Military Engineer Services-MES has published Tender For Repair/Maint Of Water Supply Lines, Control Valves, Valve Pits, Other Connected Items Including Comprehensive Repair/ Maint Of Security Lights, Solar Lights, Junction Box, Timer Switch And Connected Cables At Akhnoor Under Ge (North) Akhno. Submission Date for this Tender is 01-03-2024. Distribution Box Tenders in akhnoor Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-Feb-2024 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 01-03-2024 |
Sl. No. | Item Description |
1 | Supply, laying in replacement, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor, 1100 Volt grade, cross sectional area 10 sqmm 2 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
2 | Supply, laying in replacement, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor, 1100 Volt grade, cross sectional area 10 sqmm 4 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
3 | Supply, laying in replacement, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor, 1100 Volt grade, cross sectional area 16 sqmm 4 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
4 | Taking down old unsvstreet lights of any descriptionand M&L for 90 WattLED street light fitting made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOPopening seperate driver compartment with IP66 protection and impact resistance of IK07 and making connection with copper flexible cable of suitable size to light fitting fixed, complete all as specified and directed. Cat part No;- ENDURAOMNIPLUSSL90WLED757SASYTOPC of Make Havells or equivalent cat part of Make as specified in list of make here in after as spproved by GE.. |
5 | Taking down old unsvstreet lights of any description and M&L for 60 WattLED street light fitting made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOPopening seperate driver compartment with IP66 protection and impact resistance of IK07 and making connection with copper flexible cable of suitable size to light fitting fixed, complete all as specified and directed. Cat part No;- ENDURAOMNIPLUSSL60WLED757SASYTOPC of Make Havells or equivalent cat part of Make as specified in list of make here in after as spproved by GE.. |
6 | Supply and fixing in replacement “Lithium based Energy Efficient Integrated Solar Street Light of 24 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 53/55Wp , Lithium Battery 11.1/12.8V, 28.6AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 12-14kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant. CAT part No- SOLAR AIO 24 W ofMake Havells or equivalent cat part of Make as specified in list of make here in after as spproved by GE.. |
7 | Taking down old unsvstreet lights and M&L for 50 WattLED street light fitting made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens with Toughned Glass having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK07 and making connection with copper flexible cable of suitable size to light fitting fixed, complete all as specified and directed. Cat part No;- ENDURASUNDOWNSL45WLED765PASYBOTG of Make Havells or equivalent cat part of Make as specified in list of make here in after as spproved by GE.. |
8 | Taking down old/unsv flood lights from high mast light of any type and M&L for LED flood light of capacity100 watt built withdie-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lightingand making connection with copper flexible cable of suitable size to light fitting fixed, complete all as specified and directed. Cat part No;- JETAALBAFLOODLIGHT100W of Make Havells or equivalent cat part of Make as specified in list of make here in after as spproved by GE.. |
9 | Street light bracket of G.I. pipe light grade 32mm bore 1.5 mr long made to shape as required fixed on wall or pole with FI clamp of required shap & 40x6mm siize, nut, bolts, washers, complete all as specified and directed. |
10 | Flat aluminium cablesize 2.5 sqmm x 2 core required for street light connection incl PVC Conduit with & includingtaking down burnt cable of any size, complete all as specified and directed. |
11 | Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 meters deep below ground level) with top edge of plate not less than 1.5 metres belowground level, connected to and including galvanised iron wire 4 mm dia and light grade protection pipeof 15 mm diafrom earth electrode up to test point or up to 7.5mtr whichever is less by means of GIbolts, nuts, check nuts and washersall as per electrical plate No 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including charcoal, salt packed all around the earth electrode plate in layers, PCC earth pit chamber 1:3:6 type C1, of size 45cm x 45cm x 45 cm,RCC cover 1:2:4 type B1 of size 45x45x6 cm, excavation/earth work in any strata and returning filling, removal of surplus soil and testing/test point for required valueincluding removing old item completeall as specified and directed. Note:-The required resistance of Earthing shall be less than 3 ohm, If not found to the required resisstance, the contractor has to re earthingfor required resistance andthe cost for the same included in the quoted rate and no extra shall be paid on failure of getting required resistance. |
12 | Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sectionsincluding nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shapeor size as indicated or directed and inclusive of one primer coat, oneunder coat and one finishing coat of paint all as specified and directed. |
13 | Excavation in trenches n. exc.1.5m wide and n. exc. 1.5m in depth for foundationof pole,laying of pipe line and getting out in any type of soil complete all as specified and directed by the Engr-in-Charge |
14 | Returining filling in including spreading, levelling, watering and wall ramming in layers not exc 25cm in any type of soil complete all as specified and directed. |
15 | Removal of excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed. |
16 | Supply and laying sub class `B` bricks laid dry flat transversely along the length of cable with width equal to the length of bricks over sand cushioning as protection cover of cable laid, complete all as specified and directed. |
17 | Sand cushioning to under ground cable, 8 cms thick before laying the cable and 15 cms thick after laying and stretching the cable in trenches including hand punning and consolidating, punned to 18cm thickness, complete all as specified and directed. Note : For payment purpose, only punned thickness shall be measured. |
