Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-02-2024 | CORRIGENDUM TO GENERAL SUMMARY | Other | 17-02-2024 |
| 2 | 07-02-2024 | CORRIGENDUM TO SCHEDULE OF CREDIT | Other | 17-02-2024 |
| 3 | 07-02-2024 | CORRIGENDUM TO BOQ | BOQ | 17-02-2024 |
| 4 | 07-02-2024 | CONTENTS PAGE | Other | 17-02-2024 |
| Sl. No. | Item Description |
| 1 | E/M WORKS |
| 2 | Taking down copper / aluminium point wiring (light, fan, socket or power) including fixture and fittings viz. switches, ceiling roses, light fittings, pendants, regulators, sockets, etc. and disposing off complete all as specified and as directed |
| 3 | M&L for point wiring with 1.5sqmm, single core, FRLS PVC insulated, ISI marked, unsheathed cable 1100V grade with multi-stranded copper conductor, drawn through and including non-metallic PVC casing capping not less than 25mm wide and accessories flush on walls, ceiling etc. and including provision of 1.5sqmm copper wire, green colour as earth continuity conductor and and terminal boxes duly connected to common earth dolly complete all as specified and as directed for the following: |
| 4 | One light point controlled by one 5A one way switch |
| 5 | One ceiling fan / exhaust fan point controlled by one 5A one way switch |
| 6 | One switch socket outlet 3 pin 5A controlled by one switch on independent board |
| 7 | One switch socket outlet 3 pin 5A controlled by one switch on same board |
| 8 | M&L for point wiring with 2.5sqmm, single core PVC FRLS insulated, heavy duty, ISI marked, unsheathed cable 1100V grade with multistranded copper conductor drawn through and including non-metallic PVC casing capping not less than 25mm wide and accessories, flush on walls / roofs / floors / ceiling etc. and PVC insulated heavy duty, ISI marked, unsheathed copper conductor 2.5sqmm for earth continuity conductor and terminal boxes duly connected to common earth dolly for one switch socket combination outlet 3 pin 15A multipurpose complete all as specified and as directed |
| 9 | S&F ceiling rose surface bakelite 65x50mm, ISI marked, with three terminals complete all as specified and as directed |
| 10 | S&F switch piano flush button type, single pole, ISI marked, one way 5A, 240V complete all as specified and as directed |
| 11 | S&F switch socket outlet, 2 in 1, 5A flush type, universal, ISI marked, 240V complete all as specified and as directed |
| 12 | S&F switch socket combination outlet, 5 in 1, 5 & 16A flush type, universal, ISI marked, 240V complete all as specified and as directed |
| 13 | S&F electronic fan regulator, stepped socket type (5 steps), 100W, 50Hz, 230V, ISI marked duly connected up complete all as specified and as directed |
| 14 | Taking down old unserviceable submain wiring of any type, any size, from any location or position and disposing off including making god the disturbed surfaces, etc. complete all as specified and as directed |
| 15 | M&L for submain wring using proper colour codingwith 2 runs of single core, PVC insulated,FRLS unsheathed suitable for 1100V, multistranded, copper conducter cable of size 10sqmm and 1 run of 10sqmm multistranded, copper conductor cable 1100V green colour for earth conductor drawn through and including PVC casing caping 20mm wide, heavy duty, ISI marked flush on wall/ceiling/roof, etc. with all required accessories complete all as specified and as directed |
| 16 | S&F heavy duty, PVC body with PVC blades, legs, ISI marked energy efficient, 230V, 50Hz, 1200RPM, exhaust fan, 300mm sweep with lauvers and connecting up including provision of three core flexible copper wire of size 1.5sqmm from ceiling rose to exhaust fan including grouting the nuts and bolts including taking down old / unserviceable fan any type and disposing off complete all as specified and as directed |
| 17 | S&F wall mounted compact 20W LED batten type fitting duly connected with 3 core flexible copper conductor cable of suitable size from ceiling rose including taking down and disposing off old unserviceable fitting complete all as specified and as directed |
| 18 | S&F LED street / building security light luminaire 25W, IP-66, withLED driver, etc. with all accessories prewired and 25W LED lamp including service bracket including taking down old / unserviceable fan any type and disposing off complete all as specified and as directed |
| 19 | S&F sheet metal enclosures double door, IP 43 protection class conforming to relevant IS, with 200A rated insulated aluminium bus bar, neutral link, DIN rail, blanking plates, etc. duly flushed/grouted in wall and making good the disturbed surfaces including taking down of old enclosure and disposing off complete all as specified and as directed for the following capacities: |
| 20 | 8 way MCB DB, 240V, SP |
| 21 | 4 way MCB DB, 240V, SP |
| 22 | S&F MCB SP, 240V, 5 to 32A, 10kA, 50Hz, C curve, complete all as specified and as directed |
| 23 | S&F MCB SPN, 240V, 40 to 63A, 10kA, 50Hz, C curve, complete all as specified and as directed |
| 24 | S&F in repairs the following items without disturbing existing wiring / fittings including making good the disturbed surfaces of wall/ceiling at any location / position complete all as specified and as directed |
| 25 | Switch piano flush button type, single pole, ISI marked, one way 5A, 240V |
| 26 | Electronic fan regulator, stepped socket type (5 steps), 100W, 50Hz, 230V, ISI marked |
| 27 | PVC / polycarbonate lamp holder, insulated body, bracket holder / angle holder with back plate 240V |
| 28 | Socket outlet, 2 in 1, 3 pin, 5A flush type, ISI marked, 240V |
| 29 | Switch socket combination outlet, 5 in 1, 3 pin, 5/16A flush type, ISI marked, 240V |
| 30 | S&F in repairs non-metallic rigid PVC casing capping 25mm wide with accessories complete all as specified and as directed |
| 31 | S&F 1100V grade heavy duty PVC insulated aluminium multistranded conductor cable, 2 core 10sqmm, served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hangers not more than 1m apart including 4mm suspension wire, two twin core cable flat or circular including taking down old unserviceable wire and disposing off complete all as specified and as directed |
| 32 | Maintenance, servicing and testing of oil fired Incinerator including replacement of defective and worn out filters, gaskets, V- belts, engine oil, rubber hoses, worm drive clamps, nuts, bolts and cleaning of alternator with vaccum cleaner, tappet settings if required and greasing of bearings of engine and alternator complete all as specified and as directedNotes: (a) Servicing shall be got done through authorized service centres of the OEM as approved(b) Spares required for repair other than mentioned above will be measured and paid seperately as listed here-in-after |
| 33 | M&L for taking out unseviceable / damaged parts from the incinerator with due care, and supply / fix the following original spare parts including carrying out all related minor maintenance and ovehauling works as per site requirement suitable for oil fired Incinerator complete all as specified and as directed: |
| 34 | Sequence controller LOA to the bentone burner |
| 35 | Solenoidal coil with cable |
| 36 | Photocell |
| 37 | M&L for overhauling the ID fan, blower, motor 5HP by repairing / replacing the damaged / worn out parts with new ones wherever required and testing on completion complete all as specified and as directed |
| 38 | M&L for preparation of surfaces of oil fired Incinerator by scrubbing off old treatment and painting the primary chamber, secondary chamber, steel scrubber tank, droplet, blower motor and exhaust motor system, including connecting pipe with two coats of synthetic enamel paint (of approved tint) over a coat of zinc chrome primer complete all as specified and as directed |
| 39 | S&F maintenance free lead acid battery 12V, 180Ah capacitywith brass terminals including testing on load including taking off old battery and disposing off complete all as specified and as directed |
| 40 | S&F maintenance free lead acid battery 12V, 190Ah capacitywith brass terminals including testing on load including taking off old battery and disposing off complete all as specified and as directed |
| 41 | Maintenance and servicing to DG sets including attending faults on call basis for normal repairs including replacement of defective and worn out parts/spares viz. filters, gaskets, V- belts, engine oil, rubber hoses, worm drive clamps, nuts, bolts and cleaning of alternator with vaccum cleaner and rectifying faults of AMF panels, etc. tappet settings if required and greasing of bearings of engine and alternator, checking of batteries, applying petroleum jelly to battery terminals, addingdistilledwater checking the oil, coolant levels complete all as specified and as directed of the following capacities:Notes: (i) All items viz. cleaning agent, cotton waste, grease, minor items such as washer, nuts, bolts etc are required for carrying out the normal maintenance of the engine, mechanic charges and any specialized machine work from outside workshop if requred shall be included in the quoted rates(ii) Fresh engine oil/spare parts for DG sets shall be measured and paid separately under respecitve items as detailed hereafter. Labour for such fixing shall be included in the quoted rates (iii) During maintenance/servicing of DG set, complete DG set shall be checked properly and all setting shall be done properly |
| 42 | Notes for item No. 41 contd...(iv) The maintenance/servicing of DG set by authorized service agency of authorised service center of Kirloskar/ Greaves Cotton only(v) Servicing shall be carried out after every 500hrs run or after 6months whichever is earlier(vi) Sites shall be at Masimpur and Kumbhirgram(vii) All the above shall be deemed to be included in the quuoted rate and no claim whatsoever shall be entertained |
| 43 | 125kVA |
| 44 | 82.5kVA |
| 45 | 63kVA |
| 46 | 62.5kVA |
| 47 | 45kVA |
| 48 | 25kVA |
| 49 | Supply only the following spare parts as per site requirement suitable for 125KVA capacity DG set complete all as specified |
| 50 | Engine oil in 20litres can |
| 51 | Spin on filter for lubricating oil |
| 52 | Fuel Filter Kit 1.1litre |
| 53 | Air cleaner element |
| 54 | Rubber Hose (Compressor outlet)-K24 Turbo |
| 55 | Fuel pipe (7.5,14x14B,700 WB) |
| 56 | Banjo bolt |
| 57 | Fuel pipe 8.0,14B, 1000WB |
| 58 | Primary element |
| 59 | Secondary element |
| 60 | Primary element (6H.411.02.0.00) |
| 61 | Poly V Belt |
| 62 | Poly V Belt for (7PK BelT) |
| 63 | Hose [Raditor to Water pump pipe (45x45x130L)] |
| 64 | Hose [Pipe to water pump (45x45x80L)] |
| 65 | Hose clip (54mm) |
| 66 | Drive Hose clip (70mm) |
| 67 | Copper washer (14x18mm) |
| 68 | Supply only the following spare parts as per site requirement suitable for 62.5/63KVA capacity DG set complete all as specified |
| 69 | Engine oil in 13litres can |
| 70 | Spin on filter for lubricating oil |
| 71 | Fuel filter element pre (Bosch Part No 14574) |
| 72 | Fuel filter element micro (Bosch Part No 9451) |
| 73 | Primary element (KKFL make KFA -02-1-7047 for KFA) |
| 74 | Secondary element (KKFL NOKFA -02-1-7048) |
| 75 | V Belt( XPA 1250) COGGD |
| 76 | LO supply hose (FIP) M10 Banjo Ends X235L |
| 77 | Hose radiator to water pump pipe |
| 78 | Hose clip (54mm) |
| 79 | Hose (pipe to water pump) |
| 80 | Worm drive hose clip (70mm) |
| 81 | Fuel pipe (7.5,14 x 14 B, 700 WB) |
| 82 | Copper washer(14x18mm) |
| 83 | Lube oil pressure sensor (sensor+switch), VDO |
| 84 | K934 controller with 4-20MA updated version V3.G.4 |
| 85 | 2 position selector actuator with element |
| 86 | Contact block P/B siemens |
| 87 | SS left hand hinges for canopy |
| 88 | Right hand hinge |
| 89 | Copper wire 1.5sqmm |
| 90 | Starter mico (Bosch) F002 G2 645/F002 G20 993 |
| 91 | Supply only the following spare parts as per site requirement suitable for 45KVA capacity DG set complete all as specified |
| 92 | Engine oil 13litres can |
| 93 | Spin on filter for lubricating oil |
| 94 | Fuel filter element pre (Bosch Part No 14574) |
| 95 | Fuel filter element Micro (Bosch Part No 9451) |
| 96 | Main element for air cleaner |
| 97 | V Belt( XPA 1250) COGGED |
| 98 | Hose radiator to water pump pipe(45x45x130L) |
| 99 | Hose (pipe to water pump) |
| 100 | Rubber hose (compressor outlet)-K24 Turbor |
| 101 | Hose clip (54mm) |
| 102 | Worm drive hose clip (70mm) |
| 103 | Fuel pipe (9.0,14x14B,520WB) |
| 104 | Copper washer(14x18mm) |
| 105 | Lube oil pressure sensor (Sensor+Switch), VDO |
| 106 | LO supply hose (FIP) M10 Banjo Ends X235L |
| 107 | Supply only the following spare parts as per site requirement suitable for 25KVA capacity DG set complete all as specified |
| 108 | Engine oil 5litres can |
| 109 | Fuel filter kit (0.5litre) |
| 110 | Main element for air cleaner |
| 111 | V Belt B 48 1262 Length |
| 112 | Hose (water pipe to adaptor) |
| 113 | Hose (radiator to water pipe) |
| 114 | Hose (radiator to thermostat) |
| 115 | Hose |
| 116 | Battery distilled water (2litres bottle) |
| 117 | Expansion belloe (two ply) |
| 118 | Copper washer(14x18) |
| 119 | Fuel pipe (7.5,14 x 14 B, 700 WB) |
| 120 | Hose clip (48mm) |
| 121 | Coolant premixed 10litres can |
| 122 | Coolant premixed 5litres can |
| 123 | V Belt B 47 1237 Length |
| 124 | Diesel tank cap |
| 125 | Thermostat element |
| 126 | Joint for thermostat cover |
| 127 | Water pump with spindle Brg. andUnitized seal |
| 128 | Anabond 666 25GM |
| 129 | Supply only petrolium jelly (1kg plastic sealed container) complete all as specifiedMake: Indian oil/ Hindustan Petrolium/ Castrol/ BPCL |
| 130 | Supply and filling distilled water for topping up in lead acid batteries complete all as specified and as directed |
| 131 | Supplying and filling electrolyte of suitable specific gravity for lead acid batteries in sealed containers complete all as specified and as directed |
| 132 | S&F battery comnnecting wire, copper, 1.5m long with 2Nos suitable clamps on one side and 2Nos lugs on other side of suitable sizes and fixed including taking out worn out battery clamp and connecting wire and disposing off complete all as specified as directed. |
| 133 | S&F battery terminal, brass clamps including removal of damaged terminal compete all as specified and as directed |
| 134 | M&L fordisconnecting all electrical connections from DG set25/45/62.5/63/125KVA, removing alternator from base plate by opening nuts & bolts taking out to workshop for rewinding (as per relevant IS) and reinstalling in position including testing and commissioning complete all as specified and as directed |
| 135 | M&L for repairing and calibration of FIP & injector including all necessary minor spare parts for DG Set 45kVA capacity complete all as specified and as directed |
| 136 | M&L for dismantling and taking out radiator and strip opening radiator assembly, for servicing mechanically, proper cleaning of tubes using de-scaling solution, including repair to water tubes and top/ bottom tanks by soldering / gas welding to check leakages of tubes/tanks including replacement of gasket, nut bolts, etc. ensuring perfect leak proof service, re-assembling and fixing the same in position and testing the system complete all as specified and as directed for the following capacities of DG sets of any make:Notes: The quoted rate shall include the following:(i) Fixing of serviceable parts in position and replacement of unserviceable spares with new spares (ii) Replacement of small/minor parts viz. nuts, bolts, washers, gaskets / packing, etc.(iii) Loading, unloading, carting to/fro to workshop(iv) Complete load testing after complete repair and re-installation as per relevant IS and as directed |
| 137 | 125kVA |
| 138 | 62.5/63kVA |
| 139 | 45kVA |
| 140 | 25kVA |
| 141 | M&L for taking out of unservicable self starter 12V of 62.5kVA installed at UAV Tps Kumbhigram and connected unserviceable spares of electric wiring and carring out repairs and overhauling the self starter, engine, replacing the armature, carbon brush, bearing, bendix penion, solenoid switch, bearing, tapping of field coil refixing of all components and refixing in existing position including testing complete all as specified and as directed |
