Military Engineer Services-MES has published Tender For Repair And Maintenance Of Mccb, Apfc Panels, Pillar Boxes, Lt Panels And Accessories Other Misc Works Under Ge (U) Chandimandir.. Submission Date for this Tender is 21-02-2024. MCCB Tenders in chandimandir Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

41824602
Corrigendum : Tender For Repair And Maintenance Of Mccb, Apfc Panels, Pillar Boxes, Lt Panels And Accessories Other Misc Works Under Ge (U) Chandimandir.
Open Tender
Indian
Haryana
chandimandir
21-02-2024

Tender Details

Tender For Repair And Maintenance Of Mccb, Apfc Panels, Pillar Boxes, Lt Panels And Accessories Other Misc Works Under Ge (U) Chandimandir.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 14-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 21-02-2024

Key Value

Document Fees
INR 1000 /-
EMD
INR 145000.0 /-
Tender Value
INR 80 Lakhs /-

BOQ Items

Name of Work: REPAIR AND MAINT OF MCCB"S, APFC PANELS, PILLAR BOXES, LT PANELS AND ACCESSORIES OTHER MISC WORKS UNDERGE (U) CHANDIMANDIR
Sl. No. Item Description
1M&L in replacement of Power Cables, Aluminum Stranded Conductor 400 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098 (Part 1) 1988 complete laid in trenches / floors / ducts/ fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH Line and testing on completion including taking down old unserviceable cable complete all as specified and directed by Engineer-in-Charge. Note: 1. Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ. 2.Laying of LT UG Cable includes excavation and laying at certain places in hard standing by removing cross linked tiles, and laying cables, reflling and fixing the tiles to original shape etc., The rates quoted are deemed to be inclusive of necessary civil works to bring the area to original finish and no extra payment will be done on this account.
2All as per item No. 1.00 here-in-before but of size 300 sqmm, 3.5 core.
3All as per item No. 1.00 here-in-before but of size 240 sqmm, 3.5 core.
4All as per item No. 1.00 here-in-before but of size 185 sqmm, 3.5 core.
5All as per item No. 1.00 here-in-before but of size 120 sqmm, 3.5 core.
6All as per item No. 1.00 here-in-before but of size 95 sqmm, 3.5 core.
7All as per item No. 1.00 here-in-before but of size 70 sqmm, 3.5 core.
8All as per item No. 1.00 here-in-before but of size 50 sqmm, 3.5 core.
9All as per item No. 1.00 here-in-before but of size 35 sqmm, 3.5 core.
10All as per item No. 1.00 here-in-before but of size 25 sqmm, 4 core.
11All as per item No. 1.00 here-in-before but of size 16 sqmm, 4 core.
12Excavation in trenches for foundations, laying / taking out of cables, erecting of poles etc, in any type of soil, not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr in width and getting out, complete all as specified and as directed. Note :- Nothing extra will be paid to the contractor in this account if hard or rocky soil is encoutered during the execution.
13Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge.
14Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
15Material & Labourfor cutting of existing hard standing/road up to 15 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed. Note:- Excavation and earth work below hard standing will be measured and paid under relevant items.
16Supply and fix in replacement of 100mm dia bore tubes, "light grade" galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed by Engineer-in-Charge.
17All as per item No. 16 here-in-before but of size 80mm dia bore.
18All as per item No. 16 here-in-before but of size 50mm dia bore.
19Supply and Laying of 50mm outer dia, double wall corrugated HDPE pipe confirming to IS-14930 Part-II with antirodent and non flame propogating properties of approved colour laid in trenches/ floors/ duct or fixed on wall/ pole including all connections, accessories like socket, couplers, bends etc for protection of LT XLPE Cable grade 1100 volts complete all as specified and directed by Engineer - in - Charge.
20All as per item No. 19.00 here - in - before but of size 100 mm outer dia
21M&L for Trimming of tree branches around the LT overhead conductor, poles (not less than 3 mtr) to clear the approach of overhead including removing of nest, wild grass creepers, unwanted vagetation etc from pole/ stay including cleaning of creepers climbed on poles and angles, channels and disposal off from site beyond 50 mtr and up 250 mtr complete all as specified and directed by Engr-in-Charge. (Note : span of 30 m to 50 m shall be considered as one unit.
