Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Half brick masonry using fly ash bricks in cement mortar 1:4 (1 cement : 4 coarse sand) with bricks of class designation 40 kg/cm2 including longitudinal reinforcement of 2 Nos. 8 mm diameter bar every 12th layer embedded in horizontal RCC band (1:1.5:3) Above plinth upto floor V level (200 x 95 x 95 ) |
| 2 | Laterite masonry in neatly dressed stones of size as specified in cement mortar 1: 4 (1cement :4 coarse sand) inallsizesin superstructure from floor I level upto floor V level. |
| 3 | Pre-cast cement concrete solid block masonry of compressive strength 70 kg/cu.m in cement mortar 1:4 (1 cement : 4 coarse sand ) in Super Structure of size specified up to level 5, as per the direction of engineer in charge. |
| 4 | Providing and laying in position machine batched concrete (BMC), machine mixed and machine vibrated design mix cement concrete of specified grade for reinforced cement concrete work including pumping of concrete to the site of laying but excluding the cost of centering , shuttering, finishing and reinforcement includingadmixtures in recommended proportions as per IS 9103 to accelerate, retard setting of concrete, improve workability without impairing the strength and durability as per the direction of the Engineer-in-charge. M30 grade of reinforced cement concrete by using 420 kg of cement per cu.m. of concrete. All works upto floor V level.(Design Mix by Ready mixed concrete ( RMC) may be used atno extra cost |
| 5 | Centering & shuttering including Strutting, Propping & removal of forms for : |
| 6 | Vertical surfaces such as retaining walls, return walls, Partitions, walls (any thickness) including attached Pilasters, Buttresses, Plinth and string courses, Fillets and the like |
| 7 | Columns, Piers, Pillars, Abutments, Posts and struts (square rectangle polygon in plan) |
| 8 | Sides and Soffits of beams, Beam Haunchings, Cantilever, Girders, bressumers and Lintels plinth beams not exceeding 1m in depth |
| 9 | Staircases (except spiral staircases) excluding landing |
| 10 | Suspended floors, roofs landings, shelves & their supports |
| 11 | Providing TMT steel reinforcement bars of SAIL, TATA. VIZAG made only (Confirming to IS 1786 of 1986)for RCC work (conforming to I.S. 1786 of 1986) including bending, binding & placing in position in all the floorsalongwith the factory made precast concrete cover blocks of specified sizes whose compressive strength is not less than that of surrounding concrete in the structural member. |
| 12 | Providing woodwork in frames of doors, windows, clerestory windows trusses & other frames wrought framed and fixed in position. (Second class Indian teak wood) |
| 13 | Providing& fixing flush door shutters decoration type core of block board construction with frame of first class hard wood and well matched first class Indian teak ply veneeringwith vertical grains and cross bands and face veneers on both faces of shutters.( 35mm thick including anodized aluminum butt hinges with necessary screws ) |
| 14 | Providing flat iron hold fast 40 cm including fixing to frame with 10 mm dia bolts, nuts and wooden plugs and embedded in cement concrete block 30 x 10 x 15 cm 1:3:6 mix (1 cement: 3 coarse sand: 6 stone aggregate 20 mm nominal size.(40 x 3 mm flat iron hold fast 40 cm long) |
| 15 | Standard Wood Core Door Shutter with SingleColourManufacture, Supply and Installation (including accessories as mentioned below) of EPEE or equivalent Goan make FRP (Fiber Reinforced Polymer) door shutter of specified thickness as per options below by using tray system with seasoned hard wood, moisture less than 17%, wood styles for Top rail and lock rails. FRP (Fiber Reinforced Polymer) laminate made up of 450 grams per sq.mts (gsm) chop strand matt and unsaturated polyester resin with viscosity range of 400/450 centipoises per second (cps).The core of Shutter will be filled with MR2nd grade Block Board. The shutter to be water proof as well as mild acid /alkali resistant manufactured using RV TIFAC (R V Engineering College, Bangalore & Technology Information Forecasting & Assessment Council) technologyin line with IS13034 1990 test Standard in an ISO 9001 – 2015 certified factory. |
| 16 | i) S. S. Hinges 4”- 3 Nos ii) S. S. Latch- 1 No iii) Tower Bolt 5” - 2 Nos iv) Handle 5”- 2 Nos |
| 17 | FRP(FiberReinforcedPolymer)FramesManufacture,SupplyandInstallation(with anchorfastener)ofEPEEorequivalentGoanmake FRP (Fiber Reinforced Polymer) Frame ofcrosssectionasperoptionsbelowwithright angle joint and FRP (Fiber Reinforced Polymer)laminate made from 450 grams per sq.mts (gsm) chop strand glass fiber (matt) and unsaturated polyester resin with viscosity range of 400/450 centipoises per second (cps). The core of framewould be filled with seasoned wood as infill material. The slot of frame for door resting will be of suitable width so as to take specified thickness door.. The frame will be water proof as well as mild acid/ alkali resistant manufactured in an ISO9001- 2015 certified company. |
| 18 | 5” x 2 ½ “ |
| 19 | Providing & fixing bright finished SS handles of SS 305 grade of steel with necessary screws etc. complete. 125 mm |
| 20 | Providing and fixing bright finished SSdoor latch with necessary screws etc complete (300x 16 x 5 mm) |
| 21 | Providing & fixing bright finished Stainless Steel mortise latch & lock and a pair of levers handles with necessary screws etc.complete (100mm x 150mm) |
| 22 | Provided and fixing 150 mm SS floor door stopper with rubber cushion screws etc. to suit shutters thickness complete. |
| 23 | Providing and fixing SS hydraulic door closer of approved make with necessary screws and fittings complete. |
| 24 | Providing and fixing SS butt hinges with necessary screws etc. complete [ 125 x 70 x 4.0mm (ordinary type) ] |
| 25 | Providing & fixing SS Tower Bolts (barrel type) with necessary screws complete. ( 250 x 10 mm ) |
| 26 | Steel work in single sections (SAIL, TATA. VIZAG & using electrodes of Ador or ES4B or Deh Secheron make only) including cutting, hoisting fixing in position and applying a priming coat of red lead paint. |
| 27 | In R.S. joists, channels, angles, tees |
| 28 | Providing and fixing in position S.S. hand rail in main stair case, and landing as per approved design shown in the drawing including bending handrail pipe to proper shape in curves with specials, etc. complete. |
| 29 | Providing&fixingTwoTrackslidingwindowYashashri make or equivalent, in heavy sections made out of 104mm x51 mm x2.5 mm Upvcmulti cavity track section & shutter made out of45mm x54mmx 2.5mmUpvc multi cavity section welded in corners with Glass beading &EPDM Gasket & 4mm clear glass with lock & rollers. The average weight of Two Track Sliding window (Heavy) is 16.75 kg per sq mtr. These Upvc sections are tested by using BS 2782 & DIN53459 test methods. |
| 30 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) (Square Hollow Section (SHS) IS4923 /Rectangular Hollow Section (RHS) IS4923/ Circular Hollow Section (CHS) IS1161 closed Structural Steel of (SAIL, TATA. VIZAG, JSW ,APOLLO Steel Ltd.) make (Min Yeild Stress 310 Mpa)) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 31 | Providing and fixing M.S. grill of required pattern in wooden frames of Windows etc. with M.S. flats square or round bars with round headed bolts and nuts or byscrews. (Plain Grill) |
| 32 | Extra for powder coating with pure polyester powder of shade of required colour on the aluminum section |
| 33 | Kotah stone slab flooring over 20 mm (average) thick base laid over & jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing &complete with base of cement mortar 1:4 (1 cement : 4 coarse sand) 20mm thick |
| 34 | Providing & fixing kotah stone tread tiles 20 mm thk.in single piece with half roundednosing, antiskid grooves, laid on20 mm (average) thick bed of cement mortar 1:4 (1 cement : 4 coarse sand) with neat cement slurry including pointing with pigmented cement slurry to match the shade of slab, cleaning etc. complete. |
| 35 | Kotah stone slab flooring over 25 mm thick in risers of steps, skirtings, dado & pillars laid on12mm (average) thick cement mortor 1:3 (1 cement : 3 coarse sand) & jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing &polishingcomplete. |
| 36 | Providing and fixing 18mm thick mirror polished raws silk granite machine cutfor kitchen platforms,counters, window sills, facia, Walls and similar locations of required size of approved shade, colour and texture laid over 20mm thick bas cement mortar 1:4 (1 cement : 4 coarse sand) with joints trated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing,moulding and polishing to edge to give high gloss finish, etc. complete at all levels. |
| 37 | Providing and fixing 1st quality ceramic glazed wall tiles (Johnson, Somany, Kajaria )conforming to IS:15622 (thickness to be specified by the manufacture of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-charge in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand ) and jointing with grey cement slurry @3.3kg per sq.m including pointing in white cement mixed with pigment of matching shade complete. |
| 38 | b)Wall Ceramic Glazed Tiles : 300 x 450 |
| 39 | Providing andlaying antiskid floor tiles 12 x 12 upto 16 x 16 in of Johnson, Somany, Kajaria(thickness to be specified by the manufacturer) of 1st quality conforming to IS:15622 of approved make in shades as specified laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement & matching pigment etc,complete(a-Dark Shades) |
| 40 | Providing and and laying vitrified floor tiles in different sizes of Johnson, Somany, Kajaria (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622 of approved make in colours and shades as specified laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarsesand) including grouting the joints with white cement and matching pigment etc., complete900x900mm light shade |
| 41 | Providing and fixing Vitrified tiles in different sizes(thicknesstobespecifiedbymanufacturer), with water absorption less than0.08%andconforming toI.S.15622,of approved make, in all colours & shade, in skirting, riser of steps and dados, jointing withgrey cement slurry @3.3 kg per sqm, including pointing/grouting in white cement mixed with pigment of matching shade complete. |
| 42 | Light shade |
| 43 | Providing and laying jet black mirror polish granite flooring and dado over 20mm thick base of cement mortar 1:4 laid over and jointed with cement slurry including rubbling complete Granitic slab (jet blck with mirror polish) 20 mm thick add q0% wastage 1.00 |
| 44 | Providing and installing double skin roofing with top sheetof colur coated bare Galvalume high tensile cold rolled steel having mangalore tile profile and thermal insulation and liner sheet below fixed to M.S. Purlin. The top sheet shall be 0.5 mm thick , the thermal insulation shall be 50 mm thick with density of 24 kg / m3 , the bottom sheet shall be bare galvalume on top and colour coated at the bottom side. The sheets shall be fixed by usig rustproof self taping screws. The top and bottom sheets shall be separated byZ Shaped sub-girt made from Galvanised sheet 1.6 mm thick, spaced at 1.2m c/c . |
| 45 | Proving and Fixing Galvalume Flashings at corners,gabble ends,ridges,gutters,valleys and trim fabricated from 0.5mm colur coated bare Galvalume high tensile cold rolled steel sheets. The corrugations/profile shall match the profile of top roofing sheets. |
| 46 | Providing water proofing treatment over the newR.C.C. roofs terrace toilet by spreading cement slurry over the R.C.C. slab andlaying of 10cms. Average laterite stone ballast coba with the necessary gradient for easy flow of rain water and the coba in covered with damp proof of Hindustan water proofing co. Or equivalent jointless water proofing plaster of mix 1:3 (1 cement: 3 find sand), finished smooth with wooden trowel with false marking of 30 cms square.The vertical surface of the adjoining walls are to be treated upto a height of 30cms including rounding of junction (the rate includes for complete items including labour and materials and including cost ofinitial treatment of roof slab as follows. The injunction of damp proof or equivalent compound with cement solution will be given as and when found necessary for filling honey comb, cracks etc. in the R.C.C. slabs). NOTE: cement consumption 25 kg/sq.m. |
| 47 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of toilets consisting of following operations: (a) Applying a slurry coat of neat cement cement admixed with water proofing compound conforming toIS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto UPTOFloor level height including cleaning the surface before treatment. (b) Laying Laterite Boulders with mortar using brokenBoulders150 mm to 200mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto UPTOFloor level height including rounding of junctions of walls and slabs (c) After two days of proper curing applying a second coat of cement slurry using 2.75kg/ sqm of cement admixed with water proofing compound conforming toIS : 2645 and approved by Engineer-in-charge.(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : |
| 48 | Providing and applying on a well prepared vertical surface Sonoshield HLM 5000 of BASF makeorequivalentone-component,moisture-curing, bitumen-modified polyurethane elastomeric waterproofing membrane for exterior below-grade or between-slab applications.Theproductshallbeappliedinminimum two coats to achieve total DFT of 1.25 mm. The materials shall be mixed and applied fully in accordance with the manufacturer\"s instructions. This material has got very high Elongation Almost >600%. All scaffolding,ladders, supporting materials etc. complete. Rates shall be inclusive of all labour, materials, tools and plant etc. complete. |
| 49 | Providing and Fixing 200mm Square 0.5MM thick in color, with shades specified by architect. GI Rainwater Downtakes as including all necessary fixtures, etc complete as specified by the engineer in charge : |
| 50 | Fineline or equivalent(pre-coated) 600 mm x 600mmgridsize providing & fixing pre-coated G.I. angle size 24 x 24 x 0.90 mm thick fixed to the brick wall/partition at the perimeter of ceiling with nylon sleeves and screws at 610 mm centres. Then suspending main G.I. `T’ section (bottom pre-coted) size 24x38x0.7 mm and 3600 mm long from soffit in one direction withthe help of metal rawl plug, soffit cleat & G.I. rod4 mmdiameterwith galvanished spring steel level clip 1220 mm centres G.I. Cross T section (bottom pre-coated) size 24x 38.70 mm and 600 mmlongininsert fixed into the slots provided in main `T’ at 600 mm centres to form 600 x 600 mm grid.Boarding: 9.5 mm/ 12.5 mm thick thick Gyboard or equivalentcut in panel size of 595 x 595 mm can be laid onto the grid P.V.C. universal holding clips are to be placed on ceiling panel in each direction i.e. 4 clipsper panel. |
| 51 | Providing and applying white cement based putty of average thickness 1.00mm of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 52 | 12mm cement plaster 1:3 (1 cement : 3 fine sand) |
| 53 | 6mm cement plaster to ceiling 1: 3 (1 cement : 3 fine sand) |
| 54 | 18mm cement plaster in two coats under layer 12mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand) and top layer 6mm thick with cement plaster 1: 3 (1 cement : 3 coarse sand) finished with sponge. |
| 55 | Extra for providing and mixing water proofing material proportion recommended by the manufacturers. |
| 56 | Painting three or more coats with acrylic exterior paint of approved brand and manufacture (such as weather shield, APEX) including applying one coat of cement primer and one coat of surface treatment etc. complete. |
| 57 | Wall painting (two or more coats) with plastic emulsion paint of approved brand and manufacture on new work to give an even shade. |
| 58 | Painting (two or more coats) with synthetic enamel paint of approved brand and manufacture in all shade or new work over and under coat of suitable shade with ordinary paint of approved brand and manufacture to give an even shade. |
| 59 | Painting (one or more coats) with black Japan paint of approved brand and manufacture to give an even shade. |
| 60 | 18mm thick plain cement mortar bands in cement mortar 1:4 (1 cement : 4 fine sand) |
| 61 | 18mm thick groove cutting in cement mortar 1:4 (1 cement : 4 fine sand) cm per meter |
| 62 | Supplying and fixing of cautionary/warning sign boards with reflective tape fixed on M.S. angles, tees as per drawing confirming to IRC-67-1977 etc. complete. |
| 63 | Providing and fixing information boards of size (1.5x1.00)m consisting of angle iron post of (75x75x6mm) fixed in cement concrete M15 grade(45x45x60)cm ,60 cm below ground two supporting 1.5 m length of ISA (30x30x5mm) and mild steel plate of (1.5x1.0)m,3mm thick fixed to the angles by welding/bolting etc. including painting with synthetic enamel paint two coats of approved brand and shade over single coat of primer,including lettering transportation etc. complete. |
| 64 | Proving and fixing white vitreous china water closet squating (European type w.c. pan) with seat and lid, C.P. brass hinges and rubber buffers 10 lts. High level P.V.C..Flushing cistern (of approved make) with fittings, rack bolts 32 mm diameter P.V.C.Telescopic flush pipe with fit tings and clamps 25mm P.V.C... over flow pipe withspecials & mosquito proof coupling of approved municipal design and nylon. chain and pull complete, cutting and making good the walls and floors where required. |
| 65 | W.C. pan with white plastic seat and lid. |
| 66 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430 x 260 x 350 mmand 340 x 430 x 265 mm sizes respectively with PVC automatic flushing cistern with fittings, R.S. or C.I. brackets, standard size galvanized steel flush pipe and spreaders with brass unions & G.I. clamps complete, including painting of cistern and fittings, cutting and making good the walls and floors where required.One urinal basin with 5 litres p .v .c. automatic flushing cistern. |
| 67 | Providing and fixing vitreous china wash basin with RS or C.I. brackets painted white, 15 mm C.P. brass pillar taps C.P. brass chain with rubber plug 32 mm C.P. brass waste of pattern, 32 mm diameter M.I. or C.P. brass trap and union complete, including cutting and making good the walls where required. (b-Flat back wash basin size 630x 450mm with a single 15 mm C.P. brass pillar taps.) |
| 68 | Providing and fixing 600 x 450 mm bevelled edge mirror of superior glass (of approved quality) complete with 6 mm thick asbestos sheet ground fixed to wooden cleats with C. P. brass screws and washers. |
| 69 | Providing & fixing CP brass towel rail complete with C.P. brass brackets fixed to wooden cleats with C. P. brass screws |
| 70 | 750 x 20 mm size |
| 71 | Providing and fixing toilet paper holder : |
| 72 | C.P. brass |
| 73 | Providing & fixing liquid soap container with C. P. brass lid and brackets fixed to wooden cleats with C. P. brass screws |
| 74 | Plastic container |
| 75 | Providing and fixing brass stop cock (heavy) of approved quality : |
| 76 | 20 mm nominal bore |
| 77 | Providing and fixing brass full way valve(heavy) duty with wheelof approved quality : |
| 78 | 20 mm nominal bore |
| 79 | 25 mm nominal bore |
| 80 | 40 mm nominal bore |
| 81 | 50 mm nominal bore . |
| 82 | Providing and fixing ballvalve(brass)ofapproved quality : |
| 83 | High pressure with P.V.C. floats: |
| 84 | 3)25mm nominal bore |
| 85 | Supplying and installation of HDPE water tanks Sintex / Fusion / Polycon / Shakti make of 2000 litre capacity including 300 mm high brick masonry pedestal of 230mm thickin CM 1:5, providing 75mm thick RCC 1:2:4 slab with reinforcement 8mm tor @150mm c/c,lifting the tank , making all necessary GI/PVC connections to inlet, outlet, and overflow nozzles and cleaning the tank before commissioning. |
| 86 | Providing and fixing rigid PVC S.W.R. (soil, waste & rain water drainage pipes ofapproved including lubricant etc. complete (single/double) socketed: |
| 87 | a)110 mm dia |
| 88 | b)75 mm dia |
| 89 | Providing and fixing rigid PVC bend (approved make ) for S.W.R. pipes including lubricating etc complete bend withdoor : |
| 90 | a)110 mm dia |
| 91 | b)75 mm dia |
| 92 | Providing and fixing rigid PVCbend of required degree (of approved make) for S.W.R. drainage pipes ofapproved including lubricating. |
| 93 | 110 mm dia |
| 94 | 75 mm dia |
| 95 | Providing and fixing single tee of rigid PVC (approved make) for S.W.R. pipes including lubricatingetc. complete, without door: |
| 96 | a)110 mm dia. |
| 97 | b)75 mm dia. |
| 98 | Providing and fixing single Tee of rigid PVC (approved make ) for S.W.R. pipes including lubricating etc complete, with door : |
| 99 | a)110 mm dia |
| 100 | b)75 mm dia |
| 101 | Providing and fixing single “Y” of rigid PVC (approved make ) for S.W.R. pipes including lubricating etc complete, with door : |
| 102 | a)110 mm dia |
| 103 | b)75 mm dia |
| 104 | Providing and fixing nahani trap ofrigid PVC (approved make) for S.W.R. pipes including lubricating etc complete, without door (110 mm dia) |
| 105 | Providing and fixing NICKEL chrome plated copper alloy Fancy Pillar Cock rocket type Jaquar make or equivalent. Confirming to IS 8931;1993 |
| 106 | 15mm nominal bore |
| 107 | Providing and fixing NICKEL chrome plated copper alloy Fancy BIB Cock Short Body Jaquar make or equivalent. Confirming to IS 8931;1993 |
| 108 | 15mm nominal bore |
| 109 | Providing and fixing NICKEL chrome plated copper alloy Fancy Health Fouset 1.5M FLEXIBLE TUBE WITH SWINGING WALL HOOK Jaquar make or equivalent. Confirming to IS 8931;1993 |
| 110 | Providing and fixing R.P.V.C. vent cowl: |
| 111 | 75 mm dia |
| 112 | Providing and fixing chlorinated polyvinyl chloride (CPVC) pipes confirming to IS:15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipes with clamps at 1 m. spacing.This includes jointing of pipes and fittings with one step CPVC solvent cement and testing of joints complete as per direction of the Engineer-in-charge. Internal work exposed on wall (Medium duty SDR 13.5 pipe). |
| 113 | 15 mm outer dia CPVC pipe |
| 114 | 20 mm outer dia CPVC pipe |
| 115 | 25 mm outer dia CPVC pipe |
| 116 | 32 mm outer dia CPVC pipe |
| 117 | 40 mm outer dia CPVC pipe |
| 118 | 50 mm outer dia CPVC pipe |
| 119 | Providing & fixing G.I. pipes complete with G.I. fittings including trenching & re-filling etc. (external work). |
| 120 | 50 mm nominal bore |
| 121 | Makingconnection of G. I. Distribution branch with G. I. Main 50 mm to 80 mmnominal bore by providing and fixing tee including treading the pipe etc. complete |
| 122 | Core cuttingRCC slabs beams etc. including all scaffolding aggangement, leader,where ever required. The location of coring to be scanned by metal detector before corring and brought to the notice of engineer incharge. The coring over reinforcement shall be strictly avoided. |
| 123 | 110 mm outer dia. |
| 124 | 75 mm outer dia. |
| 125 | 50 mm dia outer dia. |
| 126 | Providing and placingsleaves in Masonry, Concrete etc with the 6kgf/sq Cm. PVC pipe at the required location. |
| 127 | 50 mm dia |
| 128 | 100 mm Dia |
| 129 | 150 mm Dia |
| 130 | Providing & fixing in position monoblock moulded Plastic chairs of approved size,color and make with arm rest and having back support. Chairs should be stackable for easy handling and shall have apx. size of (570L x 572W x 780H),etc.complete. All material shall be of approved make. All works complete as per the drawing/ Image,specification and direction of the Engineer. |
| 131 | Providing and fixing of steel cupboards of Approximate size (78\"x36\"x19\").The steel used shall be 20 gauge. The front portion is made with two openableshutters of same material with central lock and SS handles with all neccessary hardware of approvedmake including resting on nyon bushing etc.The cupboard shall have 5 compartments. All works complete as per the drawing/ Image, technical specification and direction of the Engineer. |
| 132 | Supplying and installing in position Podium of approved colour and size(APX. SIZE:54\" x 24\" x 18\" ) with top made up of 19mm thick commercial plywood board with both sides laminate and having superior edge profilewith edge banding. Vertical three sides supports and two horizontal supports made up of 19 mm thick commercial ply board with laminates on both sides. The Podium shall have one drawer made of commercial plywood.Provision of microphone & wire management shall be made. All material shall be of approved make. All works complete as per the drawing/ Image, technical specification and direction of the Engineer. |
| 133 | Providing and placing in position approved make stainless steel cylindrical dustbin with cover (8\" dia x 12\" ht) . All the materials shall be of approved make. All works complete as per the drawing, Image, specification and direction of the Engineer . |
| 134 | Supply and installing in position soft display board of apx. size 36\" x 24\" having aluminum frame including 6mm thick soft board with blazer cloth top fixed in frame with clip fitting and all stainless steel hardwares and easy fixing to the wall. All material shall be of approved make. All works complete as per the drawing / Image, specification and direction of the Engineer |
| 135 | Providing and fixing in position lockable, aamplifier cabinet made of 20SWG steel.It shall have 1 Shelve and storage area for microphones,cables etc. It shall be provided with lock and handles and shall be perforated. Ventilation slits shall be provided as per teh requirement. All the materials shall be of approved make. All works complete as per the drawing./ Image, specification and direction of the Engineer. |
| 136 | Supplying and erecting isolation valve of size 100 mm dia as per specification No. |
| 137 | Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification No.FF- VL/HV |
| 138 | Supplying fire fighting R.R.L. Hose pipe 63 mm dia, 15m in length, fitted with necessary accessories complete as per specification no FF- FFA / RRL |
| 139 | Supply, installation, testing and commissioning of double door Hose Box made of M.S of size 750 x 400 x 400 mm to accommodate 2 hoses of 15m length and 1 branch pipe with viewing glass on the doorsand duly painted with the letters \"FIRE\". |
| 140 | Supplying & errecting 20/25mm GM air release cock, with necessary GI coupling to be fitted on to of air vessel or on wet riser as per specification. |
| 141 | Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30 m high pressure polypropylene (Polyhose) long fitted with necessary accessories complete as per specification. |
| 142 | External piping , underground for courtyard hydrant |
| 143 | Supplying and installing G.I. pipeof \"C class ERW Confirming to class 1239.Painted with anti corrosion primer paint in 2 coat and final paint. |
| 144 | 80 NB |
| 145 | Electrical works |
| 146 | Supplying and erecting PVC armoured cable 2 core 1.5 sq.mm.copper conductor complete erected on wall / ceiling as per specification No.CB-LT/CU |
| 147 | Supplying, erecting,testing and commissioningManual Call Point (Pill box) with break glass push button in metal enclosure complete. |
| 148 | Supply and erecting sounder hooterwith I/P voltage 24 V AC, sound power 90 Db, with 4 kw speaker housed in a factory made ABS housing |
| 149 | supplying & installing, testing & commisioning of addressabletype multi sensor Smoke / Heat/ Gas detector . |
| 150 | Supplying and erecting ABC powder fire extinguisher as per IS : 13849/15683 of 6 kg capacity with necessary clamp for erection on wall. |
| 151 | Supply and erecting Carbon Dioxide ( Co2 ) fire extinguisher of 4.5 kg.Capacity cartridge type conf.To IS 2878 complete erected with necessary clamp made front 50 x 6 mm.MS flat with nut and bolts grouted in wall complete. |
| 152 | Providing & Fixing Self luminating signages for following items of (size 4\" x 12\") |
| 153 | Exit Signage |
| 154 | Fire extinguisher Signage |
| 155 | Hose Signage |
| 156 | Fire Alarm Signage |
| 157 | Supply, Installation, Testing and Commissioning ofElectrical Panel cubicle type, totally enclosed, free standing type, dust, damp and vermin proof,indoor type with IP 56 protection, made up of 14/16 SWG CRCA sheet, having chemical surface treatment and finishing shall be of 2-coats of synthetic enamel, RAL - 7032, complete with copper/Al busbars, danger notice plate, interconnections with suitable capacity copper leads/solid copper strips,and having incoming and outgoing switchgears with cable alley as mentioned below and complete as per technical specifications and as required. The size of cable alley shall be sufficient enough to accomodate the cable sizes as mentioned in the SLD/ specifications/ drawings etc. and along with the following. |
| 158 | METERING PANEL(FOR FIRST FLOOR) Metering panel consisting of:1) Incomers:MCCB , TPN, 100 A, 25KA Thermal release - 1 No. Busbar:150 A TPN Al.Busbar.Outgoings:MCB, SP, 25A, 230V, 10KA-11 nos.MCB, TP, 25A, 415V, 10KA-2 nos.MRT tested direct 10-60A KWH meter three phase- 2 nos. Compartment shall have sealing arrangement as per MRT norms.MRT tested direct 10-60A KWH meter single phase- 11 nos. Compartment shall have sealing arrangement as per MRT norms.N.B. : Panel desciption to be read in conjunction with the Single line diagram (SLD).Supply,Installation,Testing & Commissioning all complete |
| 159 | METER BOX(FOR SECOND FLOOR)Supply and erecting meter box suitable for three phase CT Operated energy meter and incoming FP MCCB,100A,25 Ka (Thermal release), fabricated out of 16 SWG sheet steel, powder coated, complete as required and conforming to the requirements of Goa Electricity Deaprtment.Supply,Installation,Testing & Commissioning all complete |
| 160 | SUB DISTRIBUTION PANEL(SECOND FLOOR) Sub distribution panel consisting of: 1)Mains Incomer:i) MCCB, TP, 100A, 415 volts, 36KA with Thermal magnetic release, spreader links,phase barriers, rotary handle-1 no.2) Indications & Metering:i) RYB LED Indicating lamps backed up by 3 Nos. ofMCB, SP, 2A MCB.ii) Panel mounted compact Multifunction meter for Voltage, Current, Frequency,KW, PF & KWH with DATA port protected by MCB,4P, 2Aand fed from 3 Nos. of CTs, 100/5 A, 15VA, CL-1.0.2)DG Incomer:i) MCCB, TP, 100A, 415 volts, 36KA with Thermal magnetic release, spreader links,phase barriers, rotary handle-1 no.2) Indications & Metering:i) RYB LED Indicating lamps backed up by 3 Nos. ofMCB, SP, 2A MCB.ii) Panel mounted compact Multifunction meter for Voltage, Current, Frequency,KW, PF & KWH with DATA port protected by MCB,4P, 2Aand fed from 3 Nos. of CTs, 40/5 A, 15VA, CL-1.0. 3) Motor Operated Switch (MOS):Comprising of MOS, 4P, 63Aalong with associated control circuitry with LVM to sense quality of available GEB supply and make suitable automatic changeoverto Mains/DG. And stay at OFF position if good power from either side (Mains & DG) is not avaiable.Compartment shall have visual indication of Load on Mains / DG or OFF depending of the status of ATS. ATS shall also have manual facility to selectively turn to desiredposition by handle.Normal Busbar:100 A TPN Al.Busbar.Outgoings:MCB, DP, 25A, 230V, 10KA-1 no.MCB, TP, 25A, 415V, 10KA-1 no.MCB, TP, 32A, 415V, 10KA-1 no.MCB, TP, 50A, 415V, 10KA-2 nos.Common Busbar:100 A TPN Al.Busbar.Outgoings:MCB, DP, 25A, 230V, 10KA-1 no.MCB, TP, 25A, 415V, 10KA-3 nos.MCB, TP, 63A, 415V, 10KA-1 no.N.B. : 1) Panel to have sealing arrangement in GEB incomer feeder 2) Panel desciption to be read in conjunction with the Single line diagram (SLD). |
| 161 | Supply,Installation,Testing & Commissioning all complete |
| 162 | LT CABLES |
| 163 | Supply of3 1/2 core armoured PVC insulated, PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) ,IS:7098(Part I) with latest amendments of following size.3 1/2 Core 50 sq.mm |
| 164 | Laying of one number additional PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground in the same trench in one tier horizontal formaion including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required. |
| 165 | (b) In rocky strata |
| 166 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm in the existing masonry open duct,etc.complete as required |
| 167 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, completeas required. |
| 168 | (3) 3 1/2x 50 Sq. mm. |
| 169 | Supplying and fixing following way SPN sheet steel MCB distribution board 240 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted ncluding earthing etc. as required ( but without MCB/RCCB/Isolator) |
| 170 | 8 way double door Cat A |
| 171 | Supplying and fixing following way TPN sheet steel, double door, Horizontal type MCB distribution board 415 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted including earthing etc. as required ( but without MCB/RCCB/Isolator) |
| 172 | 4 way (4+12), double door, Horizontal type Cat A |
| 173 | Supplying and fixing 6 A to 32 A,C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required. |
| 174 | SP, Cat A |
| 175 | DP,Cat A |
| 176 | TP, Cat A |
| 177 | Supplying and fixing 50 A,C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required. |
| 178 | (d) TP, Cat A |
| 179 | Supplying & erecting original 1.25 mm CRCA sheet metalenclosures with 20A. 2 pin plug & earth socket and 20A. 3 pinplug top with 20A/30A single pole MCB complete erected onangle iron/ GI frame. |
| 180 | Supplying & erecting CRCA sheet metal one way enclosures suitable for DP MCB /TP MCB /FP MCB erected on angle iron/GI frame omplete. |
| 181 | Supplying and fixing of following sizes ofrigid PVC conduit alongwith accessories in surface(medium)/recess(heavy) includingcutting the wall and making good the same in case of recessed conduit as required. |
| 182 | (a) 20 mm |
| 183 | (b) 25 mm |
| 184 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in the independent recessed PVC conduit(heavy) of appropriate size as required. |
| 185 | (b) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earthwire (20mm Conduit) |
| 186 | (c) 2 x 4 sq.mm + 1 x 4 sq.mm earthwire (20mm Conduit) |
| 187 | (i) 4 x 4 sq.mm + 2 x 4 sq.mm earthwire (25mm Conduit) |
| 188 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed PVC conduit(heavy) with modular switch, modular plates,suitable size modular GI box of specified Category and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 189 | (f) Group C-- with Cat B Modular Accessories |
| 190 | Wiring for group controlled light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed PVC conduit(heavy)and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 191 | Supplying and fixing 3 pin 5 A ceiling rose on the existing junction box/ wooden block including connections etc as required. |
| 192 | Supplying and fixing stepped type electronic fan regulator on the existing modularplate switch box including connections but excluding modular plate etc. as required (Cat B) |
| 193 | (b) Cat B |
| 194 | Supplying and fixing suitable size modular GI box with modular plate and coverin front on surface or in recess including providing and fixing 3 pin 5/6 Amodular socket outlet and5/ 6 Amodular switch connection painting etc. as required.( For light points to be used in non residential buildings) Cat B |
| 195 | (b) Cat B |
| 196 | Supplying and fixing suitable size modular GI box with modular plate and coverin front on surface or in recess including providing and fixing 6 pin 15/16 A and 5/6 A modular socket outlet modular socket outlet and15/16 Amodular switch connection painting etc. as required. |
| 197 | (b) Cat B |
| 198 | Supply and erecting fan hook box ( 100 mm diameter or equivalent square size, 75mm deep) fabricated out of 16 SWG sheet steel with 10 m round bar hook bounded to RCC steel upto 50 mm length protruding on each side of the box, including painting with 2 coats of red oxide, complete as required |
| 199 | Supplying, installation and testing of suitable size modular GI box , modular plate and cover complete with RJ-11 connector(modular telephone socket) including concealed metal box/surface GI/PVC Box, modular plate, punching, identifying, complete as required. |
| 200 | CAT B |
| 201 | Supplying and drawing/fixing indoor type 0.5 sq.mm FR PVC insulated copper conductor unarmoured telephone cable ITD/DOT approved, with GI saddles on wall or in the existing surface/recesed steel/PVC conduit having following pair(s), complete as required. |
| 202 | 2 Pair |
| 203 | Supplying and drawing/fixing jelly filled outdoor type armoured telephone cable with0.5 sq.mm dia. tinned copper conductor, ITD/DOT approved, with GI saddles on wal or in the existing surface/recesed steel/PVC conduit having following pair(s), complete as required |
| 204 | 20 Pair |
| 205 | Supplying, installing, testing and commissioning of Junction Box, ITD/DOT approved, indoor type with wall mounting/concealed facility having front door with lock along with aluminium frame for mounting disconnection type Krone modules, complete cabinetfabricated from 18 SWG CRCA sheet with powder coating in appropriate manner and suitable for following capacity of pairs including krone make modules, crimping and terminations, etc complete as required. |
| 206 | (b) 20 Pair |
| 207 | Supplying and drawing of Cat - 6 UTP, 4 pair annealed tinned copper conductor PVC insulated, PVC sheathed, unarmoured data cable in existing surface/recessed steel/PVC conduit of appropriate size including connection, etc. complete as required |
| 208 | (a) Cat 6 |
| 209 | Supplying and fixing of following sizes ofrigid PVC conduit alongwith accessories in surface(medium)/recess(heavy) includingcutting the wall and making good the same in case of recessed conduit as required. |
| 210 | 20 mm |
| 211 | Supplying and erecting LED square / circular 9 to 12W down lighter having pressure die-cast aluminium housing, opaltranslucent cover, mounting arrangement with board for surfacetype or spring loaded mounting clips for flush type complete. |
| 212 | Supplying & erecting LED 20W tube light fitting (4 feet) withaluminium housing, heat sink, integrated HF electronic drivercomplete. |
| 213 | Supplying and erecting square shaped CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) 600x600mm suitable for 36 W-40W with provision for plane front frame with translucent cover fixed to the housing complete. |
| 214 | Supply and erecting of 48 inch ( 1200mm sweep) ceiling fan, double ball bearing type, , complete with all accessories. |
| 215 | (a) Cat A |
| 216 | Supplying and fixing extra down rod of 20 cm length GI pipe 15 cm dia heavy gauge including painting etc as required |
| 217 | Supply and erecting of 9 inch (225 mm sweep) exhaust fan with double ball bearings, 1400 rpm, complete with all accessories. |
| 218 | (a) Cat A |
| 219 | Supplying, installing, testing and commissioning split type room Air conditioning unit with variable speed Inverter technology 2.5 TR capacity with R410A/R32 refrigerant & copper condenser suitable to operate on 230/415V, 50cycles, A.C. supply having 1 no. of airhandling unit (Mega spilt) Hi-wall mounting type complete at position. specification no. AP-AC/SAC |
| 220 | SITC of Electric Traction Passenger Lift with• Rated capacity :- 6 Passenger/408Kg• Floors :- G+2 floor (3Stops/3 Landings)• Travel :- 3 to 4.2 mtrs• Location of Lift Machine:- MR/MRL• Rated speed :- 1.0mps VS• Doors type :- COPO/TOPO Doors with frame having clearopening of 800 mm wide x 2000mm high made from SS 304grade sheet of 1.5mm, thick in hairline finish for car and alllanding doors with SS door architraves/frames• Lift car enclosure made from SS 304 grade sheet of 1.5mm, thickwith hairline finish with frame made from MS girders, bracing ofadequate size with minimum safety factor of 5, with Toe GuardApron, with necessary false ceiling with adequate LED lights,blower/fan for ventilation & SS chequered plate flooring,handrails, mirror, emergency light etc. |
| 221 | • COP with SS face plate having metallic push buttons with BrailleCode & luminous indicator around button with FPI, scrollingUP/DN LED indicator & with/without attendant key switch,OWD with audio-visual alarm, VAS in Marathi, Hindi & Englishwith intercom system with telephone instrument in Lift car, LMR& FCC/ground floor• Clear Car size of ......mm wide x ......mm deep x ......mmhigh• LOP with SS face plate having recess/surface push button boxfor all landings with scrolling UP/DN LED indicator havingmetallic push buttons with Braille Code & luminous indicatoraround button with CPI, Lift car arrival & next travel directionaudio-visual indication at all landings• Lift controller based on microprocessor/ PLC with VVVF Drivehaving closed loop control system, with IBMS compatible havingnecessary port, control panel duly wired with proper size &strength copper wire for power & control circuit, with provisionfor addition of floor / control card & allied accessories controlpanel having enclosure of 1.5mm CRCA sheet with powdercoating with IP54 Protection class |
| 222 | • ARD complete with necessary SMF VRLA batteries• Fireman controller having fireman switch at fire Landing,• CCTV surveillance system comprises of 2nos minimum 2.0MPFHD IP based vandal proof Dome camera in lift car & inLMR/inside lift shaft top aimed on Lift machinery & controllerwith NVR kept in LMR/FCC with HDR data backup for 60days with 18\" FHD TV monitor, to be kept in FCC/LMR asdirected by Engineer In Charge.• Lift Machine of Gearless PMSM of suitable kW with Tractionpulley, OSG, electromagnetic brakes, entire assembly mountedon adequate size girders duly fixed on LMR floor/ shaft wallscomplete with main/diverter traction sheaves, suspension wireropes/belts of adequate size & strength• Other mechanical parts such as \"T\" section adequate size guiderails for car & counter weight with brackets fasteners, counterweight frame with necessary blocks, buffers with necessarysupport arrangement, MS pit ladder etc. erected with necessarysteel work |
| 223 | Add On |
| 224 | For Lift travelling up to six floors at a speed of 1.0 mps, add as |
| 225 | below, |
| 226 | For Lift having 800mm wide x 2000mm high clear entrance in1.5mm thick SS 304 grade landing door [Two panel], this includes allnecessary accessories like LOP\"s with UP/DN buttons-arrowsindicators,extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landingdoors with all accessories etc. necessary for the normal safefunctioning of lift installation complete |
| 227 | FRP fencing complete with gate as per specification for Distribution transformer size (4M X 3M X 2M) with concreting for FRP fencing supports with plinth (0.3 x 0.3 x 0.5) cu.m. x 12 nos. Each ratio 1:3:6 |
| 228 | 11 KV, 630 Amps, outdoor, SF6 Ring Main Unit with two motor operated Load Break Switches and one Circuit Breaker with electrical closing and tripping SCADA compatible. |
| 229 | Providing and laying in position cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded granitic or basaltic stone agreegrate 40 m nominal size for foundations. |
| 230 | Centering and shuttering including struttings, propping etc and removal of formwork |
| 231 | 12 mm cement plaster 1:4 (1-cement: 4- fine sand ) for foundations. |