Tender For Repair / Maintenance To Eot Crane, Lifts, Fire Fighting & Fire Alarm System And Other Miscellaneous Items At Afs Sarsawa Under Ge ( Af ) Sarsawa, sarsawa-Uttar Pradesh

Military Engineer Services-MES has published Tender For Repair / Maintenance To Eot Crane, Lifts, Fire Fighting & Fire Alarm System And Other Miscellaneous Items At Afs Sarsawa Under Ge ( Af ) Sarsawa. Submission Date for this Tender is 08-02-2024. Cranes Tenders in sarsawa Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

41734116
Corrigendum : Tender For Repair / Maintenance To Eot Crane, Lifts, Fire Fighting & Fire Alarm System And Other Miscellaneous Items At Afs Sarsawa Under Ge ( Af ) Sarsawa
Open Tender
Indian
Uttar Pradesh
sarsawa
08-02-2024

Tender Details

Repair / Maintenance To Eot Crane, Lifts, Fire Fighting & Fire Alarm System And Other Miscellaneous Items At Afs Sarsawa Under Ge ( Af ) Sarsawa

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 85000.0 /-
Tender Value
INR 42.50 Lakhs /-

BOQ Items

NAME OF WORK : REPAIR/MAINT TO EOT CRANE, LIFTS, FIRE FIGHTING & FIRE ALARM SYSTEM AND OTHER MISCELLANEOUS ITEMS AT AFS SARSAWA UNDER GE (AF) SARSAWA
Sl. No. Item Description
1M&L for periodic inspection/ Servicing of 2 Ton capacity02 Nos EOT Crane of any make installed at different building/location in Airforce Station Sarsawa, making the crane in fully serviceable condition complete all as specified & directed as under:- (A) LONG TRAVERSE MOTION- (i) Checking gear box oil level , checking and rectification of leakage if any and filling with new gear box oil upto required level. (ii) Checking function of all LT Brakes of any capacity and making adjustment for proper working including replacement of worn out parts if any. (iii) Checkingof LT Wheels for any abnormal sound and checking mounting and fixing arrangement. (iv) Checking of grase in geared coupling and tightening of nut and bolts etc. (v) Checking of LT Motion cut-off at the extreme ends of bay length with L.T limit switches (vi) Checking drive shaft and coupling including tightening of nut and bolts. (vii) Checking of terminal connections of all LT motors and tightening properly including replacing burnt / overheated cable ends if any.
2(B) CROSS TRAVERSE MOTION (i) Checking gear box oil level , checking and rectification of leakage if any and filling with new gear box oil upto required level. (ii) Checking function of CT Brakes of any capacity and making adjustment for proper working including replacement of worn out parts if any. (iii) Checkingof CT Wheels for any abnormal sound and checking mounting and fixing arrangement. (iv) Checking of grase in geared coupling and tightening of nut and bolts etc. (v) Checking of CT Motion cut-off at the extreme ends of bay length with C.T limit switches (vi) Checking drive shaft and coupling including tightening of nut and bolts. (vii) Checking of terminal connections ofCT motors and tightening properly including replacing burntoverheated cable ends if any.
3(C) HOIST MOTION (i) Checking gear box oil level , checking and rectification of leakage if any and filling with new gear box oil upto required level. (ii) Checking function of all Hoist Brakes of any capacity and making adjustment for proper working including replacement of worn out parts if any. (iii) Checkingof Equalizing pully / rope drum for any abnormal sound and checking mounting and fixing arrangement. (iv) Checking of grase in geared coupling and tightening of nut and bolts etc. (v) Checking of Hoist Motion cut-off at the extreme ends of up and downwith rotary gearedlimit switches (vi) Checking drive shaft and coupling including tightening of nut and bolts. (vii) Checking of terminal connections ofHoist motors and tightening properly including replacing burnt / overheated cable ends if any.
4(D) ELECTRICALS (i) Checking and tightening all electric connection (ii) Checking the contactors/ relays etc for overheating or flashing. (iii) Cleaning off all connection and control cables. (iv) Properly bunching the loose control cable. (v) Checking functioning of cable carriers.
5(E) GROUND MOTION CONTROL PANEL (i) Opening the push button control unit, checking all connection, replacing flashed/ over heated connections, general cleaning and checking all the functions, of the LT/CT/ Hoist motion push buttons and lights switch including reassembling the unit complete Notes:- 1. Gear box oil shall be measured and paid separately. 2.Contractor"s rep will visit once in 03 months, check and inspect every crane and on occurance of any fault during contract period take servicibility certificate duly signed by the users and MES Rep. 3.The inspection and serviceing work shall be carried out by contractor through any vender having minimum 05 years experiance of similar work in any state/central govt department approved by GE.
6Supply only Gear box oilEP -230 for EOT crane complete all as specified & directed.Note:- The record for replacement of Oil shall be maintain by Engineer -in- charge duly signed by all concern.
7Supply onlyBrake oil for EOT crane complete all as specified & directed.Note :- The record for replacement of oil shall be maintain by Engineer -in- charge duly signed by all concern.
8S&F in replacement of old L.T / C.T D.S.L System in 2 TON capacity EOT Crane with New C-Track system with 4 wheel cable Trollies should be mounted on Angle Iron Brackets of suitable size duly clamped complete all as specified & directed.
9M&L in replacement of Flexible Cable of 01sqmm, 14 core for Pendent Push Button Station from Main Panel to Push Button Station on Newly fixed ‘C’-Track system suitable for 02 ton EOT Crane complete all as specified & directed.
10S&F in replacement new pendent Push Button Station made out of MS Sheet, duly powder coated, and pre wired for 2 TON EOT Crane having 10 Nos Push Button of different color with NO+NC Contact Block, the Push Button Station shallbe hangwith and including suitable insulated Steel Wire Rope with ‘D’ clamps complete all as specified & directed.
11M&L fabrication of New foundation base for LT Moterand Gear Boxincluding drilling and bolting of high tensile bolts complete all as specified & directed. NOTE : (a)The baseplate shall be fabricated by cutting MS Plate of min 10mm thick and cost of the same is included in this item.(b) The welding and drilling work, if required shall be done by contractor at their own cost.
12M&L in replacement ofUnserviceable L.T and C.T Disc Brake with Newdisc brake of suitable size complete all as specified & directed. Make : Megtech/ Cranex/ Pethe
13M&L in replacement of L.T & C.T box type limit switch with lever complete for 2 TON EOT Crane complete all as specified & directed. Make : Megtech/ Cranex/ Pethe
14S&F in replacement of multi standard copper conductor flexible (industrial cable) 1100 volts grade ,PVC insulted and sheathed cable of size 6sqmm 4 core complete all as specified & directed.
15S&F in replacement multi standard copper conductor flexible (industrial cable) 1100 volts grade, PVC insulted and sheathed cable of size 2.5sqmm 4 core complete all as specified & directed.
16S&F in replacement multi standard copper conductor flexible (industrial cable) 1100 volts grade, PVC insulted and sheathed cable of size 1.5sqmm 3 core complete all as specified & directed.
17M&L in replacement of Main Electric Control Panel of 2 TON EOT Crane made out of M.S Sheet not less than 16 SWG duly powder coated Prewired with flexible copper cable of suitable size having 20% cushion duly Terminated with copper lugs and having Terminal Blocks mounted on channel. The Panel should be fixed/ welded on the crane as directed. The Panel should have Main ON-OFF TPN MCCB 63 Amps rated,The Main Contactor should be 40 Amp rated 415/110 volts and Hoist Contactor should be 25 Amp rated-2 NOS, LT & CT Contactor should be 25 Amps rated having Coil Voltage 415/110 Volts-4NOS. The Panel should have step down Transformer having input 415/output 110/36/24/12 Volts andvariable frequency drive3 phase suitable for hoist motor with DBR. The Panel shall be made by C.P.R.I approved firm Make of Panel: R.T.F Automation/ Cranex Ltd/ Tricolite Note: The Panel wiring Diagram 3 Copies shall be submitted by contractor well in advancefor the approval of GE
18M&L for replacement of 9mm steel wire rope of 6x36 FMC Construction duly tested for 2 ton EOT Crane complete all as specified & directed. Make : Usha Martin/Mahadev or as approvedby GE on recommandation of OEM. Note: Necessary Test Certificate for steel wire rope shall be submitted by the contractor.
19S&F in replacement of MCCB TPN 63 Amp 16KA rated fixed in CRCA sheet steel enclosure duly powder coated to be mounted on the wall with the help of fastners complete all as specified & directed.
20M&L for radiography testing of crane main hook block by approved firm from BARC Mumbai complete all as specified & directed. Note:The Original film and testing report of radiography shall be submitted by the contractor to GE.
21M&L for Load Testing of 2 TON capacity EOT Craneby applying 25% extra dead weight load, complete all as specified & directed. Note:- Necessary T&P and Dead Weight load should be arranged by contractor at site at their own cost.
22M&L for fixing box type TPN DSL System of 63 Amp rated capacity for main hanger gate. The box type DSL system should be mounted on angle iron brackets of suitable size duly clamped complete all as specified & directed. Note : The cost of angle iron brackets shall be included in the quoted rate.
23M&L for fixingof 32 Amp rated TPN current collector for box type DSL System complete all as specified & directed.
24M&L for fabrication of MS bracket made out of angle iron / channel of suitable size for current collector / cables complete all as specified & directed.
25S&F, testing & commissioning of AC drive, upto5.5kW V/F control operated on 3 phase 415 Volt AC for hoist control CT/LT motor of EOT crane complete all as specified & directed.
26Supply, fixing and making all connection Rotary limit switch capacity 40 Amps 415 volts all as per existing for LT/CT/Hoist motion of 2 ton capacity crane, including taking down old unserviceable rotary limit switchcomplete all as specified & directed.
27S&F in repairs, push button with element in push button box as per required colour codecomplete all as specified and as directed .
28S&F in repairs, power contactor 20 Amps with 2 NO + 2NC , complete all as specified & directed.
29M&L for re-winding of electric motor upto5 HP, 3 Phase 415 volt of any make after disconnecting motor electrically and mechanically systemfromthe elevated heightandtransporting to workshop for repairs, taking out burnt winding wire, cleaning the rotor and stator properly, rewinding the motor with super enameled copper winding wire as per existing gauge, varnishing /drying etc complete, replacing the ball bearings as per existing size, reassembling the motor, shifting and installing at original position , making electrical and mechanical connections and testing for proper working complete all as specified & directed.
30S&F in repairs motor of capacity 2 HP/1.5 KWthree phase RPM 1450 suitable for electric operated motorised door complete all as specified & directed Make : ABB or any make from list of makes, as approved by GE.
31S&F in repair of Gear box matching with motor given at ser item no 26 above and matching with existing make complete all as specified & directed.
32S&F in repairs Hanger door Iron roller wheel of size upto 300mm x 75mmas per exisiting size having groove suitable for movement on iron rail including all T&P required for replacement at site complete all as specified & directed.
33S&F in repairs of Hanger door Iron roller free wheel of size upto 300mm x 75mm as per exisiting size having groove suitable for movement on iron rail including all T&P required for replacement at site complete all as specified & directed.
34S&F in repairs of Hanger door motor chain having width 1 inch and pitch 5/8 inch heavy duty complete all as specified & directed.
35S&F in repairs, power contactor 18 Amps AC3 12A/5.5 KWCE15 C series complete all as specified & directed.
36S&F in repairs, MCB Single pole ofcapacity0-6 Amp rated at 240-410 V, 10 KA complete all as specified & directed.
37S& F in RepairStart/Stop Push Button of Control panel complete all as specified & directed.
38S&F in repair Indicating LED lamp of control panelcomplete all as specified & directed.
39S&F in replacement of PVC insulated flexible copper conductor 3 core 1100 volts grade of size 4 sqmm complete all as specified & directed.
40M&L for periodical inspection / servicing by removal of dirt/dust & carbon particles form electric drives, greasing / oiling of all moving parts including checking & adjustment of boom alignment and minor repair ofboom barrier complete all as specified & directed.
41S&F in replacement ofMCBSP 5- 32 Amp 240 Volts 10KA rating, ISI marked, complete all as specified & directed.
42M&L for periodic inspection/ servicing of Dehumidefire of 175 CFM Model No : FFB-300, Bry air make by removal of dirt/dust & carbon particles form electric drives, checking & adjustmentweather parameter setting complete all as specified & directed. Note: The work shall be executed through any vender having minimum 05 years experiance of similar work in any state/central govt department.
43Comprehensive maintence, testing/Servicing and repair including preventive and periodical maint with renewals and replacement of defective parts of all existing fire protection and fire fightingsystem complete consisting of main fire control panels of 1X 12.5HP Jockey pumpset, 2X 75HP electric driven pumpset, and 1X 90HP Engine driven pump, 1X 12.5HP Terrace pumps , 2X15 HP CFT pumps by necessary decarbonising ,cleaning, tightening & 100 % servicing of of all loose contact, sub panels, pressure switch, presure vessels, fire hydrents, hose reels, canvas hose pipes, gunmetal valves etc with control panel, starters and to keep Fire fighting system in auto runmode on variation in pressure to make 100% serviceability of the complete installed at ATC building of Saraswa AF station. Notes: (i) The work shall be executed through any vender having minimum 05 years experiance of similar work in any state/central govt department. (ii) The contractor rep will visit site once in every month and on occurence of any fault during contract period take serviceability certificate from Users and MES rep.
44Comprehensive maintence, testing/Servicing and repair including preventive and periodical maint with renewals and replacement of defective parts of all existing fire alarm system complete & 100 % servicing of fire alarm panel, smoke/heat detector/response indicator, Hooters, Manual call points complete including checking, cleaning of fire detector by removing dust or dirt, cleaning of heavy greasy deposit if any, checking the connection of battaries, specific gravity of electrolyte, the alarm function control panel and indicating eqpts be checked by the operation of trigger device in each zone as described the system installed at following Bldgs of Sarsawa AF Station. Notes: (i) The work shall be executed through any vender having minimum 05 years experiance of similar work in any state/central govt department. (ii) The contractor rep will visit site once in every month and on occurence of any fault during contract period take serviceability certificate from Users and MES rep.
45ATC Bldg (G+4), addressable type fire alarm system
46SRE Bldg (G+6), conventional type fire alarm system
47OPS Bldg (01 floor), conventional type fire alarm system
48Notes for BOQ item No 39.00, 41.00 & 41.01 to 41.03 :-(a)Cost of new components shall be paid for separately under relevant item of BOQ. (b) Contractor"s rep will visit every month to, check and inspect every panel and on occurance of any fault during contract period take servicibility certificate duly signed by the users and MES Rep. (c) Cost of minor spares any type not costing more than Rs 500.00 per month in totaldeemed to be included in the quoted rate. (d) Payment will be processed on production of servicibilty certificate only and a panel recovery @ double the quoted rate will be charged for non carrying out of periodic serviceability check. (e)The rates quoted shall be inclusive T&P required for carrying repairs and stationery for maintaining records of periodic maintenence all as described by the Engr in charge.
49M&L for wiring with new 1100volt grade, 1.5 sqmm 2 core, FRLS, multistranded copper wire ISI marked drawn in and including PVC , 20mm dia, ISI Marked conduit for laying of cable fixed over the wall/roof, surface through saddles /spacers etc for making connections to fire detectors /MCP to control panels etc including taking down old unserviceable wiring with conduit pipe complete all as specified & directed.
50Taking down old unserviceablemultisensor detector any type by moveable ladder complete all as specified & directed
51S&F addressable type multisensor detector with heat and smoke combination UL listed with dual LED for 360 degree visibility, advance detection & communication protocal, regular 100mm base, address setting by 8 digit DIP switch, IP-42 rating complete all as specified & directed.
52S&F conventional type multisensor detector with heat and smoke combination UL listed with dual LED for 360 degree visibility, advance detection, regular 100mm base, IP-42 rating complete all as specified & directed. Note for BOQ item No. 44.00 & 45.00: Replaced unit shall be compatible with existing fire alarm system installed in the bldg.
53Taking down old unserviceable hooter any type complete all as specified & directed
54S&F hooter UL listed with MS housing, operating voltage 12/24 volt DC, current 220mA, 4 watt speaker having minimum audible range of 90db at 10 feet, IP-42 rating complete all as specifed & directed
55S&F hooter UL listed with MS housing, operating voltage 12/24 volt DC, current 220mA, 4 watt speaker having minimum audible range of 90db at 10 feet, IP-42 rating with control module for addressing complete all as specifed & directed. Note for BOQ item No. 47.00 & 48.00: Replaced unit shall be compatible with existing fire alarm system installed in the bldg.
56S&F in replacementof Battary Charger 220Volt AC/12 Volt DC ,5 Amps compactpanel mounting type suitable for Fire fightingpanel for charging the battery of FF engine complete all as specified & directed.
57S&F in replacement, testing and commissioning of Battary 12V, 7AH sealed maintenance free lead acid complete all as specified & directed.
58S&F in replacement, testing and commissioning of Battary 12V, 90AH sealed maintenance free lead acid complete with battery terminals all as specified and directed.
59S&F in replacementaddressable type control panel of 8 zone complete with charger, rectifier, 12 Volts battary, alarm display with all other neccessary attachments complete all as specified & directed.
60S&F in replacement testing and commissioning of pressure switch universal type complete all as specified & directed.
61S&F in replacement testing and commissioning of pressure gauge 100mm dial & 0 to 14 Kgs rating complete all as specified & directed.
62S&F in replacement fire hydrant landing valve type B ( double head outlet) of 63 mm dia conforming to IS 13039-1991 along with 2 nos cast iron hand wheel , 2 nos female Instantaneous outlet, 2 nos ABS blank cap and chain, complete all as specified & directed.
63S&F in replacement remote response indicators UL listed, flush/ceiling wall mounted with dual LED for wider visibility, operating voltage 5 to 28 volt DC, current 10mA, IP-42 rating complete all as specified & directed
64S&F in replacement hose box wall mounting type for keeping 2 Nos hose pipe of length 15 meter each, branch pipe.nozzle, coupling etc made out of 16 gauge mild steel sheetsize 800mm x 600mm x 250mm , acrylic fronted double door with lock , 2 keys and a break glass recess for Key, painted fire red, complete all as specified & directed. Make: Padmini/DSS/Newage.
65S&F in replacement of branch pipe gun metal 63mminstantaneous inlet, made threaded outlet, 15mm bore nozzle long conforming to IS 903, complete all as specified and as directed Make: Padmini/DSS/Newage.
66S&F in replacement of 63 mm dia 15 meter long CP hose conforming to IS 636 complete with male and female coupling conforming to IS 903,complete all as specified and as directed Make: Padmini/DSS/Newage.
67S&F in replacement Non returnbutterfly valve 150mm bore PN-16 complete all as specified & directed
68S&F in replacement ofNon return butterfly valve 100mm bore PN-16 complete all as specified & directed
69S&F in replacement sluice valve of class PN 1.6 flanged both ends 150mm bore complete all as specified & directed
70S&F in replacement sluice valve of class PN 1.6 flanged both ends 200mm bore complete all as specified & directed
71S&F in replacement GI tubing 40mm dia medium grade complete all as specified & directed
72S&F in replacement GI tubing 25mm dia medium grade complete all as specified & directed
73S&F in replacement 25 mm bore Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed
74S&F in replacement foot valve of 150mm dia conforming to IS 4038, complete all as specified & directed
75S&F in replacement foot valve of 100mm dia conforming to IS 4038, complete all as specified & directed
76S&F in replacement MCCB 200 Amps 4 Pole breaking capacity 25 KA,415 V,ICS=75 % of ICU Adjustable type with fastening elements including taking down old unsv mccb, complete all as specified & directed.