22Material and labour for Surface dressing not exc 15cm deep in any type of soil and site clearance including cutting and removing of plants/bushes, leveling of surface area, throw wastage material out of fencing area/ compound wall up to 50m distance at sub station areas / pump House areas complete all as specified and as directed by Engineer-in-Charge.
23M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II
24Material and Labour for repair of existing deteriorated earth pit and re- construct new earth pit of size 450mm x 450mm inside dimension and 300mm deep with bricks masonary of 1:4 ratio cement mortar and provide inside and outside cement plaster 10mm thick (1:4 Cement mortar) with RCC top cover as per earth pit 100mm thick and provide GI funnel for watering complete with two coat of white colour weather coat and marking with black colour (Earth No.1) earth number complete all as specified and directed by Engr-in-Charge.
25Material and labour for taking out complete existing deteriorated lightning protection fixed on roof (Horizontally) , fix on wall of various unit location at Chandimandir including GI/Aluminium, Aluminium Air Terminal pointer, test point terminal box, insulator and re-fix on same position after removing deteriorated strip/pointer and replace with new GI/Aluminium strip and pointer including insulator, making the hole in GI/Al strip, bending etc and testing complete all as specified and directed by Engr-in-Charge. Note :- (i) The cost of the insulator will be included in the laying in GI/Aluminium strip. (ii) The distance between insulators will be 75cm. (iii) GI/Aluminium strip will be measured and paid separately. (iv) Two nuts and bolts will have to be provided on each joint. cost of nut bolts shall be deemed to included in quoted rates. (v) Welding work will not be permitted anywhere in GI strip.
26Supply OnlyGI strip 32 x 6 mm for earthing complete all as specified and directed by Engr-in-Charge.
27Supply Onlyaluminium strip of size 25 x3.15 mmfor earthing complete all as specified and directed by Engr-in-Charge.
28Supply & fixing in replacement test point terminal block made of gun metal or phosphrous bronze size 75 x 75 x 25 mm drilled and screwed including 3 Nos, 8 mm dia 25mm long hex head screw complete all as specified and directed by Engr-in-Charge.
29Supply & fixing in replacementAir termination, single pointed aluminium rod 12mm dia and 300 mm long complete all as specified and directed by Engr-in-Charge.
30Supply and fix in replacement of MCCB 630 Amp, 4 pole, 50 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and directed by Engr-in-Charge.
31Supply and fix in replacement of MCCB 500 Amp, 4 pole, 50 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and directed by Engr-in-Charge.
32Supply and fix in replacement of MCCB 400 Amp, 4 pole, 36 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and directed by Engr-in-Charge.
33Supply and fix in replacement of MCCB 315/350 Amp, 4 pole, 36 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
34Supply and fix in replacement of MCCB 250 Amp, 4 pole, 36 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
35Supply and fix in replacement of MCCB 200 Amp, 4 pole, 36 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and directed by Engr-in-Charge.
36Supply and fix in replacement of MCCB 160 A , 4 pole, 36 KA(Ics =100% Icu) with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and directed by Engr-in-Charge.
37Taking down old unserviceable ACB any type andSupply, installation, testing and commissioning new LT ACB of 630 Amps, four pole, manual draw out with thermal magnetic release based, 415 Volts, 50 Hz suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge.
38Taking down old unserviceable ACB any type andSupply, installation testing and commissioning new LT ACB of 800 Amps,four pole, manual draw out with thermal magnetic release based, 415 Volts, 50 Hz suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge.
39Taking down old unserviceable ACB any type andSupply, installation testing and commissioning new LT ACB of 1000 Amps, four pole, manual draw out with thermal magnetic release based, 415 Volts, 50 Hz suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge.
40Shutdown the power supply, disconnecting all incoming & outgoing cables carefully from outdoor type LT panel board, removing the burnt wiring, cleaning the bus bars, insulators and MCCBs with CTC, meggering the insulation value and replacing the bus bar supporting insulators wherever required to achieve required insulation resistance value, tightening all fasteners (renew if required), reconnecting back the incoming and outgoing cables with suitable cable Lugs, glands and wrapping the insulation tape on all bare conductors, supply and fixing EPDM rubber gasket for all doors for dust & vermin proofetc and testing on completion for proper functioning complete all as specified and directed by Engineer-in-Charge. Note: (i) Replacement of unserviceable MCCBs shall be measured and paid separately. (ii) Replacement of broken/corroded metal sheets/ angle iron parts of panel boards shall be measured and paid separately.
41Material and labour for replacement of old and deteriorated MS sheet of any size and shape from the outdoor/indoor panel 3.00 mm thick and fix on outdoor/indoor panel as per required size and shape complete inclusive fixing the hinges, door lock etc, including two coat of super enamelled paint as per existing colour over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
42M & L for Preparation of old steel surfaces of outdoor type LT panel boards of any size and painting with One coat of synthetic enamel paint of approved colour (both internally & externally) and fixing 02 Nos steel danger plates on panel board complete all as specified and directed by Engineer-in-Charge.
43Supply and fix in replacement of On-Load Changeover switch 4 Pole, 315A, 415 Volts, AC, 50 Hzin sheet Metal enclosure with front operated handle complete all as specified and directed by Engr-in-Charge.
44Supply and fix in replacement of On-Load Changeover switch 4 Pole, 400A, 415 Volts, AC, 50 Hzin sheet Metal enclosure with front operated handle complete all as specified and directed by Engr-in-Charge.
45Supply and fix in replacement of On-Load Changeover switch 4 Pole, 630A, 415 Volts, AC, 50 Hzin sheet Metal enclosure with front operated handle complete all as specified and directed. Note for srl item no. 43.00 to 45.00: Any modifications needed for fixing the open execution switch in the panel is deemed to be included in the rates quoted and no extra payment will be done on this account
46Supply and fixHeat Shrinkable jointing kit for 1100 volts grade cable for straight through jointcomplete with jointing material and accessories suitable for 3.5 core XLPE cable of size 25 to 50 Sqmm complete all as specified and directed by Engr-in-Charge.
47Supply and fixHeat Shrinkablejointing kit for 1100 volts grade cable for straight through jointcomplete with jointing material and accessories suitable for 3.5 core XLPE cable of size 70 to 120 Sqmm complete all as specified and directed by Engr-in-Charge.
48Supply and fixHeat Shrinkablejointing kit for 1100 volts grade cable for straight through jointcomplete with jointing material and accessories suitable for 3.5 core XLPE cable of size 150 to 185 Sqmm complete all as specified and directed by Engr-in-Charge.
49Supply and fixHeat Shrinkablejointing kit for 1100 volts grade cable for straight through jointcomplete with jointing material and accessories suitable for 3.5 core XLPE cable of size 240 to 300 Sqmm complete all as specified and directed by Engr-in-Charge.
50Supply and fixHeat Shrinkablejointing kit for 1100 volts grade cable for straight through jointcomplete with jointing material and accessories suitable for 3.5 core XLPE cable of size 400 to 500 Sqmm complete all as specified and directed by Engr-in-Charge.
51Supply and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor and overall PVC sheathed in service connections one twin core cable flat or circular of size 10 sqmm complete all as specified and directed by Engineer-in-Charge.
52Supply and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor and overall PVC sheathed in service connections one twin core cable flat or circular of size 6 sqmm complete all as specified and directed by Engineer-in-Charge.
53Supply, Installation, Testing & Commissioning of indoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
54Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 2000mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacityincluding taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :-
55(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB"s and outgoing MCCB"s up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
56(ii) Incomer : (a) Air Circuit Breaker (ACB), 800 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos (b) MCCB 320 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos (c) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos (d) MCCB 160 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
57Supply, Installation, Testing & Commissioning of indoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
58Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 2000mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacityincluding taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :-
59(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB"s and outgoing MCCB"s up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
60(ii) Incomer : (a) Air Circuit Breaker (ACB), 800 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos (b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (c) MCCB 160 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
61Supply, Installation, Testing & Commissioning of indoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
62Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 2000mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacityincluding taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :-
63(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB"s and outgoing MCCB"s up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
64(ii) Incomer : (a) Air Circuit Breaker (ACB), 800 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (b) MCCB 320 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (c) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (d) MCCB 160 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
65Supply, Installation, Testing & Commissioning of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
66Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 2000mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacityincluding taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :-
67(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB"s and outgoing MCCB"s up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
68(ii) Incomer : (a) Air Circuit Breaker (ACB), 630 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (b)MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (c) MCCB 160 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (d) MCCB 100 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
69Supply, Installation, Testing & Commissioning of indoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
70Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 2000mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacityincluding taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :-
71(i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB"s and outgoing MCCB"s up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
72(ii) Incomer : (a) Air Circuit Breaker (ACB), 800 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No (b) Digital Voltmeter with selector switch - 01 Set (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 Set of 3 (d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3 (iii) Outgoing :- (a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (b)MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (c) MCCB 160 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (d) MCCB 100 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (e) ON LOAD changeover switch 4 pole, 415 volts, 50 Hz in sheet metal enclosure with front operated handle of cap 630 Amps - 01 No
73Supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings)having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.
74Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards(02 Nos) LT 415/440 Volts, and manufacturer"s name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1500mm x 1300mm x 450mm (outer dimensions)for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable LT Panel complete all as specified and directed:-
75(i) Bus bar: TPN Aluminium bus bar of rating suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.)and Continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
76(ii) Incomer: (a) MCCB, 400 A, 4 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No (b) Digital Voltmeter with selector switch - 01 Set. (c) Digital Ammeter with selector switch & suitable ratio of CT"s - 01 set of 03 (d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 (iii) Outgoing:- (a)MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (b) MCCB 160 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos (c) MCCB 100 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
77Note for BOQ Srl Item no. 53.00 to 58.00: (i) Factory made name plates with feeder names / Bldg Nos shall be fixed on relevant incomer / outgoing MCCB doors. (ii) The Contractor shall submit set of all drawings of the L.T. Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
78Supplying, installing, testing and commissioningof 100 KVAR Automatic Power factor Corrector (APFC) Panel of approx. size of 1800 X1100 X500mm factory made, cubical compartmentalized for each stage, outdoor type, IP 54 degree Protection, dust, vermin and weather proof, made out of CRCA MS Sheet of 3.15mm thickness, front openable with locking arrangement, fixed on 50x50x6mm angle iron 4 leg frame structure having 40cm ground clearance, duly grouted in P:C:C (1:2:4) complete panel powder coated with seven tank process from inside and outside, duly prewired with suitable size FRLS PVC insulated multistranded copper conductor wire for capacitor stages, metering & control accessories, earthing straps for connecting earth strips, cable entry from bottom including taking down old unserviceable APFC Panel and comprising the following:-
79(a) Bus Bar system- Aluminium bus bars of size 30X10mm for phases and 30 x 5mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incomer – MCCB 200 Amp, 4 pole, 36 KA, ICS= 100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle -01 No. (c) MCB, TP 63 Amp, D Series, 415 volts-01 No (d) MCB, TP 40 Amp, D Series, 415 volts-02 Nos (e) MCB, TP 20 Amp, D Series, 415 Volts-01 No. (f) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 Volts & 50 HZ system of 50 KVARcapacity-01 No
80(g) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 25 KVAR capacity-01No (h) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 15 KVAR capacity-01No MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50 HZ system of 10 KVAR capacity-01No (k) Capacitive duty contactor suitable for 50 KVAR Heavy duty Capacitor -01 No (l) Capacitive duty contactor suitable for 25 KVAR Heavy duty Capacitor -01 No (m) Capacitive duty contactor suitable for 15 KVAR Heavy duty Capacitor -01 No (n) Capacitive duty contactor suitable for 10 KVAR Heavy duty Capacitor -01 No (o) 04- Stage Automatic power factor Correction relay- 01 No (p) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly prewired with suitable size copper wire- 01 No
81(q) Digital Amp meter 0 to 200 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No (r)Indicator lamp indicating Cycle on with Amber sheds LED type -06 Nos (s) Space Heater, 60 Watt, 230 volt Ac alongwith toggle switch- 01 Set (u) ventilating fans of 6” sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 Volt, 50 HZ Ac -01 No. Note:- 1.The drawing for APFC panel shall be approved by GE before placement of order. 2.Any kind of brick work, PCC, Plastering etc as required for installation of APFC Panel during execution of work, is included in quoted rate and no extra cost will be paid in this effect.
