Survey,Supply, Transportation, Carriage, Erection,Testing And Commissioning For Creation Of 630 Kva Sub Station At District Hospital Udhampur For Make Shift Arrangements In New Medical College Udhampur On Turnkey Basis, udhampur-Jammu And Kashmir

Power Development Department has published Survey,Supply, Transportation, Carriage, Erection,Testing And Commissioning For Creation Of 630 Kva Sub Station At District Hospital Udhampur For Make Shift Arrangements In New Medical College Udhampur On Turnkey Basis. Submission Date for this Tender is 27-01-2024. Electrification Work Tenders in udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

41612183
Survey,Supply, Transportation, Carriage, Erection,Testing And Commissioning For Creation Of 630 Kva Sub Station At District Hospital Udhampur For Make Shift Arrangements In New Medical College Udhampur On Turnkey Basis
Open Tender
Indian
Jammu And Kashmir
udhampur
27-01-2024

Tender Details

Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Creation Of 630 Kva Sub Station At District Hospital Udhampur For Make Shift Arrangements In New Medical College Udhampur On Turnkey Basis- 1 Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Erection Of 11 Kvtapping Point At Mid Span At District Hospital Udhampur. 2 Gi V Cross -Arm With Top Bracket Including Clamps 3 Gi Channel X-Arm Including Clamps And Angle For Braces 4 50Mm² Acsr Rabbit Conductor 5 11 Kv Go Ab Switch 3 Phase, 3 Pole, 200 Amp, Vertical 6 11 Kv Polymer Composite Pin Insulator 12 Kv, 5 Kn, Lighting Impulse 75 Kv Positive And 80 Kv Negative, Creepage Distance 320Mm. 7 11 Kv Polymeric Composite Disc Insulator 12 Kv, Min Failing Load 45 Kn, Lightening Impulse 75Kvpositive And 80 Kv Negative, Creepage Distance 320Mm With Fitting 8 Galvanized Nuts And Bolts 9 Danger Plates With Clamps 10 Anti Climbing Device With Clamps 11 Earthing Complete Bygi Rod 20 Mm, 2.5 Mtr Long Through G.I. Strip 25X3 Mm 12 Painting Of 9 Mtr St Poles With One Coats Of Red Oxidepaint. 13 Painting Of 9 Mtr St Poles With Two Coats Of Aluminiumpaint. 14 Pg Clamps 15 Galvanised Stay Set With 50X8mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 200X 200 X 6 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Complete 16 Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Creation Of 630 Kva Sub Stn. At District Hospital Udhampur 17 11 / 0.433 Kv, 3-Phase Distribution Transformer 630 Kva ( To Be Provided By Pwd Authority At Site ) 18 Gapless Surge Arrestor, 9 Kv, 10 Ka , La With Polymer Housing Stn. Type 19 11 Kv Go Ab Switch 3 Phase, 3 Pole, 200 Amp, Vertical 20 11 Kv Horn Gap Fuse Set 3 Phase 200 A 21 300Mm² 1.1 Kv Grade, Pvc Insulated Stranded Conductor Frls Type 22 11 Mtr. Long St Pole ( St-410 Sp56 ) 23 11 Kv Polymeric Composite Disc Insulator 12 Kv, Min Failing Load 45 Kn, Lightening Impulse 75Positive And 80 Kv Negative, Creepage Distance 320Mm With Fitting 24 Gi Channel / Angle / Flat Of Sizes Including Clamps 25 Galvanized Nuts And Bolts. 26 Earthing Of Sub Stn. Excavation Of Earth Pit Of Dia 650Mm & Depth 3000Mm Installation Of Earthing Pipe Of 40Mm Nominal Bore & 4Mm Wall Thickness & Length 2.5 Mtr. Long As Per Is 1239. G.I Strip For Neutral Earthing Of Size 25Mmx3mmfor Connection Of Transforemr Body, Go Set & Lightening Arrestor As Per Is 2629 / 85, Gi Nuts & Bolts Refilled With Earth Enhancement Materials And Earth Chamber With Rcc Slab Cover 27 Transformer Pad / G.I Channel Bedding 28 11 Kv Polymer Composite Pin Insualtor, 12 Kv, 5Kn Lightening Impulse 75 Kv Positve And 80 Kv Negative, Creepage Distance 320Mm 29 Galvanised Stay Set With 50X8mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 200X 200 X 6 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Complete 30 Pg Clamps 31 Danger Plates With Clamps 32 Gi Barbed Wire For Anticlimbing 33 3-Phase Ht Trivector Meter With Ct Pt Unit 34 Cement Bottoming 1:2:4 Mix As Per Rec Standard 0.5 Cum Per Pole 35 Painting Of St Poles 11 Mtr. Long With 2 Coat Of Al. Paint 36 Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Erection Of 120Mm², Ht Ab Cable On 9 Mtr St Poles At District Hospital Udhampur. 37 9 Mtr. Long St Poles ( St-410 Sp33 ) 38 120Mm² Ab ( Ht ) Cable ( 3X120+1X95mm² ) Xlpe ( 11 Kv 3C+Earth ) 39 Heat Shrinkable Outdoor Cable Termination Kit 40 Suspension / Tension Clamp With Eye Hook 41 Galvanized Nuts And Bolts. 42 Danger Plates With Clamps 43 Anti Climbing Device With Clamps 44 Earthing Complete Bygi Rod 20Mm 2.5 Mtr. Long Through Gi Strip 45 Painting Of 8 Mtr St Poles With Onecoat Of Red Oxide Paint 46 Painting Of 8 Mtr St Poles With Two Coat Of Aluminium Paint 47 Cement Bottoming 1:2:4 Mix As Per Rec Standard 0.5 Cum Per Pole 48 Mid Span Straight Through Jointing Kit For 11 Kv Abc 120Mm² 49 Galvanised Stay Set With 50X8mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 200X 200 X 6 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Complete

Key Value

Document Fees
INR 600 /-
EMD
INR 11500.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Survey,Supply, Transportation, Carriage, Erection,Testing and Commissioning for Creation of 630 KVA Sub station at District Hospital Udhampur for make shift arrangements in New Medical College Udhampur on turnkey basis.
Sl. No. Item Description
1Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KVTapping point at Mid span at District Hospital Udhampur.
2GI V Cross -arm with top Bracket including clamps
3GI Channel X-arm including clamps and Angle for braces
450mm² ACSR Rabbit Conductor
511 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
611 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
711 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting
8Galvanized Nuts and Bolts
9Danger Plates with Clamps
10Anti climbing device with clamps
11Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
12Painting of 9 mtr ST poles with one coats of Red oxidepaint.
13Painting of 9 mtr ST poles with two coats of Aluminiumpaint.
14PG Clamps
15Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
16Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for creation of 630 KVA Sub stn. at District Hospital Udhampur
1711/0.433 KV, 3-phase distribution Transformer 630 KVA(to be provided by PWD authority at site)
18Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type
1911 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
2011 KV Horn gap fuse set 3 phase 200 A
21300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
2211 mtr. Long ST pole (ST-410 SP56)
2311 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75Positive and 80 KV Negative, creepage distance 320mm with fitting
24GI Channel /Angle/flat of sizes including clamps
25Galvanized Nuts and Bolts.
26Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
27Transformer pad/G.I Channel bedding
2811 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
29Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
30PG Clamps
31Danger Plates with Clamps
32GI Barbed wire for Anticlimbing
333-phase HT Trivector meter with CT PT Unit
34Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
35Painting of ST poles 11 mtr. long with 2 coat of Al. paint
36Survey,supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 120mm², HT AB Cable on 9 mtr ST poles at District Hospital Udhampur.
379 mtr. Long ST poles (ST-410 SP33)
38120mm² AB (HT) Cable (3x120+1x95mm²) XLPE (11 KV 3C+Earth)
39Heat shrinkable outdoor cable termination kit
40Suspension /tension clamp with eye hook
41Galvanized Nuts and Bolts.
42Danger Plates with Clamps
43Anti climbing device with clamps
44Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip
45Painting of 8 mtr ST poles with onecoat of Red oxide Paint
46Painting of 8 mtr ST poles with two coat of Aluminium Paint
47Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
48Mid span straight through jointing kit for 11 KV ABC 120mm²
49Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail