Tender For Miscellaneous Repairs To Electric Supply System Capacitor Panel High Mast Amf Panel And Allied Works Under Age E/M No-Ii Of Ge (U) Secunderabad, Hyderabad-Telangana

Military Engineer Services-MES has published Tender For Miscellaneous Repairs To Electric Supply System Capacitor Panel High Mast Amf Panel And Allied Works Under Age E/M No-Ii Of Ge (U) Secunderabad. Submission Date for this Tender is 28-02-2024. Electrical Panel Tenders in Hyderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

41994969
Corrigendum : Tender For Miscellaneous Repairs To Electric Supply System Capacitor Panel High Mast Amf Panel And Allied Works Under Age E/M No-Ii Of Ge (U) Secunderabad
Open Tender
Indian
Telangana
Hyderabad
28-02-2024

Tender Details

Miscellaneous Repairs To Electric Supply System Capacitor Panel High Mast Amf Panel And Allied Works Under Age E / M No-Ii Of Ge ( U ) Secunderabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Feb-2024 AMENDMENT Other 21-02-2024
2 21-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

BOQ Items

NAME OF WORK : MISCELLANEOUS REPAIRS TO ELECTRIC SUPPLY SYSTEM, CAPACITOR PANEL, HIGH MAST, AMF PANEL AND ALLIED WORKS AT MCEME , DEPOT BN , EME RECORDS, NML, OHL ECO"s FALAKNAMA,AGAMAN AND ADJOINING AREA UNDER AGE E/M NO-II OF GE (U) SECUNDERABAD
Sl. No. Item Description
1M&L in replacement Spare coil of Power contactor MCX-43 of having capacity 400 Amps 4 pole 2NO +2NC complete all as specified and directed.
2M&L in replacement Spare coil of Power contactor MCX-42 of having capacity 360 Amps 4 pole 2NO +2NC complete all as specified and directed.
3M&L in replacement Power contactor MCX-43 of having capacity 400 Amps 4 pole 2NO +2NCcomplete all as specified and directed.
4M&L in replacement Power contactor MCX-42 of having capacity 360 Amps 4 pole 2NO +2NCcomplete all as specified and directed.
5M&L in replacement Power contactor MCX-34 of having capacity 255 Amps 4 pole 2NO +2NCcomplete all as specified and directed.
6Dismantling of cross arms of Ms channel of angle setion for issue of schedule ofcredit
7Dismantling of steel poles/ concrete poles of an site an location for issue of schedule of credit
8M&L for the following materials as in repairs/replacements complete all as specified and directed.
9Supply and stringing ACSR conductor ofany size forLT/HT over headlineconnections of squirrel/weasel/Mink as per site requirement including provision of aluminum biding wire complete .
10Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut,100mm height, 65mm dia for 1100 volts grade.
11Shackle type insulator, porcelain vitreous, white / brown / green,1100 Volts grade, 75mmheight&90 mmdiaincludinggalvanisedmildsteel strapof31 x 3 mm, 12 mm dia insulator bolt, washers& nuts.
12Loop type insulator porcelain vitreous white, brown or green with overall dimensions of 90 x 140 mm, clearance of hole 25.5 mm.
13M&L in replacement Off-Load changeover switch (In sheet steel enclosure), AC 21 (Side Handle), 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
14M&L in replacement On-Load changeover switch (In sheet steel enclosure), AC 23 (Side Handle), 4 pole of capacity 100 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
15M&L in replacement On-Load changeover switch (In sheet steel enclosure), AC 23 (Side Handle), 4 pole of capacity 63 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
16Supply & Replace MCCB along with both side spreader link and nut bolts of appropriate size(Conforms to IEC:60947-II/IS:13947-II) in exisitng LT Panel box/Feeder Pillar boxes (KIOSK),in MCCB DBsof capacity 315-400 Amps, 4 Pole, 35 KA, 415 Volt including disconnecting/taking out existing old unserviceable/burned MCCB complete all as specified and directed.
17All as per item No-12 here in before but of capacity 250 Amps, 4 pole, 36 KA
18All as per item No-12here in before but of capacity 200 Amps, 4 pole, 36 KA Note for Item 12 to14: Fixing of MCCB in existing panels including addition/alteration to sheet metal enclosure etc., and misc items required for fixing of MCCB"s are deemed to be included in the quoted rates.
19M&L in replacement for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional arealaid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminum conductor of following sizes complete all as specified and directed :-
204 core X 10 Sqmm
214 Core X 16 Sqmm
224 Core X 25 Sqmm
233.5 Core X 35 Sqmm
243.5 Core X 50 Sqmm
253.5 Core X 70 Sqmm
263.5 Core X 95 Sqmm
273.5 Core X 120 Sqmm
283.5 Core X 150 Sqmm
29Labour only for releasing the binding of ACSR conductor of LT / HT over head line from insulator, removing the jumper, connector, service wire, UG cable and restringing the existing ACSR conductor of any size, length, span upto desired sag and fixing the existing ACSR conductor on insulators by proper binding, jumper connection etc complete all as specified and directed. Notes:- (i)Single run of conductor will be measured as one unit which is deemed to be included in the quoted unit rate. (ii) Extra aluminum conductor required for jumpers and binding purpose is deemed to be included in the quoted unit rate.
30Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / densesoil complete all as specified and directed.
31All as per item No 17.00 here in before but depth above 1.5 m & below 3 m
32Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
33Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
34M&L filling riddled earth in trenches forcushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of sand cushion after punning down only shall be measured for payment.
35Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
36M&Lfor PCC 1:3:6 type C1 using 20mm graded aggregate set in cement mortar 1:4 as in coping/pedestals of poles including necessary form work complete and applying two coats of white wash to exposed surface of coping/platform complete all as specified and directed.
37M&Lfor PCC 1:3:6 type C2 using 40mm graded aggregate as in foundation, filling and mass concrete for pole / stay / post etc complete all as specified and directed.
38M&L brick protection with common burnt brick sub class ‘B’ of size 230x115x75mm for cable protection complete all as directed by Engr-in-charge.
39Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P including craneand safety equipments to complete the job.
40Cutting unaxious green growth and grass by manual labour or by machine at all 11 KV Electric Installation premises/around 2/4 Pole structure/along the boundary fencing and removing rubbish from the site of work complete all as specified and directed.
41M & L for cross arms, bracing supports clamps and back plates fabricated from structural steel section incl nuts, bolts washers, welding, bending cold or hot drilling holes for bolts in any shapes or size as directedincluding applying two coat of quality aluminum paint over one coat of red oxide primer and fixed over RCC Pole/ steel poles of any height complete all as specified and directed.
42Supplying, errecting and fixing newsteel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long)including painting with two coats of aluminum paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellowpaint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) widecomplete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
43M&L in replacement Pipe bracket for street light fitting made out of 40mm dia GI pipe, medium grade, tubing bend to shape, 1.5m long fixed to pole wall including provn of two sets of clamps made out of flat iron of size 40x6 mm including of provn of bolts, nuts and washers complete all as specified and directed.
44Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through jointwith jointing material and accessories suitable forLTUGcable of size16 to 50 Sqmm, 3.5 Core complete all as specified and directed.
45All as per item No 31 here in before but suitable foraluminium conductor cable of sizefrom 70 sqmm, 3.5 Coreto 95 Sqmm, 3.5 Core
46All as per item No 31 here in before but suitable foraluminium conductor cable of sizefrom 120 sqmm, 3.5 Coreto 185 Sqmm, 3.5 Core
47S&F in replacement includingconnecting and testingenergy saving,environmental friendly long life Varsatile pressure die cast aluminium alloy for housing (heat sink) with IP66 protection road way light fitting with high power LED as light source of capacity 90 watts with suitable driver andcable gland for maintaining ingress protection with Epoxy powder coated siemens grey finish after phosphochromate treatment, Tempered protective toughened glass,thermal shock and impact resistant fixed to the housing with SS screws , High efficiency long life LED chip in modules with lumen efficacy of >140 lm/W with PC lens and system lumen 6000. Powered by Built-in electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Phase to Phase protection, Over Voltage protection, Surge Voltage protection. CCT 5700, CRI>70, THD<10%, PF>.95, IP66, .Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +50 DEG.C; Input Supply Voltage Range:140-270 V, Frequency : 50-60 HZ, Driver safety requirement standards :IS 15885-2-13 complete.
48All as per item No-34 here in before but 100watts.
49S&Fin replacement LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting, with high power LED as light source of capacity 120 watts with suitable drivers etc and connecting with 4.0 Sqmm aluminium conductor PVC insulated twin core weather proof cable etc, fixing to wall/pole complete all as specified and directed. Note for Item 34 to 36: (i) Contractor has to produce LM-79/LM-80 certificate alonwith purchase vouchers and Guarantee certificate from Manufacturer. (ii) Surge protection of the driver should be 10 KVexcluding inbuit SPD
50All as per item No-36 here in before but 100 watts.
51Supply only LED Driver of similar wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS certifiedsuitable for60 to 72 watts LED street light/flood lights fittings of any makecomplete all as specified and directed.
52Supply only LED Driver of similar wattage with operating voltage inputac 85- 300 volt , pf> .95 asper IS 15885 with inbuilt surge protectionof minimum 5 kvand BIS certifiedsuitable for90 to 100 watts LED street light/flood light fittings of any makecomplete all as specified and directed.
53Supply and fixing lantren of dia 60 CMfor fixing of flood light,cap type to be fixed on the top of 9 m SP-31 Steel pole , made of MS pip medium gradedia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50X6 mm 8 nosincluding two coat of aliminium painting over a coat of redoxide primer complete all as directed
54Supply & lay heavy duty PVC insulated multi stranded Aluminum conductor 3 core of size 4 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
55Supply & lay heavy duty PVC insulated multi stranded Aluminum conductor twin core of size 6.0 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
56Supply & lay heavy duty PVC insulated multi stranded Aluminum conductor twin core of size 10.0 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
57Supply & lay GalvanisedIron tubing50mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified anddirected.
58All as per item No 44 above but GI tubing 80 mm bore.
59M&L cutting of road/hard standing upto a size not exceeding 20 cm in width and not exceeding 60 cm in depth for laying of LT UG cable/protection pipe line making good the disturbed portion so as to match existing finishing with PCC 1:2:4 type B1/cement mortar in CM (1:2) complete all as specified and directed
60M&L in replacementcable junction box thermoplastic body IP 66 , size 225mmx295mmx122mm suitable for helogen free and weather proof for out door installation with metric knockout for cable entry suitable for cable size 16-35 sqmm including clamp, lugs,cable terminal & 6-10 amps MCB complete all as specified and directed.
61Supply only powerfactor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
62All as per item No 48 above but 10 KVAR Capacitor Bank
63All as per item No 48 here-in-before but 20 KVAR Capacitor Bank
64All as per item No 48here-in-before but 25 KVAR Capacitor Bank
65S&F APFC relay etaCON M series with auto-set function 5 stage including taking down old unserviceable one complete all as specified and directed.
66All as per item No 52 here-in-before butAPFC relay with auto-set function 7 stage
67All as per item No 52 here-in-before butAPFC relay with auto-set function 8 stage
68Supply and fixing of automatic street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off >10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor along with suitable power contactors incoming outgoing MCBS SP andauto manual (sensor bypass selection option should be enclosed in a pole /wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 8 KW with circuit wiringmin 10 sq mm copper wire 63 Ampscontactorand suitable MCBs atboth positions at incoming and out goings of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt(4 nos)for fixing on pole / wallcomplete all as directed including taking down old one . Make : Model Number Swadeep-02 EC 5KW 3P or equivalent from Havells/Legrand as approved by GE.
69Supply and fixing automatic street light switch using infrared sensor based nature switch for automatic switching of street lights.Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off >10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs.The sensor along with suitable power contactors incoming outgoing MCBS SP andand automanual (sensor bypass selection option should be enclosed in a pole /wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 three phase load of 5 KW with Circuit wiring, 3 nos contactor,incoming outgoing MCB (3 nos)Make : Model Number Swadeep-02 EC 8KW 3P or equivalent as approved by Engr-in-charge
70Supply, Installation, test and Commissioningfactoryfabricated, out door type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheetwith projected Globe roof for rain water protection Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embededwith 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete withinternal connection with suitable size of cable ,cable lugs,and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installationcomplete all as specified and comprising of the following :–
71(a) Aluminium bas bar 300 amps- 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 200 amps ,415 volt ,36 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar AsIN COMING- 01 Nos (c) MCCB 100 amps ,415 volt ,25 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar AsOUT COMING- 02 Nos (d)MCCB 63 amps ,415 volt ,16 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar Asoutgoing- 02 Nos (e) Indicator LED Type for RYB set of 3 - 01 set (f) Voltmeter 0-500 Volt Digitalwith selector switch - 01 No (g) Ammeter 0 to 400 Amps amps Digital with CTs and selector switch - 01No (i) Control wiring with PVC insulated multi stranded copper conductor, insulators for busbar mounting3 Nos of suitable CT"s and accessories Note:(i) All Internal connectionbetween MCCB and Changeover and Bus bar shall be connected by aluminium strip of suitable size and capacity. (ii) All MCCB to be connected with both side Spreader Link. (iii) Cable alley to be provided for connection of outgoing cables The rate shall deemed to be include in the item rate
72Supply, Installation, test and Commissioningfactoryfabricated, out door type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheetwith projected Globe roof for rain water protection Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embededwith 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level comp -lete withinternal connection with suitable size of cable ,cable lugs,and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installationcomplete all as specified and comprising of the following :–
73(a) Aluminium bas bar 600 amps-4 nos, supported with suitable size of heavy duty porcelin stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 400 amps ,415 volt ,36 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar as incoming - 01 Nos (c)MCCB 200 amps ,415 volt ,25 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar asoutgoing- 02 Nos (d) MCCB 100 amps ,415 volt ,16 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar asoutgoing- 04 Nos (e) MCCB 63 amps ,415 volt ,16 KA Breaking capacity4 pole Electromagnetic releaseduly connected to Bus Bar asoutgoing- 01 No (e) Indicator LED Type for RYB set of 3 - 01 set (f) Voltmeter 0-500Volt Digitalwith selector switch - 01 No (g) Ammeter 0 to 400 Amps amps Digital with CTs and selector switch - 01No (h) Control wiring with PVC insulated multi stranded copper conductor, insulators for busbar mounting3 Nos of suitable CT"s and accessories Note: (i) All Internal connectionbetween MCCB and Changeover and Bus bar shall be connected by aluminium strip of suitable size and capacity. (ii) All MCCB to be connected with both side Spreader Link. (iii) Cable alley to be provided for connection of outgoing cables The rate shall deemed to be include in the item rate
74Supply, installing, testing and commissioning, factory made and tested,LT panel board outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar 600 Amps rating , 4 strips in 3 phase and half neutral fashion, the panel should be dust proof,made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incomming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- (a)MCCB4 pole adjustable, 400 Amp, 415 Volts 36KA -01 No (b)MCCB 3 pole adjustable,200 Amp, 415 Volts 25 KA - 02 Nos (c)MCCB 3 pole adjustable,100 Amp, 415 Volts 16 KA - 02 Nos (d)MCCB 3 pole adjustable,63 Amp, 415 Volts 16KA - 02 Nos (e)Indicating lamps (set 03 Nos)- 01 set (R,Y & B) (f) Digital Voltmeter, Ammeterthree phase class including CTs of suitable ratio with selector switch (g) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs.
75Supply, installing, testing and commissioning, factory made and tested, LT panel board outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar of suitablerating , 4 stripsin 3 phase and half neutral fashion, the panel should be dust proof, made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incomming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- (a)MCCB4 pole adjustable, 200 Amp, 415 Volts 25 KA -01 No (b)MCCB 3 pole adjustable,100 Amp, 415 Volts 16 KA - 02 Nos (c)MCCB 3 pole adjustable,63 Amp, 415 Volts 16 KA - 01 Nos (d)MCB 3 pole adjustable,32 Amp, 415 Volts 10 KA - 08 Nos (e)Indicating lamps (set 03 Nos)- 01 set (R,Y & B) (f) Digital Voltmeter, Ammeterthree phase class including CTs of suitableratio with selector switch (g) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs.
76Supply, Installation, test and Commissioning factoryfabricated, outdoor type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheet of suitablesizewith projected Globe roof for rain water protection Dust and Vermin Proof ,Double door withboth side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeddedwith 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete withinternal connection with suitable size of cable ,cable lugs, and cable glandsPCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and comprising of the following :– (a) Aluminium bas bar of suitable rating - 04 Nosin 3 phase and half neutral fashion, supported with suitable size of heavy duty porcelain stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 100amps, 415 volt,16 KA Breaking capacity4 pole Electromagnetic release duly connected to Bus Bar asIN COMING- 01 Nos
77Advance Maintenance Free G.I. SAFE EARTHINGElectrodewith PIPEof not less than 50 mm outer dia) and two meterlength, The electrode should be ofgalvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm7.5 m . The GI Electrode shall be pre-filled with Crystalline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg Backfill compoundto provide maximum contact between the electrode and Back Fill Compound.connected to earthing test point including excavation, earth work, PCC pit, RCC cover 50 mm thick, lifting rod andtesting on completion, complete all as specified and directed.Make: ASHLOK/GRAVIN/TRUE POWER/JVM
78S&F cable route indicator for LT UG cable of 1100 volts bolted with 25x5 mm flate iron member of height 0.60 mtrs and 80 mm CI plate embeded in PCC 1:3:6 type C2 of size 15x15x20 cm block complete all as specified
79M&L for repairing/Servcing of automatic operation of highmast lantren including all arrangements required including crane and replacement of all unserviceable spares of highmast lighting system of height 12 m to 16 meter . Quoted rates deemed to be inclusive ofthe following:- (i) crane as required for taking down of high mast pole including light without any damage to the mast, lantern and lights etc and refixing the same after repairing of the all problem on the same position (ii) Necessary disconnection and reconnection of electrical connection. (iii) Replacement of all unserviceable sparelikeHigh mast head, high mast ring , stainless steelwire, clamp, winch, transition plate, service door , Hook ring, nose plate, cabinet, gear, reel, transmission belt etc including servicing of gear box , filling of gear oil, greasing etc complete(quoted rates deemed to be inclusive of all spares required for proper functioning of lantern system except stainless steel wire, High mast head, high mast ring etc.
80All as per item No 65 here in before but for highmast system above 16.5 meter and upto 25 meter
81Supply only steel wire rope 6mm dia (7/19 construction)suitable for highmast system including u bolt complete all as directed
82Taking down, transport to workshop , Re-winding of electric motor 3 phase installed at highmast pole of capacity 2.2/3 HPand refixing of the same including necessary arrangement complete all as directed
83Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 100 KVARs and up 8 stages installed atvarious locations at MCEME area including carrying out complete maintenance/repairs as required of all the sub systems viz. basedcontrol panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT,MCBs/MCCBs for isolation (with all the accessoires) anybreakdownmaintenance and replacement of unserviceable parts, refixingof old serviceable parts/new parts if anyproject completionand trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, repavement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etcand necessary servicing repair by expert technician and register will be maintaned for the same. (ii)The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCBshall be measured and paid seperatly
84Supply anfd fix locally available gate / garden light of best qualitymetal Silver / metal blackDecorative Exterior of size not less than 300 mm X220 mm with and including LED bulb 9 wattsuitable for outdoor installationandsuitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directedincluding taking down old one .
85Material and labour for Taking down UNSV LED Lights and removing Carbon from its connector joints incl replacement of Connecting wire with new PVC sheated weatherproof 3Xsingle core cable for electrical connection and refixing the fittingafter repair to its original/New location or as directed by engr-in-charge.(connecting wire will be measured and paid separately only)
86Supply anfd fix locally available Acrylic globe light best quality clear with and including LED bulb 9 watt of 200 mm dia complete suitable for fixing in 40/50 mm dia GI pipe including necessary connections complete all as specified and directed including taking down old one .
87M&L for painting the existing LT steel poles of 9.0 Mtr long including cross arms, clamps, street light junction boxes etc with 1 coats of aluminium paintincluding throughly cleaning the existing surface, writing of pole numbers in yellow circle 15 cm with black paint on poles. Painting the poles up to 1.5 Mtr height with alternate bands 30 cm height (3 Nos black and 2 Nos Yellow) from ground level, complete all as specified and directed.
88M&L for Painting the existing LT PCCpoles with 1 coats of synthetic enamle base paintincluding painting of cross arms, clamps, etc with one coat of aluminium paint and providing alternative band of 30 cm width (3 black and 2 yellow) from bottom of pole to 1.5 metres height , writing of pole numbers in yellow circle15 cm with black paint on poles complete all as specified and directed.
89S&F MCCBfactory made enclosure box with neutral link for TPN System made of sheet metal Powder coated Suitable for fixing at Pole including two set of clampscomprising with the following i) MCCB63 Amps 16 KA TP .
90S&F MCCBfactory made enclosure box with neutral link for TPN System made of sheet metal Powder coated Suitable for fixing at Pole including two set of clampscomprising with the following i) MCCB100 Amps 16 KA TP .
91Dismentling ofdamage / broken coping of PCC/steel pole of any size and and removing the debries from site complete all as specified and directed
92Supply and fixon wall with necessary arrangements busbar chamber 100 amps 4 way4 polewall mounted IP -31 , made out of 1.6 mmthick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Secondincluding necessary cable connectionscompleteall as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber.
93Supply and fixon wall with necessary arrangements busbar chamber 200 amps 4 way4 polewall mounted IP -31 , made out of 1.6 mmthick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Secondincluding necessary cable connectionscompleteall as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections, cable glands as required for proper fixing / functioning of Bus Bar Chamber.
94Replacement of transformer/LT Panel Boards End covers with suitable size of MS Sheet of 2mm thick including drilling holes as per existing transformer/LT Panel end cover, painting with 1 coat of red oxide primer and two coats of synthetic enamel paint and fixing with suitable size of nuts and bolts, hinges completecomplete all as specified.
95M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size Complete all as specified and as directed
96All as per item No 80 above but of HT 25x20 cm size
Disclaimer :