| 142 | M&L for taking out of unservicable self starter 12V of 125kVA installed at GE Silchar Masimpur and connected unserviceable spares of electric wiring and carring out repairs and overhauling the self starter, engine, replacing the armature, carbon brush, bearing, bendix penion, solenoid switch, bearing, tapping of field coil refixing of all components and refixing in existing position including testing complete all as specified and as directed |
| 143 | S&F in repair battery charging circuit suitable for 12/24V, DC in existing DG set panel board including addition/ alteration in wiring system with auto transformer, diodes, filter circiut, condensors, DC ammeter, DC volt meter with selector switches and indicating bulbs, etc. complete all as specified and as directed |
| 144 | S&F AVR (automatic voltage regulator) control unitassembly suitable for 25kVA to 125kVA DG set including taking out old unserviceable AVR and dsiposin off compete all as specified and as directed |
| 145 | S&F in repairs fuel steel braided pipe with benjo bolts and washers, etc. of length 30cm compete all as specified and as directed |
| 146 | S&F in repairs fuel steel braided pipe with benjo bolts and washers, etc. of length 45cm compete all as specified and as directed |
| 147 | S&F digital ammeter of size 96x96mm flush monting type of capacity 0-100A with sufficient number of suitable sized CTs including taking out old unserviceable ammeter complete all as specified and directed |
| 148 | S&F digital voltmeter of size 96x96mm flush monting type of capacity 0-200V with sufficient number of suitable sized CTs including taking out old unserviceable voltmeter complete all as specified and directed |
| 149 | S&F power contactor ML -12, 2 NO + 2 NC along with 1 aux contact block 415V, 50Hz AC suitable for DG set control panel/ AMF panelincluding taking off old unserviceable power contactor compete all as specified and as directed |
| 150 | S&F power contactor MNX 70-2P along with 1 aux contact block 415V, 50Hz AC suitable for DG set control panel/ AMF panelincluding taking off old unserviceable power contactor compete all as specified and as directed |
| 151 | S&F power contactor MNX 225, 2 NO + 2 NC along with 1 aux contact block 415V, 50Hz AC suitable for DG set control panel/ AMF panelincluding taking off old unserviceable power contactor compete all as specified and as directed |
| 152 | S&F in repairs solinoid switch assembly 12/24V suitable for 25KVA DG set to 125KVA DG set compete all as specified and as directed |
| 153 | S&F solenoid valve suitable for the following capaities of DG sets including taking out old and testing for smooth functioning complete all specified and as directed |
| 154 | 45KVA to 63KVA |
| 155 | 125KVA |
| 156 | M&L for complete wiring of the DG set upto 125KVA with provisioning of additional auto cables, heavy duty, suitable for generator set applications including taking off old unserviceable wiring compete all as specified and as directed |
| 157 | M&L for overhauling engine of DG set capacity 125kVA by opening the top cover including dismatlling the engine head, cylinder liner and piston assembly, crankshaft assembly, radiator fan belt and radiator fan, gear assembly,repair / replacement of parts viz. gasket, washer, \"O\" ring all types, etc including grinding polishing of crank shaft, head repairing and overhauling valve seat cutting and replacing, valve tapping, fixing the head, reassembling the DG set and testing on full load as per relevant IS complete all as specified and as directedNotes: (i) Overhauling shall be got done through authorised service centres of OEM(ii) Cost of all necessary loading / unloading, carting, etc. for transorting to workshop (if required) shall be deemed to be included in quoted rate(iii) Spare parts will be measured and paid seperately under relevent items detailed hereafter |
| 158 | Supply only the following spare parts as per site requirement suitable for 125KVA capacity DG set at serial item No. 157 hereinabove complete all as specified |
| 159 | Cylinder liner with joint ring |
| 160 | Piston assembly complete |
| 161 | Piston ring set |
| 162 | Bearing main KIR 6R 1080 STD |
| 163 | KIR 4RTA C/G BRG, STD |
| 164 | Bearing bush |
| 165 | Oil seal |
| 166 | Plate with rubber moulding |
| 167 | Piston cooling nozzle assembly |
| 168 | Bolt for cylinder head |
| 169 | Gasket for cylinder head |
| 170 | Valve spring |
| 171 | Push rod (welded) |
| 172 | Lube oil pump assembly |
| 173 | Assembly for internal gear |
| 174 | Thermostat element |
| 175 | WP assembly with DEL volute |
| 176 | Set of joint 6R108OTA 125 KVA |
| 177 | Con rod assembly |
| 178 | Rubber hose (compressor outlet) K-24 Turbo |
| 179 | Hose for air cleaner |
| 180 | Coolant premixed |
| 181 | Supply, install, testing and commissioning in cubical indoor type AMF panel for DG sets conforming to IP-54 weather proof and vermin proof, powder coated, fabricated out of 2mm thick MS steel sheet with partitions, with switch enclosure doors of 1.6mm MS with minimum clearance of 750mm including all internal wiring with suitable copper cables and accessories all as per IS, with easy access and working condition, mounted on brick masonry pillars at a height of minimum 0.45m above GL, with both inside and outside control wiring with multi-stranded single core PVC flexible copper cable 1.1kV grade,1sqmm (2.5sqmm for CT cct) and power wiring with multistranded single core PVC copper cable 1.1kV grade of suitable size, with all necessary marking for identificatio of incoming andoutgoing CCT and earthing pillar box at 2 points & providing aluminium bus bar comprising of the followings with all accessories connected accessories including dismantling and disposing off old panel complete all as specified and as directed for the following capacities: |
| 182 | AMF panel for 125KVA DG set(a) Power contractor 4P, 36kA, 200A- 02Nos (b) Spreader link for 200A, 4P, MCCB- 02sets (c) Direct rotary handle for 200A 4P MCCB- 03 Nos (d) Auxiliary contact- 02Nos (e) 200A 4P Power contactor- 02Nos (f) C/T 200/5A CL 1- 03Nos (g) 20A fuse base 7Nos. (h) 2A Fuse link-03Nos. (j) 4A DP MCB-01No. (k) 6A DP MCB-01No. (l) VFA meter 150/5A- 01No. (m) AMF relay- 01No. (n) Analog type ammeter (0-30A)- 01No. (o) Analog type voltmeter (0-60V)-01No. (p) Hooter sif-96 (12V DC)-01No. (q) 6A DP 2 Way without selector switch (1-2)-01No. (r) 6A SP 1 Way ON/OFF selector switch-01No. (s) SMPS battery charger 230/12V DC-01No. (t) CO Pla Relay with bus 12V DC (12V DC)- 03Nos. (u) CO Pla relay 12V DC-02Nos. (v) LED type red indicating lamp (240V AC)-04Nos. (w) LED type yellow indicating lamp (220V AC)-01No. (x) LED type blue indicating lamp (220V AC)-01No. (y) 6A red push button NO element-01No. (z) 6A green push button- 01No. (aa) 6A NO element for push button-04Nos. (ab) 6A NC element for push button-02Nos. |
| 183 | AMF panel for 62.5KVA DG seta) Power contractor 4P, 36kA, 125A- 02Nos (b) Spreader link for 125A, 4P, MCCB-02sets (c) Direct rotary handle for 125A 4P MCCB- 02Nos (d) Auxiliary contact- 02Nos (e) 200A 4P Power contactor- 02Nos (f) C/T 150/5A CL 1- 03Nos (g) 20A fuse base-07Nos. (h) A Fuse link-03Nos. (j) A DP MCB-01No. (k)6A DP MCB-01No. (l) VFA meter 150/5A-01No. (m) AMF relay-01No. (n) Analog type ammeter (0-30A)- 01No. (o) Analog type voltmeter (0-60V)-01No. (p) Hooter sif-96 (12V DC)- 01No. (q) 6A DP 2 Way without selector switch (1-2)-01No. (r) 6A SP 1 Way ON/OFF selector switch-01No. (s) SMPS battery charger 230/12V DC- 01No. (t) 2 CO Pla relay with bus 12V DC (12V DC)-03Nos. (u) CO Pla relay 12V DC-02Nos. (v) LED type red indicating lamp (240V AC)-04Nos. (w) LED type yellow indicating lamp (220V AC)-01No. (x) LED type blue indicating lamp (220V AC)-01No. (y) 6A red push button NO element-01No. (z) 6A green push button-01No. (aa) 6A NO element for push button-04Nos. (ab) 6A NC element for push button-02Nos. |