82Supplying, installing, testing and commissioning in replacement of 150 KVAR Automatic Power factor Corrector (APFC) Panel of approx. size of 1800 X1100 X500mm factory made, cubical compartmentalized for each stage, outdoor type, IP 54 degree Protection, dust, vermin and weather proof, made out of CRCA MS Sheet of 3.15mm thickness, front openable with locking arrangement, fixed on 50x50x6mm angle iron 4 leg frame structure having 40cm ground clearance, duly grouted in P:C:C (1:2:4) complete panel powder coated with seven tank process from inside and outside, duly prewired with suitable size FRLS PVC insulated multistranded copper conductor wire for capacitor stages, metering & control accessories, earthing straps for connecting earth strips, cable entry from bottom including taking down old unserviceable APFC Panel and comprising the following:-
83(a) Bus Bar system- Aluminium bus bars of size 50X10mm for phases and 25 x 10mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incomer – MCCB 320 Amp, 4 pole, 36 KA, ICS= 100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle -01 No. (c) MCB, TP 63 Amp, D Series, 415 volts-01 No (d) MCB, TP 40 Amp, D Series, 415 volts-03 Nos (e) MCB, TP 20 Amp, D Series, 415 Volts-02 No. (f) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 Volts & 50 HZ system of 50 KVARcapacity-01 No
84(g) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 25 KVAR capacity-03No (h) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 12.5 KVAR capacity-02No (k) Capacitive duty contactor suitable for 50 KVAR Heavy duty Capacitor -01 No (l) Capacitive duty contactor suitable for 25 KVAR Heavy duty Capacitor -03 No (m) Capacitive duty contactor suitable for 12.5 KVAR Heavy duty Capacitor -02 No (n) 04- Stage Automatic power factor Correction relay- 01 No (o) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly prewired with suitable size copper wire- 01 No
85(q) Digital Amp meter 0 to 400 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No (r)Indicator lamp indicating Cycle on with Amber sheds LED type -06 Nos (s) Space Heater, 60 Watt, 230 volt Ac alongwith toggle switch- 01 Set (u) ventilating fans of 6” sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 Volt, 50 HZ Ac -01 No. Note:- 1.The drawing for APFC panel shall be approved by GE before placement of order. 2.Any kind of brick work, PCC, Plastering etc as required for installation of APFC Panel during execution of work, is included in quoted rate and no extra cost will be paid in this effect.
86Supplying, installing, testing and commissioning of 200 KVAR Automatic Power factor Corrector (APFC) Panel of approx. size of 1800 X1200 X800mm factory made, cubical compartmentalized for each stage, outdoor type, IP 54 degree Protection, dust, vermin and weather proof, made out of CRCA MS Sheet of 3.15mm thickness, front openable with locking arrangement, fixed on 50x50x6mm angle iron 4 leg frame structure having 40cm ground clearance, duly grouted in P:C:C (1:2:4) complete panel powder coated with seven tank process from inside and outside, duly prewired with suitable size FRLS PVC insulated multistranded copper conductor wire for capacitor stages, metering & control accessories, earthing straps for connecting earth strips, cable entry from bottom including taking down old unserviceable APFC Panel and comprising the following:-
87(a) Bus Bar system- Aluminium bus bars of size 60X10mm for phases and 30 x 10mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incomer – MCCB 400 Amp, 4 pole, 36 KA, ICS= 100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle -01 No. (c) MCB, TP 63 Amp, D Series, 415 volts-03 No (d) MCB, TP 40 Amp, D Series, 415 volts-01 Nos (e) MCB, TP 20 Amp, D Series, 415 Volts-02 No. (f) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 Volts & 50 HZ system of 50 KVARcapacity-03 No
88(g) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 25 KVAR capacity-01No (h) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 12.5 KVAR capacity-02No (k) Capacitive duty contactor suitable for 50 KVAR Heavy duty Capacitor -03 No (l) Capacitive duty contactor suitable for 25 KVAR Heavy duty Capacitor -01 No (m) Capacitive duty contactor suitable for 12.5 KVAR Heavy duty Capacitor -02 No (n) 04- Stage Automatic power factor Correction relay- 01 No (o) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly prewired with suitable size copper wire- 01 No
89(q) Digital Amp meter 0 to 500 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No (r)Indicator lamp indicating Cycle on with Amber sheds LED type -06 Nos (s) Space Heater, 60 Watt, 230 volt Ac alongwith toggle switch- 01 Set (u) ventilating fans of 6” sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 Volt, 50 HZ Ac -01 No. Note:- 1.The drawing for APFC panel shall be approved by GE before placement of order. 2.Any kind of brick work, PCC, Plastering etc as required for installation of APFC Panel during execution of work, is included in quoted rate and no extra cost will be paid in this effect.
90Design, supplying, installing, testing and commissioning in replacement of 300 KVAR Automatic Power factor Corrector (APFC) Panel of approx. size of 1800 X1500 X800mm factory made, cubical compartmentalized for each stage, outdoor type, IP 54 degree Protection, dust, vermin and weather proof, made out of CRCA MS Sheet of 3.15mm thickness, front openable with locking arrangement, fixed on 50x50x6mm angle iron 4 leg frame structure having 40cm ground clearance, duly grouted in P:C:C (1:2:4) complete panel powder coated with seven tank process from inside and outside, duly prewired with suitable size FRLS PVC insulated multistranded copper conductor wire for capacitor stages, metering & control accessories, earthing straps for connecting earth strips, cable entry from bottom including taking down old unserviceable APFC Panel and comprising the following:-
91(a) Bus Bar system- Aluminium bus bars of size 100X10mm for phases and 50 x 10mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incomer – MCCB 630 Amp, 4 pole, 36 KA, ICS= 100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle -01 No. (c) MCB, TP 125 Amp, D Series, 415 volts-01 No (d) MCB, TP 63 Amp, D Series, 415 volts-03 No (e) MCB, TP 40 Amp, D Series, 415 volts-02 Nos (f) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 Volts & 50 HZ system of 100 KVARcapacity-01 No
92(g) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 Volts & 50 HZ system of 50 KVARcapacity-03 No (h) MPP Capacitor, resin filled, heavy duty type for 3 phase 440 volt & 50HZ system of 25 KVAR capacity-02No (k) Capacitive duty contactor suitable for 100 KVAR Heavy duty Capacitor -01 No (l) Capacitive duty contactor suitable for 50 KVAR Heavy duty Capacitor -03 No (m) Capacitive duty contactor suitable for 25 KVAR Heavy duty Capacitor -02 No (n) 04- Stage Automatic power factor Correction relay- 01 No (o) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly prewired with suitable size copper wire- 01 No
93(q) Digital Amp meter 0 to 700 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No (r)Indicator lamp indicating Cycle on with Amber sheds LED type -06 Nos (s) Space Heater, 60 Watt, 230 volt Ac alongwith toggle switch- 01 Set (u) ventilating fans of 6” sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 Volt, 50 HZ Ac -01 No. Note:- 1.The drawing for APFC panel shall be approved by GE before placement of order. 2.Any kind of brick work, PCC, Plastering etc as required for installation of APFC Panel during execution of work, is included in quoted rate and no extra cost will be paid in this effect.
94Design, Fabricate, supply, installation and testing in replacementof outdoor type cubical panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 600mm x 600mm x 400mm (outer dimensions)for accommodating and including taking down old unserviceable and provision of following switchgears complete:- (i) TPN Aluminium bus bar 400 Amps 4 stripsprovided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision suitable glands. (ii) MCCB, 250 A, 4 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No
95Design, Fabricate, supply, installation and testing in replacementof outdoor type cubical panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 600mm x 600mm x 400mm (outer dimensions)for accommodating and including taking down old unserviceable and provision of following switchgears complete:- (i) TPN Aluminium bus bar 500 Amps 4 stripsprovided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision suitable glands. (ii) MCCB, 320 A, 4 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No
96Design, Fabricate, supply, installation and testing in replacementof outdoor type cubical panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 750mm x 750mm x 450mm (outer dimensions)for accommodating and including taking down old unserviceable and provision of following switchgears complete:- (i) TPN Aluminium bus bar 600 Amps 4 stripsprovided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision suitable glands. (ii) MCCB, 400 A, 4 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No
Disclaimer :