18 | Replacement of GI water tubing 15mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches, complete all as specified and as directed. |
19 | Replacement of GI water tubing 20 mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches,complete all as specified and as directed. |
20 | Replacement of GI water tubing 25 mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches,complete all as specified and as directed. |
21 | Replacement of GI water tubing 40 mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches,complete all as specified and as directed. |
22 | Replacement of GI water tubing 50 mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches,complete all as specified and as directed. |
23 | Replacement of GI water tubing 80 mm bore "medium grade", galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches,complete all as specified and as directed. |
24 | Construction of valve pit ofsizes 120cmx120cmx120cm (internal dimentions),any type soil, returning, filling in, disposal of surplus spoil to a distance not exceeding 50m and depositing where directed, 100mm thick PCC in foundation of the mix (1:4:8), type D-2, (using 40mm graded crushed stone aggregate) brick masonry in cement mortar (1:4), rendering, 12 mm thick cement mortar (1:4) internally, finished even and fair & pointing flush externaly as the work proceeds in the same mortar, mild steel frame 40x40x5mm, MS sheet cover 3.15mm thick with handle and locking arrangement, painting all the exposed MS work with two coats of synthetic enamel paint of the tint as approved by the GE over a coat of red oxide primer and painting all the MS embedded in PCC1:2:4 type B-1 copingwith two coats of black bituminous paint, complete all as specified. |
25 | Construction of valve pit ofsizes 90cmx90cmx90cm (internal dimentions),any type soil, returning, filling in, disposal of surplus spoil to a distance not exceeding 50m and depositing where directed, 100mm thick PCC in foundation of the mix (1:4:8), type D-2, (using 40mm graded crushed stone aggregate) brick masonry in cement mortar (1:4), rendering, 12 mm thick cement mortar (1:4) internally, finished even and fair & pointing flush externaly as the work proceeds in the same mortar, mild steel frame 40x40x5mm, MS sheet cover 3.15mm thick with handle and locking arrangement, painting all the exposed MS work with two coats of synthetic enamel paint of the tint as approved by the GE over a coat of red oxide primer and painting all the MS embedded in PCC1:2:4 type B-1 copingwith two coats of black bituminous paint, complete all as specified. |
26 | Taking down old unsv sluice valve and Supply and fixing ball valve having SS ball with both CI end flanged, ISI marked, with nuts,bolts and washers and rubber gaskets with stainless steel handle over PVC coating complete all as specified and directed for following bore pipe:- |
27 | 150mm dia |
28 | 100mm dia |
29 | 80mm dia |
30 | 50mm dia |
31 | Taking down old unsv Non return valve and Supply and fixing non return valve heavy duty both ends flanged ISI marked complete with nuts, bolts washers etc complete all as specified and directed of following sizes:- |
32 | 150mm dia |
33 | 100mm dia |
34 | Taking out old unsv Ball valve and supply and fixing for ball brass valves,high pressure,with polythene float and flynut complete, screwed for iron pipe or brass ferrule and fixed complete of sizes :- |
35 | 15mm bore of pipe |
36 | 20mm bore of pipe |
37 | 25mm bore of pipe |
38 | 40mm bore of pipe |
39 | 50mm bore of pipe |
40 | Surface excavation n exc 30cm deep and averaging 15 cm deep and getting out in any type of soil, complete all as specified and directed. |
41 | Rolling and consolidating of soling of broken bouldersnot exceeding 15cm thick with power roller exc 5 tonne and nexc 8 Tonne, complete all as specified and directed.. |
42 | Hardcore of broken stone or boulder of guage exc 63mm but n exc 100mm deposited, spread and levelled in layers n exc 15cm thick, watered and rolled/rammed to a true surface, complete all as specified and directed.. |
43 | Cement concrete type D2 1:4:8 using 40 mm graded crushed stone aggregate as in foundation filling and mass concrete, complete all as specified and directed. |
44 | PCC 1:2:4, type B-1 (using 20mm graded crushed stone aggregate), in roof kerbs or mud stops, filling in electric pole installation, protection for interlocking paver blocks,rounded or chamfered angles and edges, including necessary form work complete all as specified and directed. |
45 | Machine pressed precast concrete interlocking paver block (ISI marked) any shape and size confirming to IS 15658-2006 of 60mm thickness with grey cement and pigment M35 Grade, complete all as specified and directed. |
46 | 25 mm thick sand filling under floors or in foundation including watering and consolidation for laying inter locking tiles/paver blocks, complete all as specified. |
47 | Supply and fixing Glow sign board made of flex glow sign board fixed on 0.50mm thick & 12cm wide PGI sheet frame box reactangular in shapehaving LED lighting arrangement of superior quality of 20watt showing installation Nomenclature as approvedmarked with & including prewired with copper wiring of required size, completeall as specified and directed. Note: (i) Installation line diagram to be enfaced will be approved by AGE E/M and no extra will be paid of any addition and alteration of words or marking of colours. (ii) Frame work for fixing sign board shall be measured & paid under respective item. |
48 | Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary , gusset plates, riveting etc n exc 10 Kg each brackets, conforming to Fe.290. Gde E-165 (Brackets over 10 Kg each to be measured under "Structural Steel"), complete all as specified and directed. Note-(i) Quoted rate shall also include cost of fabrication and fixing at site. (ii) Earthwork & PCC shall be measured & paid seperately under respective item. |
49 | Surface dressing in any type of soil n exc averaging 15cm deep for cleaning the area by cutting the unwanted bushes/vegitation growth in and around the area of installations/around the valve pit chamber/along the pipe line route if required etc all as specified and directed. |
50 | Preparation of new or previously untreated steel surfaces of any description over 10cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy