along the boundary fencing and removing rubbish from the site of work complete all as specified and directed.
69S&F LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete, lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection and impact resistance of IK07 with 10 KVBuilt-in-Surge Protection Device,road way light fitting with high power LED as light source of capacity 90 watts with suitable drivers etc and connecting with 1.5 Sqmm copperconductor PVC insulated three core weather proof cable etc, fixing to wall/pole, complete all as specified and directed. Note :(i) LED"s used should be the make of Cree/Osram/Lumilieds/Nitchia. (ii) Contractor has to produce LM-79/LM-80 certificate alongwith purchase vouchers. (iii) Surge protection of the drive should be 10 KV
70All as per item No-57 above but 70/72watts.
71All as per item No-57 above but 60 watts.
72S&F LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrossion resistant complete with driver and lamp die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting, with high power LED as light source of capacity 120 watts with suitable drivers etc and connecting with 4.0 Sqmm aluminium conductor PVC insulated twin core weather proof cable etc, fixing to wall/pole complete all as specified and directed. Note :(i) LED"s used should be the make of Cree/asram/Lumilieds/widchia (ii) Contractor has to produce LM-79/LM-80 certificate alonwith purchase vouchers and Guarantee certificate from Manufacturer. (iii) Surge protection of the driver should be 10 KV
73All as per item No-60 above but 120 watts.
74All as per item No-60 above but 150 watts.
75All as per item No-60 above but 200 watts.
76Supply, fixing, connecting and testingpost top light fitting in spherical shape polycarbonate PMMA clear diffuser and IP65 protection, new generation energy saving and environmental friendly long life aesthetically desinged aluminium decorative luminaires with high power LED as light source of capacity1X35/40 watts, fixed to Pole/Wall in any position including taking down old existing street light fitting of any type and capacity complete all as specified and directed.
77Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for60 watts LEDstreet light fittings of any makecomplete all as specified and directed.
78Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for70/72 watts LEDstreet light fittings of any makecomplete all as specified and directed.
79Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for90 watts LEDstreet light fittings of any makecomplete all as specified and directed.
80Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for100/110/120 watts LEDstreet light fittings of any makecomplete all as specified and directed.
81Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for100 watts LED floodlight fittings of any makecomplete all as specified and directed.
82Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for120 watts LED floodlight fittings of any makecomplete all as specified and directed.
83Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for150 watts LED floodlight fittings of any makecomplete all as specified and directed.
84Supply only LED Driver of similer wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS crtifiedsuitable for200 watts LED floodlight fittings of any makecomplete all as specified and directed.
85Supply and fixingsteel light bracket made out of 40 mm bore mild steel GI light grade tubing over all length 1.5 mtr bend to shape as directed including providing two Nos MS flat iron 40x6 mm clamp of appropriate size with nut bolts and washer duly painted with two coat of synthetic enamel paint over a coat of primer (GI surface shall not be painted) complete all as specified.
86S&F PVC insulated unsheathed/sheathed cable with stranded Aluminium conductor 1100 Volts grade, flat twin core service cable of size 4 Sqmm conforming to IS:694/1990 with latest amendments ISI including disconnecting/taking out existing unsv/damaged old service cable complete all as specified and directed.Make : Richa/havells or equivalent.
87All as per item No-74 above but of size 6 Sqmm complete all as specified and directed.
88S&F hot press moulded SMC junction/terminal box of size with internal diamensions of 300 x 200 x 1055 mm with hinged door, incl provision of 2 way connector 415 Volts made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/glands, fixed on pole by means of clamps made out of MS flat iron of size 25mm x 3 mm 2 Setincluding dismantling of old unserviceable all as specified and as directed. Make : Syntex/C&S/Havells.
89Supply and laying GI tubing light grade of size 40 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
90Supply and laying GI tubing light grade of size 50 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
91Supply and laying GI tubing light grade of size 80 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
92S&F LT line rigid PVC Spacers spiral type, two lines, Phase to phase distance 300 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
93S&F LT line rigid PVC Spacers spiral type, three lines, Phase to phase distance 600 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
94S&F LT line rigid PVC Spacers spiral type, four lines, Phase to phase distance 900 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
95S&F On-Load changeover switch (In sheet steel enclosure), AC 21 (Side Handle), 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
96S&F On-Load changeover switch (In sheet steel enclosure), AC 23 (Side Handle), 4 pole of capacity 100 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
97Supply only of aluminium cable lugs of following sizes :-
9816to 25 Sqmm Size
9935to 50 Sqmm Size
10070to 95 Sqmm Size
101120to 150 Sqmm Size
102185to 240 Sqmm Size.
103S&F MCCBboxFACTORY FABRICATED Powder coated Suitable for fixing at WALLincluding two set of clampscomprisinf with the following i) MCCB63 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK.
104S&F MCCBboxFACTORY FABRICATED Powder coated Suitable for fixing at WALLincluding two set of clampscomprisinf with the following i) MCCB100 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK.
105S&F MCCBboxFACTORY FABRICATED Powder coated Suitable for fixing at WALLincluding two set of clampscomprisinf with the following i) MCCB125 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK.
106Supply and fixon wall with necessary arrangements busbar chamber 100 amps 4 way4 polewall mounted IP -31 , made out of 1.6 mmthick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Secondincluding necessary cable connectionscompleteall as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber.
107Supply and fixon wall with necessary arrangements busbar chamber 200 amps 4 way4 polewall mounted IP -31 , made out of 1.6 mmthick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Secondincluding necessary cable connectionscompleteall as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber.
108Dismentling ofdamage / broken coping of PCC/steel pole of any size anf and removing the debries from site complete all as specified and directed
109Supply and fixing lantren of dia 60 CMfor fixing of flood light,cap type to be fixed on the top of 9 m SP-31 / 11 m SP-55Steel pole , made of MS pip medium gradedia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50X6 mm 8 nosincluding two coat of aliminium painting over a coat of redoxide primer complete all as directed
110Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
111Supply anfd fix locally availablegate / garden lightlight best qualitymetal Silver / metal blackDecorative Exterior of size not less than 300 mm X220 mm with and including LED bulb 9 wattsuitable for outdoor installationandsuitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directedincluding taking down old one .
112Supply anfd fix locally availablegate / garden lightlight best quality Black Color Steel Shade With Fiber Glass Outdoor Gate Lampof size not less than 360 mm X250 mm with and including LED bulb 9 wattsuitable for outdoor installationandsuitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directedincluding taking down old one .
113Material and labour for Taking down UNSV LED Lights and removing Carbon from its connector joints incl replacement of Connecting wire with new PVC sheated weatherproof 3Xsingle core cable for electrical connection and refixing the fittingafter repair to its original/New location or as directed by engr-in-charge.(connecting wire will be measured and paid separately only)
114Supply anfd fix locally available Acrylic globe light best quality clear with and including LED bulb 9 watt of 200 mm dia complete suitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directed including taking down old one .
115Supply anfd fix locally available Acrylic globe light best quality clear with and including LED bulb 9 watt of 300 mm dia complete suitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directedincluding taking down old one .
116Material and Labour for drawing two runs ofPVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm with one run of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm including 20mm dia PVC conduitof dia 20 mm medium gradeexclusive of boxes but inclusive of all tees, bends, elbow, reducers etc and fixing accessories such as couples, lock nuts, saddles, pipe hooks, clampsetc complete all as specified
117Supply and lay PVC Insulated , PVCsheathed industrial HV round multicore flexible cablewithcopper conductorTHREE core 2.5 sqmm including PVC conduit 20mm dia medium grade and necessary bends, fittings and fixturesas required for connection of light fittings . ( uSED FOR GARDEN LIGHT CONNECTION, EXCAVATION , RETUNING FILLIING ETC WILL BE MEASURED AND PAID SEPARATELY.
118Supply, fixing, connecting and testing decorative LED Bollard light with opal diffuser and aluminium reflector of 9/12 watt LEDincluding nut, bolts, washers, clamps etc as in repair complete all as specified and directed.
119Supply and lay PVC Insulated , PVCsheathed industrial HV round multicore flexible cablewithcopper conductorTHREE core 1.5 sqmm as required for connection of light fittings .
120Excavation in post holes (or similar holes) each n exc 0.50 cum getting out In hard / dense soil returning filling in and ramming earth or broken rubble mixed with earth around in layers not exceeding 25 cm complete all as specified and directed
121M&L for framed works in posts and struts in fencing including cutting tops to shape as directed drilling holes notching for wire etc flat iron fillets ( for securing wire mesh etc ) including all necessary drilling bolting or riveting etc and simlar work conforming to FE-290 Gde E-165 including dismantling of old fencing complete all as specified and directed.
122S&F 3.15 mm dia chain link MS galvanised fencing wire and average size of mesh 100 mm X 100 mm including line wires to ant type of standard rails straining bolts etc including provision of binding with MS wire annealed not less than 0.9 mm dia complete all as specified and directed.
123M&L for cleaningAND painting LT panel boards of any size thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt / rust carefully and applying two coats of synthetic enamel paint OVER A COAR OD RED OXIDE PRIMER COMPLETE all as specified and directed.
124Supply, Installation, test and Commissioning factoryfabricated, outdoor type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheet of suitablesize Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeddedwith 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete withinternal connection with suitable size of cable ,cable lugs, and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and comprising of the following :– (a) Aluminium bas bar of 300 Amps - 04 Nos in 3Phase and half neutral fashion , supported with suitable size of heavy duty porcelain stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 100amps, 415 volt,16 KA Breaking capacity4 pole Electromagnetic release duly connected to Bus Bar asIN COMING- 01 Nos
125Supply, Installation, test and Commissioningfactoryfabricated, outdoor type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheet of suitable size with projected Globe roof for rain water protection Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeddedwith 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete withinternal connection with suitable size of cable ,cable lugs, and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and comprising of the following :– (a) Aluminium bas bar of 400 Amps - 04 Nos in 3Phase and half neutral fashio, supported with suitable size of heavy duty porcelain stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 200amps, 415 volt,16 KA Breaking capacity4 pole Electromagnetic release duly connected to Bus Bar asIN COMING- 01 Nos
126M&L for shingle filling in floors or pavings of gauge 20 mm to 40mm deposited spread and levelled in layers not exc 150 mm thick watered and rammed to true surface complete all as specified and directed
127Replacement of transformer/LT Panel Boards End covers with suitable size of MS Sheet of 2mm thick including drilling holes as per existing transformer/LT Panel end cover, painting with 1 coat of red oxide primer and two coats of synthetic enamel paint and fixing with suitable size of nuts and bolts, hinges completecomplete all as specified.
128M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size Complete all as specified and as directed
129All as above but of HT 25x20 cm size
130Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 100 KVARs and up 8 stages installed atvarious locations at MCEME area including carrying out complete maintenance/repairs as required of all the sub systems viz. basedcontrol panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT,MCBs/MCCBs for isolation (with all the accessoires) anybreakdownmaintenance and replacement of unserviceable parts, refixingof old serviceable parts/new parts if anyproject completionand trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, repavement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etcand necessary servicing repair by expert technician and register will be maintaned for the same. (ii)The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCBshall be measured and paid separately
131Supply only powerfactor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
132All as per item No 114 above but 10 KVAR Capacitor Bank
133All as per item No 114 here-in-before but 20 KVAR Capacitor Bank
134All as per item No 114here-in-before but 25 KVAR Capacitor Bank
135S&F APFC relay etaCON M series with auto-set function 5 stage including taking down old unserviceable one complete all as specified and directed.
136All as per item No 118 here-in-before butAPFC relay with auto-set function 7 stage
137All as per item No 118 here-in-before butAPFC relay with auto-set function 8 stage