| 184 | AMF panel for 45KVA DG set(a) Power contractor 4P, 36kA, 100A- 02Nos (b) Spreader link for 100A, 4P, MCCB- 02sets (c) Direct rotary handle for 100A 4P MCCB- 03Nos (d) Auxiliary contact- 02Nos (e) 100A 4P Power contactor- 02Nos (f) C/T 100/5A CL 1- 03Nos (g) 20A fuse base-07Nos (h) 2A fuse link- 03Ns (j) 4A DP MCB-01No. (k)6A DP MCB-01No (l) VFA meter 100/5A-01No. (m) AMF relay-01No (n) Analog type ammeter (0-30A)-01No (o) Analog type voltmeter (0-60V)-01No. (p) Hooter sif-96 (12V DC)-01No (q) 6A DP 2 Way without selector switch (1-2)-01No. (r) 6A SP 1 Way ON/OFF selector switch-01No (s) SMPS battery charger 230/12V DC=01No. (t) 2 CO Pla Relay with bus 12V DC (12V DC)-03Nos. (u) CO Pla relay 12V DC-02Nos (v) LED type red indicating lamp ( 240V AC)-04Nos. (w) LED type yellow indicating lamp (220V AC)-01No. (x) LED type blue indicating lamp (220V AC)-01No. (y) 6A red push button NO element01No. (z) 6A green push button-01No. (aa) 6A NO element for push button-04Nos (ab) 6A NC element for push button-02Nos. |
| 185 | Notes for serial item Nos. 181 to 184: (a) The Contractor shall submit drawings from the approved OEM for approval of the GE through the Engineer-in-charge(b) The panels shall include 2Nos. danger notice plates made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 250x200mm with letter, figures and conventional skull bones in signal red colour duly fixed with nuts, bolts and washers, etc. with voltage and danger indicated both in Hindi and English(c) Excavation, earthwork in any type of soil, construction of PCC foundation for panel shall be deemed included in quoted rate. Foundation specifics shall be as per OEM of panel. The Contractor shall submit foundation desgn drawings to attain approal of he GE(d) Foundation bed shall be in PCC 1:3:6 type C2 using 40mm graded stone aggregates with a depth of 15cm below ground level and 1.5m above ground level with stare and slot openings for I/C and O/G cables |
| 186 | M&L for earthing using GI earthing wire with galvanised steel earth plate electode 600x600x6mm thick buried directly in ground, earth pit not less than 2.25m deep below ground level connection to and including GI earth lead wire 4mm dia extended to 7.5m as earth lead by means of GI bolts, nuts, etc. with provision of charcoal and salt all as per electrical plate No. 3 of SSR Part-I including water arrangement with GI pipe 20mm dia (medium grade), earth lead protection pipe 15mm light grade with bends, elbow, etc. from earth plate to test point, excavation and earthwork in any type of soil, returning, filling, ramming and removing of soil to distance not exceeding 50m, make good to match with existing surface making PCC pit (earth chamber) having internal size 300x300x300mm and outer size 600x 600x600mm with RCC reinforced cover 50mm thick and testing on completion including making test points on wall as per SSR specifications, taking down and disposing off old earthing complete all as specified and as directed |
| 187 | M&L for earthing with galvanised iron earth plate electrode 600x600x6mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m below ground level connetced with galvanised strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (using 20mm graded stone aggregates), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 150mm C/C bothways and suitable handle made of 10mm dia ound bar including all necessary earthwork, excavation, returning filling in any type of soil and removing surplus earth upto a distance not exceeding 50m all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) including testing on completion and making test points on wall as per SSR specifications complete all as specified and as directed |
| 188 | Notes for serial item No. 186 & 187: (i) The cost of GI earth continuity wire / strip with GI pipe 20mm medium grade upto 7.5m is deemed to be included(ii) The earth chamber to be constructed 0.5m from edge of earth pit with necessary watering arrangement. The cost for the same is deemed to be included in above item(iii) Earthing shall produce desired earth resistance values as directed by the Engineer-in-charge |
| 189 | M&L for taking down AC units for required servicing, cleaning of cooling coil, air filters/plasma filters, etc. (indoor unit), condenser, compressors, fan motor, etc. (outdoor unit) with vacuum cleaner and cleaning solutions, etc., checking serviceabilityof electrical / electronic parts viz. circuit relays, wiring kit, thermostat switches, knobs, remote control unit, fan, blower, etc. and ensuring the AC unit in satisfactory working conditions complete all as specified and as directed for the following:Notes:(a) Spares / parts / components replaced will be measured and paid separately under relevant items hereinafter and labour charges for replacement including all allied works shall be deemed to be included in the unit rate quoted (b) Gas charging as required shall be deemed to be included in the quoted rate (c) Cost of taking down, loading / unloading, carting (to & fro) to workshop if required shall be deemed to be included in the quoted rate |
| 190 | Split type AC 1.5/2TR |
| 191 | Window type AC 1.5/2TR |
| 192 | M&F for attending to complaints in case of breakdown of AC units any type at UAV Kumbhirgram whenever required, rectifying the fault and restoring the units including all necessary arrangements, T&P, etc. as required at site complete all as specified and as directed Notes:(i) The cost of replaced spare parts, gas charging will measured and paid seperately under resective item herein(ii) Complaint will be intimated by any means either written or electronic and shall be attended by the Contractor immediately within 24hrs (maximum). In the event the complaint if not attended a penalty of Rs. 500/hour beyond 24hrs shall be levied. The amount shall be deducted from immediate payments due to the Contractor(iii) The cost of transportation (to and fro) for all kind of necessary equipment/T&P shall be arranged/brought by contractor to complete the job at site or at E/M yard shall be deemed to be included in the the quoted rate(iv) Successful restoration of AC units shall only be considered for payment purposes |
| 193 | Supply, installing, testing and commissioning of compressors of AC units in any location / position including disconnecting electrical mains, remove the refrigerant and capture it in a storage cylinder, cutting line sets, removing the condenser coil and everything around the compressor, taking out the condenser unit, cleaning and removing dust / dirt, etc., necessary minor modifying (replacement of capilary tubes, etc.), replacing the compressor and finally put the rest back together and balance charging of refrigerant gas F-22/R-134A (if required) including disposing of old unserviceable condensor unit complete all as specified and as directed of the following capacities:Notes: (i) Compressor units shall be from manufacturer as approved by the GE(ii) Compressors shall be brought in sealed conditions(iii) Compressor shall bear a minimum warrantee of 5years and as given by manufacturers |
| 194 | 2Ton |
| 195 | 1.5Ton |
| 196 | M&L for charging refrigerant gas F-22/R-134A in split type AC unit of any capacity including required staging / taking down of compressor units, etc. as required, detecting leakages, etc. stopping leakages by welding and testing on commissioning in satisfactory working conditions complete all as specified and as directed |
| 197 | Supply only the following spare parts including necessary fittings as per sample and suitable for and in maintenance of air conditioner units of capacity 1.5/2T complete all as specified |
| 198 | Condensing coil assembly including necessary fittings viz. clamps, nuts, bolts, etc. including all required soldering, brazing, etc. |
| 199 | Thermostat switch with regulator knob unit and necessary fittings |
| 200 | Starting capcitor of 80/100/120MFD |
| 201 | Selector switch with knob including necessary fittings |
| 202 | Blower motor capacitor 8MFD |
| 203 | Running capacitor 36MFD |
| 204 | Running capacitor 50MFD |
| 205 | Relay box/open type |
| 206 | Remote control hand set |
| 207 | Remote control PCB circuit |
| 208 | Overload protector relay |
| 209 | Front grill as per existing pattern including fixing screws and accessories |
| 210 | Air filter |
| 211 | Capillary charging |
| 212 | MS stand as per approved drawing and specifics |
| 213 | PVC drain pipe 15mm dia 3m long with clamp |
| 214 | Blower fan motor for spilt units |
| 215 | Blower fan motor for window units |
| 216 | M&L for disconnecting from mains and taking down for servicing water coolers including cleaning the cooling coil, air filters, condenser, compressors, fan motor, etc. with vacuum cleaner and cleaning solution, checkingserviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, fan and blower, etc. andmaking the water cooler to satisfactory working conditions complete all as specified and as directed of the following capacities:Notes: (a) Spares / parts / components replaced will be measured and paid separately under relevant items hereinafter and labour charges for replacement including all allied works shall be deemed to be included in the unit rate quoted(b) Gas charging as required shall be deemed to be included in the quoted rate (c) Cost of lifting, loading / unloading, carting (to & fro) to workshop if required shall be deemed to be included in the quoted rate |
| 217 | 120 to 150litres |
| 218 | 40 to 80litres |
| 219 | S&F company made new sealed compressor units for water coolers of capacity 60/120litres, including disconnecting electric and water connections in any position / location, cleaning and removing dust / dirt, etc., necessary minor modifying (replacement of capilary tubes, etc.), replacing the compressor and finally putting the rest back together and balance charging of refrigerant gas (if required) including disposing off old unserviceable compressor unit complete all as specified and as directedNotes: (i) Compressor units shall be from existing manufacturer / as approved by the GE(ii) Compressors shall be brought in sealed conditions(iii) Compressor shall bear a minimum warrantee of 5years and as given by manufacturers |
| 220 | M&L for charging refrigerant gas F-22/R-134A in water cooler units of any capacity and testing on commissioning in satisfactory working conditions complete all as specified and as directed |
| 221 | S&F in repairs blower motor assembly of water coolers of any make, as per existing including necessary fittings viz. clamps, nuts, bolts, etc. complete all as specified and as directed |
| 222 | S&F in repairs condensing coil assembly of water coolers of any make, including necessary fittings viz. clamps, nuts, bolts, etc. and all required soldering, brazing, etc. complete all as specified and as directed |
| 223 | Supply only the following spare parts as per sample and suitable forand in maintenance of water coolers including necessary fittings complete all as specified |
| 224 | Starting capacitor 60-80Mfd |
| 225 | Running capacitor 25Mfd |
| 226 | Thermostatic switch with regulating knob |
| 227 | Push cock, self closing chromium plated 15mm bore including nut and washer, etc. |
| 228 | PVC drain pipe 1m long including clamps |
| 229 | Float valve of gun metal, 15mm bore with ball |
| 230 | Over load protector relay |
| 231 | Running capacitor36Mfd |
| 232 | Pencil strainer |
| 233 | Water Tap with 6\"\" concealed end pipe of size 15mm |
| 234 | M&L for disconnecting from mains, for servicing refrigerators / deep freezers including cleaning the cooling coil, air filters, condenser, compressors, fan motor, etc. with vacuum cleaner and cleaning solution, checkingserviceability of electrical/electronic circuits relays, wiring kit, thermostat switches, knobs, leakage of gas, etc. andmaking the deep freezer / refrigerator to satisfactory working conditions complete all as specified and as directed of the following capacities:Notes: (a) Spares / parts / components replaced will be measured and paid separately under relevant items hereinafter and labour charges for replacement including all allied works shall be deemed to be included in the unit rate quoted(b) Gas charging as required shall be deemed to be included in the quoted rate (c) Cost of lifting, loading / unloading, carting (to & fro) to workshop if required shall be deemed to be included in the quoted rate |
| 235 | 230/285/286/310llitres |
| 236 | 165/175/185litres |
| 237 | S&F company made new sealed compressor units for refrigerators, including disconnecting electric and water connections in any position / location, cleaning and removing dust / dirt, etc., necessary minor modifying (replacement of capilary tubes, etc.), replacing the compressor and finally putting the rest back together and balance charging of refrigerant gas (if required) including disposing off old unserviceable compressor unit complete all as specified and as directed for the following capacities:Notes: (i) Compressor units shall be from existing manufacturer / as approved by the GE(ii) Compressors shall be brought in sealed conditions(iii) Compressor shall bear a minimum warrantee of 5years and as given by manufacturers |
| 238 | 165litres |
| 239 | 200/300/362litres |
| 240 | M&L for charging refrigerant gas F-22/R-134A in refrigerator units of any capacity and testing on commissioning in satisfactory working conditions complete all as specified and as directed |
| 241 | M&L for charging refrigerant gas F-22/R-134A in deep freezer units of any capacity and testing on commissioning in satisfactory working conditions complete all as specified and as directed |
| 242 | Supply only the following spare parts as per sample and suitable for and in maintenance of refrigerators / deep freezers including necessary fittings complete all as specified and as directed |
| 243 | Relay open type (over load cum relay) |
| 244 | Overload protector |
| 245 | Cooling coil door with locking spring |
| 246 | Thermostat switch with regulating knob |
| 247 | Fan motor / evaburator |
| 248 | Fan blade |
| 249 | Chiller tray as per existing model |
| 250 | Frost free timer |
| 251 | Frost free cooling coil |
| 252 | Capillary charging |
| 253 | Thermal fuse |
| 254 | S&F in repairs capillary tube and silica drier type strainer suitable for deep freezer 200/300/345/400litres capacity complete all as specified and as directed |
| 255 | S&F in repairs starting capacitor 4/6/8Mfd as per requirement at site suitable for deep freezer 200/300/345/400litres capacity complete all as specified and as directedMake: TESLA/EPCOS/SIEMENS/USHA |
| 256 | S&F in repairs over load protector relay suitable for deep freezer 200/300/362litres capacity complete all as specified and as directedMake: SHRIRAM/RENUTROL/DANFOSS |
| 257 | S&F in repairs thermostat switch suitable for deep freezer 200/300/362litres capacity complete all as specified and as directedMake: SHRIRAM/RENUTROL/DANFOSS |
| 258 | S&F in repairs relay open type suitable for deep freezer 200/300/362litres capacity complete all as specified and as directedMake: SHRIRAM/RENUTROL/DANFOSS |
| 259 | S&F in repairs fan motor suitable for deep freezer 200/300/362litres capacity complete all as specified and as directed |
| 260 | M&L for repairs/maintenance of voltage stabilizer 4/5kVA of different make including replacement of worn out parts viz. volt meter, transformer, circuit plate, step-up, step-down relays, etc. and testing for proper functioning complete all as specified and as directed |
| 261 | M&L for submain wring using proper colour codingwith 4 runs of single core, PVC insulated,FRLS unsheathed suitable for 1100V, multistranded, copper conducter cable of size 6sqmm and 1 run of 6sqmm multistranded, copper conductor cable 1100V green colour for earth conductor drawn through and including non-metallic PVC casing capping 25mm wide, heavy duty, ISI marked fixed on wall/ceiling, etc. with all required accessories complete all as specified and as directedNotes:(i) 4 runs of 6sqmm main cable, 1 run of earth conductors and 1 run of PVC casing capping as per item shall be measured as one length(ii) Separate casing capping shall be used for each sub-main wiring circuit irrespective of numbers of wire(iii) The minimum size of casing shall be as stipulated, however higher sizes shall be used as per number of cables passing through. The Engineer-in-charge shall ensure for proper size of conduit as per requirement at site |
| 262 | S&F in repairs single pole and neutral sheet metal enclosure powder coated with a two pin and earth plug and socket complete with and including01No. MCB 20A SP and making good the disturbed surfaces complete all as specified and as directed |
| 263 | S&F in repairs MCB, SP, 6 to 32A, 240V, 10kA, B curve complete all as specified and as directed |
| 264 | M&L for point wiring with 4sqmm, single core, FRLS PVC insulated, ISI marked, unsheathed cable 1100V grade with multi-stranded copper conductor, drawn through and including non-metallic rigid PVC casing capping not less than 20mm wide and accessories surface on walls, ceiling etc. and including provision of 2.5sqmm copper wire, green colour as earth continuity conductor and connected to common earth dolly with 1.6mm thick pressed steel concealed terminal boxes for AC / equipment controlled by one SP / SPN MCB on independent board complete all as specified and as directed |
| 265 | B/R WORKS |
| 266 | Taking down chowkats or frames not exceeding 1.5sqm each with shutters (without taking off shutters from the frame) and disposing off |
| 267 | Taking down chowkats or frames exceeding 1.5sqm but not exceeding 4sqm each but with shutters (without taking off shutters from the frame) and disposing off |
| 268 | Dismantling mild steel work or wraught iron of any description and in any position complete all as specified and as directed |
| 269 | Dismantling floor hearth or wall tiling including cement mortar bedding (but not backing) and disposing off complete all as specified and as directed |
| 270 | Dismantling plain or corrugated steel sheeting, any gauge or any thickness as in roof covering, wall cladding, etc. complete all as specified and as directed |
| 271 | Demolition of cement concrete (un-reinforced) in ground floors and pavings not exceeding 15cm thickness (below or above ground level) and removal of debris complete all as specified and as directed |
| 272 | Demolition of reinforced cement concrete (reinforcement cut as required to facilitate demolition) of any description and in any position not otherwise specifically provided for and removal of debris complete all as specified and as directed |
| 273 | Demolition of brickwork or stone / boulder masonry, built in cement mortar including all quoins, arches, pillars, etc but excluding ashlar facings, dressed stonework and precast concrete articles and disposing off complete all as specified and as directed |
| 274 | Taking down cement or cement/lime plaster,any description on brick or stone walls, etc. including raking out joints, hacking for keys, scubbing down with water, etc. including all necessary scaffolding as required and rubbishing off the premises, etc. complete all as specified and as directed |
| 275 | Taking up or down 15mm bore steel water tubing and connections from any location / position including disposing off, etc. complete all as specified and as directed |
| 276 | Taking up or down 20mm bore steel water tubing and connections from any location / position including disposing off, etc. complete all as specified and as directed |
| 277 | Dismantling rain water pipe and sewage line pipe of any type and any size including fitting complete all as specified and as directed |
| 278 | M&L for mild steel TMT bars grade Fe-500D, 10mm dia and over, cut to length, bent to shape required including cranking, bending spirally or hooping for columns, hooking ends and binding with and including MS wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed |
| 279 | M&L for mild steel TMT bars grade Fe-500D, 6 to 8mm dia, cut to length, bent to shape required including cranking, bending spirally or hooping for columns, hooking ends and binding with and including MS wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed |
| 280 | M&L for precast RCC 1:2:4 type B-1 using 20mm graded mechanically crushed stone aggregates as in cover slab for man holes, drains, soak wells, and similar articles, set in CM 1:4 with plain faces including necessary formwork and chamfering, weathering, throating, etc. complete all as specified and as directed |
| 281 | M&L for 75mm thick plain cement concrete 1:3:6 (type C-2) using 40mm graded stone aggregate as in floors, plinth protection, pavings, etc. including making spike rolling to surfaces or making impressions of expanded metal whilst the concrete is green laid in alternate bays of 3m length and joints between bays filled with 85/25 grade bitumen and sand mix @ 1:2 complete all as specified and as directed |
| 282 | M&L for plain cement concrete 1:3:6 (type C-1) using 20mm graded stone aggregate as in beds of drains, surface channels, foundations of manholes, etc. complete all as specified and as directed |
| 283 | M&L for 75mm thick plain cement concrete type B-2, 1:2:4 (using 40mm gradedstone aggregates) in flooring and similar works finished fair and even complete all as specified and as directed |
| 284 | Extra for forming fair finished drain or channel 30cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred / stopped ends etc. complete all as specified and as directedNote: Inner girth shall only be measured |
| 285 | M&L for brickwork with sub-class \"B\" bricks, straight or curved on plan exceeding 6m mean radius built in CM (1:6) complete all as specified and as directed |
| 286 | M&L for brickwork with sub-class \"B\" bricks, straight or curved on plan to any radius as in half brick thick walls built in CM (1:4) complete all as specified and as directed |
| 287 | M&L for rendering 10mm thick in cement mortar (1:6) on other side of lathing finished even and fair without using extra cement complete all as specified and as directed |
| 288 | M&L rendering 15mm thick, in cement mortar (1:4) on walls / concretesurfaces, etc. in two layers (10+5mm) finishing layer mixed with integral water proofing compound @3% by weight of cement, finished even and smooth without using extra cement complete all as specified and as directedNote: WPC will be measured and paid separately under respective item herein |
| 289 | Supply only integral water proofing compound all as specified |
| 290 | Cutting chases, pinning in brick walls and making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc. and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exceeding 10cm in girth complete all as specified and as directed |
| 291 | S&F solid PVC door frame of size 50x47mm made out of 5mm thick plain / printed coloured PVC sheet (as approved) reinforced with MS square tube all as per specifications and drawing given in SSR Part-I 2009 all as per manufacturer\"s instructions and making good the disturbed surfaces complete all as specified and as directed |
| 292 | S&F factory made solid panel PVC door shutter 30mm thick (style) consisting of frame made out of MS tubes for top & bottom rails, MS frame covered with heat moulded plain colour PVC ‘C’ channel having a PVC sheet strip of 20mm width, stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail, paneling of plain colour PVC sheet to be fitted in the MS frame welded/sealed to the stiles & rails with suitable PVC sheet beading and jointed together with solvent cement, supply and fixing in the frame at site as per clause 8 B.2.1 of MES schedule Part-II (2020) complete all as specified and as directed |
| 293 | S&F 30mm thick flush shutters, solid core construction, with block board core and plywood face panels, commercial type on both sides, smooth finish with lipping of teak wood on edges complete all as specified and as directed |
| 294 | S&F framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc. drilled for fixing of steel sheeting or other covering, doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, also fastening and fixing conforming to Fe 290 grade-E -165 complete all as specified and as directed |
| 295 | S&F stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staples complete all as specified and as directed |
| 296 | S&F in repairs stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staples complete all as specified and as directed |
| 297 | S&F for GI wire netting 0.71mm dia and 12mm mesh lathing to wood or metal studding joints, etc. in walls, ceiling stanchion, beams, etc. including all laps cutting and wastes complete all as specified and as directed |
| 298 | S&F 3mm thick sheet glass ordinary quality and glazing with oil putting square not exceeding 0.5sqm in each pane complete all as specified and as directed |
| 299 | S&F 3mm thick sheet glass ordinary quality and glazing with oil putting including hacking out old broken glass (any thickness, size quality or description) from wooden frame or stone, concrete or brick surrounds, glazed with putty or fixed with beads square not exceeding 0.5sqm in each pane complete all as specified and as directed |
| 300 | S&F in repairs 300mm aluminium anodised sliding door bolt with hasp and staple, bolt type, with mild steel hinge pin including bolt to hinge plate and fixed with screws complete all as specified and as directed |
| 301 | S&F 200mm long aluminum anodised barrel tower bolts of extruded section complete all as specified and as directed |
| 302 | S&F 150mm long aluminum anodised barrel tower bolt of extruded section complete all as specified and as directed |
| 303 | S&F 150mm extruded aluminum alloy handles, fabricated type, anodized complete all as specified and as directed |
| 304 | S&F 100mm extruded aluminum alloy handles, cast type, anodized complete all as specified and as directed |
| 305 | S&F 100mm long butt hinges, stainless steel, with stainless steel hinge pin, anodised and fixed complete all as specified and as directed |
| 306 | S&F 100mm MS butt hinges, medium weight, cold rolled complete all as specified and as directed |
| 307 | S&F door closer hydraulically regulated, designation No. 3 universal type of aluminium (extruded section body) suitable for door shutters 851 to 1000mm width and weight not exceeding 61 to 80kg complete all as specified and as directed |
| 308 | S&F in repairs 25mm dia fancy type MS chromium plated (tint as approved) MS curtain / drapery rods, etc. of rod wall thickness 1mm (min), including pair of brackets, holders with funnel at ends complete all as specified and as directed |
| 309 | M&L for non-skid ceramic tiles, coloured, area of tile exceeding 0.06sqm but not exceeding 0.11sqm each, 7 to 8mm thick of superior quality as in floors, etc. jointed in neat cement slurry @3.00kg of cement per sqm and pointed in white cement mixed with colouring pigment to match shade of tiles, laid over and including 15mm thick screed bed in CM (1:6) (rate shall be included) complete all as specified and as directed |
| 310 | M&L for non-skid ceramic tiles, coloured, area of tile exceeding 0.11sqm but not exceeding 0.18sqm each, 7 to 8mm thick of superior quality as in floors, etc. jointed in neat cement slurry @3.00kg of cement per sqm and pointed in white cement mixed with colouring pigment to match shade of tiles, laid over and including 15mm thick screed bed in CM (1:6) (rate shall be included) complete all as specified and as directed |
| 311 | M&L for rubber moulded reflective type chequered cement concrete tiles 25mm thick, area of tile exceeding 0.06sqm but not exceeding 0.11sqm each, set, jointed and pointed in neat grey cement slurry mixed with pigment to match colour of tiles as in floors laid over and including 15mm screed bed in CM 1:6 (rate shall be included) complete all as specified and as directed |
| 312 | Fixing only steel water tubing, medium grade, galvanised with screwed and socketed joints, including supply and fixing all fittings, ISI marked conforming to IS-1239 and fixed to walls or laid in floors / trenches required for water connections complete all as specified and as directed for the following bores:Note: Serviceable tubings obtained from dismantling herein before will be reused under this item |
| 313 | 15mm bore |
| 314 | 20mm bore |
| 315 | S&F steel water tubing, medium grade, galvanised with screwed and socketed joints, in any length, including supply and fixing all fittings, ISI marked conforming to IS -1239 and fixed to walls or laid in floors / trenches required for water connections complete all as specified and as directed of the following bores: |
| 316 | 15mm bore |
| 317 | 20mm bore |
| 318 | Supplying, hoisting, fixing and connecting up 500litres rotational moulded polythylene water storage tanks (cylindrical vertical with closed top), hoisted and fixed in position all as specified in SSR Part-I including connecting the overflow drain out, inlet and outlet pipes, tank nipple, elbow, bend, unions, sockets, etc. including taking down old damaged water tank and disposing off complete all as specified and as directed |
| 319 | S&F 20mm dia ball PTMT valves, weighing minimum 210gm, high pressure, with high density plastic / polythene float / ball, epoxy coated aluminium rod and flynut, screwed for iron pipe or brass ferrule and fixed complete all as specified and as directed |
| 320 | S&F in repairs 20mm dia ball PTMT valves, weighing minimum 210gm, high pressure, with high density plastic / polythene float / ball, epoxy coated aluminium rod and flynut, screwed for iron pipe or brass ferrule and fixed complete all as specified and as directed |
| 321 | S&F in repairs gun metal globe or gate valve, 20mm dia with iron wheel head, screwed both ends for iron pipe and fixed including necessary cutting into existing pipe, threading, inserting new piece of GI pipe of existing size, breaking/cutting into cement concrete, masonry, etc. and making good the disturbed surfaces complete all as specified and as directed |
| 322 | S&F in repairs vitreous China squatting pan, Orissa pattern of size 580x440mm, white, with integral foot rests and \"P\" or \"S\" trap, connecting to flushing pipe and trap and making good to the disturbed surfaces in CM 1:3 with finishes to match with the existing complete all as specified and as directed |
| 323 | S&F in repairs wash hand basin, vitreous China, white, flat back type, of size 550x400mm, including CI brackets, cutting for and pinning in ends of brackets with coupling and including PVC connection 60cm key with brass union complete all as specified and as directed |
| 324 | S&F 10litres capacity PVC flushing tank, white / coloured, syphonic action type, low level, valveless, with PVC inlet ball valve, PVC flush pipe, float and suitable sized brackets including cutting of floor / wall and making good to the disturbed surfaces in CM 1:3 with finishes to match with the existing and taking down of old PVC flush tank and disposing off complete all as specified and as directed |
| 325 | S&F internal accessories kit suitable for 10litres capacity PVC flushing tank, including taking outof old damaged set and disposing off complete all as specified and as directed |
| 326 | S&F in repairs 20mm dia bib taps, fancy type, PTMT any colour, high pressure (minimum weight 125gms) screwed down, screwed for iron pipe or for brass ferrule complete all as specified and as directed |
| 327 | S&F in repairs 15mm dia bib taps, fancy type, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule complete all as specified and as directed |
| 328 | S&F 15mm dia pillar taps, fancy type, cast copper alloy, with capstain heads, chromium plated, screwed down, high pressure, with or without lettered \"HOT\"/\"COLD\", with long screwed shanks and fly nuts, screwed for iron pipe complete all as specified and as directed |
| 329 | S&F in repairs 15mm dia stop cocks / angle valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, concealed type, screwed both ends for iron pipe or for unions or for brass ferrule complete all as specified and as directed |
| 330 | S&F in repairs 15mm PVC connections, 450mm long with brass couplings, PTMT nuts, etc. complete all as specified and as directed |
| 331 | S&F in repairs 32mm dia PVC waste pipe, 900mm long, PTMT complete all as specified and as directed |
| 332 | S&F in repairs PVC (SWR) pipes, 110mm bore, single socketed in any length with rubber ring joints fixed on walls with suitable clamps, etc. complete all as specified and as directed |
| 333 | S&F in repairs PVC (SWR) pipes, 75mm bore, single socketed in any length with rubber ring joints fixed on walls with suitable clamps, etc. complete all as specified and as directed |
| 334 | S&F in repair 110mm bore PVC (SWR) bend of any radius with oval access door complete all as specified and as directed |
| 335 | S&F in repair 110mm bore PVC (SWR) bend of any radius complete all as specified and as directed |
| 336 | S&F in repairs 75mm bore PVC (SWR) bend of any radius complete all as specified and as directed |
| 337 | S&F PVC(SWR) floor trap, 75mm dia outlet, plain with CP grating including jointing with solvent cement complete all as specified as directed |