77S&F in replacement MCCB 160 Amps 4 Pole breaking capacity 16 KA,415 V,ICS=75 % of ICU Adjustable type with fastening elements including taking down old unsv mccb, complete all as specified & directed.
78S&F in replacement MCCB 63 Amps 4 Pole breaking capacity 10 KA,415 V,ICS=75 % of ICU Adjustable type with fastening elements including taking down old unsv mccb, complete all as specified & directed.
79S&F in replacement 3 pole power contactor CTX 150 - 150 Amp suitable for 75 HP pumpset complete all as specified & directed.
80S&F in replacement of 3 pole power thermal relay RTX 150 suitable for CTX 150- 150 Ampfor 75 HP pumpset complete all as specified & directed.
81S&F in replacement of 3 pole motor protection circuit breaker MPX32H - 32 Amp suitable for 20 HP pump set complete all as specified & directed.
82S&F in replacement of 3 pole phase failure relay VSP D2 having protection against single phasing, over/under voltage, phase reversing, unblancing, panel mounted suitable for 20 HP pump set complete all as specified & directed. Make : Minilec or as mentioned in list of makes.
83S&F in replacement DOL starter with single phase preventer3 phase 415 volt complete with contactor, relay, wall mounted suitable for 05 HP pump set complete all as specified & directed.
84S&F in replacementAlarm Buzzer Industrial Electronic wind screw motorsuitable for outdoor installation, totally enclosed 3 phase 415 volt of 5 HP rating ISI marked duly housed in weather proof enclosure high Decibelsiren sound range upto 2 KM complete all as specified & directed.
85Comprehensive, preventive and periodical maintance of 01 No . electrically operated passenger lift of capacity 544 kg Kgs carrying 08 passengers Make : Schindler, suitable for serving G+3 floors (total 4 landings) with electric power opearted doors, auto electric levelling device completewith ARD facility installed at ATC building to be maintained roundthe clockas described here-in after in reliable, safe and efficient operating condition by regularly examine lubricating and adjust the mechanical and electrical driving equipment governer, sleeve shaft assembly bearing / contacts & governor jaws,limit switches (car & hall mechanical buttons, car & hall position indicators, car direction indicators and all other car and landing signal fixtures, deflectors, car and counter weight guide rails and buffers,equipment and carry out planned maintenance in a systematic and controlled manner using techniques and expertise consultancy includingreplacement ofspares parts as and when requiredall asdirected and specified to the entire satisfaction of GE. Note :AMC to be carried out through OEM only. MOU to this effect shall be submitted by the contractor to Engr-in-charge before starting of work.
86S&F in repair Module VVVF5+ drive T2L/C2 EU/NA suitable for schindler make 08 passenger lift complete all as specified & directed.
87S&F in repair PAPF Kit for Biodyn 12 suitable for schindler make 08 passenger lift complete all as specified & directed.
88S&F in repair ME_PCBA SEM 21.Q version ""F"" (594239S) suitable for schindler make 08 passenger lift complete all as directed and specified.
89S&F in repair SMI61.Q, anti-sulphur resistors suitable for schindler make 08 passenger liftcomplete all as specified & directed.
90S&F in replacement ofLED Solar street light fitting 20 Watt not less than 125 Lumen per watt delivered lumen efficacy total syatem not less than 5000 lumen solar PV module should be 12V 60W Mono-crystalline & solar charge controller should be MPPT & its capacity not less than 12V,6Amp with battery (LIiFeP40) with BMS 12.8 V 24 Ah & its backup should be 2 days with dimming & its life span must be more than 50000 Hrs complete all as specified & directed.
91S&F in replacement 50 mm bore medium Grade GI pipe for fixing of solar street light complete all as specified & directed.
92Supply, Install, Testing and Commissioning in replacement of"Solar Hot Water System" (Flat Plate Collector) based on indirect transfer of heat of capacity 1000 LPD including electrical backup and angle iron structure for mounting of Tank & collector plate of suitable sizecomplete all as specified & directed.
93S&F in replacement of1000 ltr capacity Rotational moulded polyethylene water storage tanks ( cylindrical vertical with closed top ) hoisted and fixed in position all as specified in SSR Part - Icomplete all as specified & directed.
94M&L in replacement for Hot water pipe duly insulated with glass wool and aluminum cladding 15 mm bore medium grade complete all as specified & directed.
95M&L in replacement for Hot water pipe duly insulated with glass wool and aluminum cladding 20 mm bore medium grade complete all as specified & directed.
96S&F in replacement of solar water heater element of 3 KW capacity as per sample or site requirement complete all as specified & directed.
97S&F in replacement of existing vertical tank with500 ltr capacity Rotational moulded polyethylene water storage tanks ( cylindrical vertical with closed top ) hoisted and fixed in position all as specified in SSR Part -I,complete all as specified & directed.
98S&F in replacement MCB TPN63 Amps,415 volts,curve "B", breaking capacity 10 KA,complete all as specified & directed
99S&F in replacement of Thermostat suitable for 500 LPD capacity solar water heater complete all as specified & directed.
100M&L for servicing of Solar water heater including cleaning of solar panel repalcement of nut bolts gasket and cleaning of blocked pipe with chemical and making it functional before winter season complete all as specified & directed.
101M&L for attending complaints related to solar water heater installed at Airforce station Sarsawa by performing following tasks complete all as specified & directed:- (a) checking all connections, (b) Checking pipe blockage. (c ) Checking of thermostat. (d) Checking of Electrical element. (e ) checking of Tank. (f) Checking of Insulation of Pipe. (g) Checking of Any leakage.
102M&L for inspection , servicing and repair of diesel engine of fire fighting sysytem with B check including minor repairs and replacement of worn out spares such as fuel filter, air filter , oil filter , hose pipes, cut out, electrical wiring,tightening of nut bolts, washers, tappet adjustments, cleaning of head assembly including and de-carbonising, changing of lubricating oil , checking and adjustment of fuel injector system and self starter etc; complete includingtesting complete all as specified & directed. Notes: (i) Engine oil & coolant shall be measured & paid seperately. (ii) The work shall be executed through any vender having minimum 05 years experiance of similar work in any state/central govt department approved by GE.
103Supplyonly coolant premix with additive for protection from corrosion, cavitation and scale for fire engine complete all as specified & directed. Make: Castrol / Servo / HP / Valvoline / Bharat Petrolium
104SupplyonlyEngine oil, multi grade 20 W 40 or equivalent gradecomplete all as specified & directed. Make: Castrol / Servo / HP / Valvoline / Bharat Petrolium
105M&L for replacement ofbattery terminal of brass suitable for 12V, 90 AH to 150 AH battery all as specified and directed.
106M&L forreplacement of battery lead, copper conductor, single core, 25 Sq mm, multi stranded, PVC insulated with suitable terminals at both ends of lengths as per site requirements complete all as specified & directed.
107Dismantling and taking down radiator assembly from engine of fire fighting system for repairs including de-scaling, bracing of inner tubes and body as required to plug leakages, repairs to radiator frame and tank including cutting and removing deteriorated inner tubes, chamber, frame etc.and re-constructing the same with same material in original size and shape, cleaning / straightening of fins and re fixing after repairs including replacement of worn out nut bolts, washers, aluminium water elbow,radiator cap, radiator beds etc; and pressure testing for leakage complete all as specified & directed.
108For Credit Schedule refer tender documents. The amount of credit schedule shall be deducted from total quoted amount of BOQ to arrive contract sum.