| 338 | M&L for preparation of new masonry / concrete wall surfaces and applying two coats of oil emulsion distemper over a coat of wall primer including all necessary staging, scaffolding, etc. as required to work at heights, etc. complete all as specified and as directed |
| 339 | M&L for applying two coats of 100% premium acrylic emulsion paint having VOC less than 50gm/litre and UV resistance as per IS 15489:2004, alkali & fungal resistant, dirt resistant, exterior paint of approved shade (company depot tinted) with silicon additives @1.43litre/10sqm over and including a priming coat of exterior primer applied @0.90 litre/10sqm over new surfaces of brickwork,concrete, etc. including all necessary staging, scaffolding, etc.required complete all as specified as as directed |
| 340 | M&L for or complete removal and preparation of old decorated surfaces of walls by brooming down or steel wire brushing, scrapping down smoke shoots, moulds, moss and efforescent salts, trading oil, greasy spots, etc. and applying two coats of 100% premium acrylic emulsion paint having VOC less than 50gm/litre and UV resistance as per IS 15489:2004, alkali & fungal resistant, dirt resistant, exterior paint of approved shade (company depot tinted) with silicon additives @1.43litre/10sqm over and including a priming coat of exterior primer applied @0.90 litre/10sqm using roller including all necessary staging, scaffolding, etc. as required complete all as specified as as directed |
| 341 | M&L for complete removal and preparation of old decorated surfaces of walls by brooming down or steel wire brushing, scrapping down smoke shoots, moulds, moss and efforescent salts, trading oil, greasy spots, etc. and applying one coat of oil emulsion distemper including all necessary staging, scaffolding, etc. as required to work at heights, etc. complete all as specified and as directed |
| 342 | M&L for preparing of new steel / metal surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint (tint as approved) over a coat of red oxide zinc chrome primer complete all as specified and as directed |
| 343 | M&L for preparing of old steel / metal surfaces of any description over 10cm in width or girth and applying one coat of synthetic enamel paint (tint as approved) complete all as specified and as directed |
| 344 | M&L for preparing of new wood / wood based surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint over a coat of pink primer, tint as approved complete all as specified and as directed |
| 345 | M&L for preparing of old wood / wood based surfaces of any description over 10cm in width or girth and applying one coat of synthetic enamel paint (tint as approved) complete all as specified and as directed |
| 346 | M&L for writing stops, commas, short lies, dashes, brackets, etc. not exceeding 30cm high in synthetic enamel paint (of approved tint) at any locations / positions complete all as specified and as directed |
| 347 | M&L for painting lines, dashes, arrows, letters, etc. on roads, pavements and the like exceeding 10cm wide in synthetic enamel paint (of approved tint) complete all as specified and as directed |
| 348 | S&F pre-painted galvalume aluminum zinc coating GI based corrugatedsteel sheet 0.50mm thick of any colour (as approved) having tensile strength of 550Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed |
| 349 | --ditto-- all as per item No. 348 hereinabove but except sheets |
| 350 | S&F pre-painted galvalume aluminum zinc coating GI based plain steel sheet 0.50mm thick of any colour (as approved) having tensile strength of 550Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed |
| 351 | S&F 0.63mm thick corrugated galvanised steel sheetings, with grade of zinc coating 275gm/sqm and with two corrugation side lap fixed with‘L’ type or ‘J’ type cranked hook bolts, nuts, washers, etc. as in roof, wall, etc. complete all as specified and as directed |
| 352 | --ditto-- all as per item No. 351 hereinabove but except sheets |
| 353 | S&F 0.63mm thick corrugated galvanised steel sheetings, with grade of zinc coating 270gm/sqm, plain, fixed with cranked hook bolts, nuts, washers, etc. as in ridges, hips, valley gutters, drip and straight flashings (length or girth as fixed) complete all as specified and as directed |
| 354 | M&L for cleaning / de-sludging of septic tanks, using mechanical pumps, diesel driven, with fuel, operator, etc. and all necessary tools / plants including loading and carting off the drawn sludge, waste material, scum, spoil water, etc. outside MD land through designated sludge carriers / bio tanks complete all as specified and as directed of the following capacities: |
| 355 | 25 Users |
| 356 | 50 Users |
| 357 | M&L for cleaning / de-sludging of sewage soakage wells/pits of depth 10 to 12m, using mechanical pumps, diesel driven, with fuel, operator, etc. and all necessary tools / plants including loading and carting off the drawn sludge, waste material, scum, spoil water, etc. outside MD land through designated sludge carriers / bio tanks complete all as specified and as directed |
| 358 | M&L for cleaning of kitchen / bathroom trap (floor trap/ gully trap) by using rubber pump and rod, etc. including removal of sludge and other foreign materials complete all as specified and as directed |
| 359 | M&L for cleaning of water closet (any type) and inspection chamber by using rubber pump and rod, etc. including removal of sludge and other foreign materials complete all as specified and as directed |
| 360 | M&L for desilting of manholes with a lift upto 5m including sewer lines of 110 to 150mm bore, by removing either by mechanical or manual means, the exiting slush/hardened silt/sludge/ any other hardened debris accumulated over a period and in foul conditions (debris like concrete pieces, stone boulders, hardened lime, etc.) including taking out these materials, transportation and depositing at a point within a lead exceeding 50m but not exceeding 100m, spreading, dressing and leveling the heaps to a level not higher than 1m level including all tools, tackles, equipment, labour, etc. complete all as specified and as directed |
| 361 | M&L for desilting and cleaning PVC / SGSW drain pipe, RCC hume pipe, CI pipe lines of 110 to 150mm bore, by removing either by mechanical or manual means, the exiting slush/hardened silt/sludge/ any other hardened debris accumulated over a period and in foul conditions (debris like concrete pieces, stone boulders, hardened lime, etc.) including taking out these materials, transportation and depositing at a point within a lead exceeding 50m but not exceeding 100m, spreading, dressing and leveling the heaps to a level not higher than 1m level including all tools, tackles, equipment, labour, etc. complete all as specified and as directed |
| 362 | M&L for loose filling with broken brick aggregates of gauge 40 to 80mm in soakage pits, soakage wells, etc. complete all as specified and as directed |
| 363 | Notes for item Nos. 354 to 362:(i) All necessary precautions and all safety measures as per Municipality rules / relevant regulatory guidelines shall be taken by the Contractor in employing his mechnical means and workmen. No person shall be employed in direct contact working in septic tanks, manholes, sewage wells, etc. in foul conditions to prevent any health hazards, etc. and only mechanical means shall be used(ii) The Contractor shall be solely responsible for any mishap to any of labourer deployed and to equipment/machinery/plants/material, etc. brought at site for work and any lapses whatsoever during the execution,(iii)The work shall be executed under the supervision of highly skilled tradesman / supervisor(iv) Drawn sludge, waste material, scum, spoil water, etc. shall be removed to outside MD land through designated sludge carriers / bio tanks only |
| 364 | Notes for item Nos. 354 to 362 (contd..):(v) To avoid any hazard or spreading of any foul gas bleaching powder shall be spread as directed(vi) The rates quoted shall be deemed to be inclusive of the above aspects, and no claims whatsover shall be entertainable at later stages and or during execution |