}

Tender For Repair/Maintenance Of Dg Sets At Various Locations And Repair/Maintenance Of Amf Panel In Technical And Domestic Area At Af Stn Hasimara, hasimara-West Bengal

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Dg Sets At Various Locations And Repair/Maintenance Of Amf Panel In Technical And Domestic Area At Af Stn Hasimara. Submission Date for this Tender is 08-02-2024. Diesel Generators Tenders in hasimara West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

41596942
Corrigendum : Tender For Repair/Maintenance Of Dg Sets At Various Locations And Repair/Maintenance Of Amf Panel In Technical And Domestic Area At Af Stn Hasimara
Open Tender
Indian
West Bengal
hasimara
08-02-2024

Tender Details

Tender For Repair/Maintenance Of Dg Sets At Various Locations And Repair/Maintenance Of Amf Panel In Technical And Domestic Area At Af Stn Hasimara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Nature of Work : REPAIR/MAINT OF DG SETS AT VARIOUS LOCATIONS AND REPAIR/MAINT OF AMF PANEL IN TECHNICAL AND DOMESTIC AREA AT AF STN HASIMARA
Sl. No. Item Description
1M&L for conducting ‘B’ check ofDG set of capacity 35/40 KVAto carry out the following maintenance/servicing, complete all as specified and as directed :- (i) Change of diesel filter/oil filter, top up/replacement of engine oil, coolent if required. (ii) Check and clean engine, alternator battery,instrument panel, elect panel, timer, contactors, meters and others etc. (iii) Tightening of all nuts & bolts of DG set and its accessories. (iv) Check for any diesel lekage from any point and rectify if observed. (v)Check and adjust fan belt tension, replace the fan belts if found damaged. (vi) Check leakage of smoke from exhaust system/silencer, repair if required. (vii) Check electrical connections of engine. The wiring shall be maintened properly and engine starting system from engine instrument panel is to be kept in order(viii) Check and tighten the AVM pads, nuts and bolts,change AVM pads if found damaged. AVM to be provided by contractor. (ix) Check exhaust pipe,flange and lagging Repair if found damaged. (x) Check output of alternator, if found OK adjust the same to specified values in case of brush type. (xi) Checking of all hoses and cleanup,change/tighten if required.(xii) Checking of all hoses and cleanup if required. Also changing air filter elements,if required. (xiii)Oiling,Greasing and checking for proper & smooth functioning. etcand refitting, testing on load complete (xiv) Repair / Calibration of Injector complete all as specified and directed. (xv) Overhauling and testing of governor assembly including machine work Note 1. :- Price for minor spare parts and fuel filter, head/filter gasket, air filter, cleaning of radiator, fuel pipe, cleaning of nozzle, tapit setting included in the quoted rates against each capacity. Note 2. Price for major spare parts and coolent required for replacement shall be measured and paid separately under respective item of schedule.
2All as per item No. 1.00 here in before but DG set 20 KVA, complete all as specified and as directed.
3All as per item No. 1.00 here in before but DG set of capacity 50 KVA, complete.
4All as per item No. 1.00 here in before but DG set of capacity 62.5 KVA, complete.
5All as per item No. 1.00 here in before but DG set of capacity 82.5 KVA, complete.
6All as per item No. 1.00 here in before but DG set of capacity 125 KVA, complete.
7All as per item No. 1.00 here in before but DG set of capacity 160 KVA, complete.
8All as per item No. 1.00 here in before but DG set of capacity 200 KVA, complete.
9All as per item No. 1.00 here in before but DG set of capacity 250 KVA, complete.
10All as per item No. 1.00 here in before but DG set of capacity 320 KVA, complete.
11All as per item No. 1.00 here in before but DG set of capacity 400 KVA, complete.
12All as per item No. 1.00 here in before but DG set of capacity 500 KVA, complete.
13All as per item No. 1.00 here in before but DG set of capacity 750 KVA, complete.
14Supply only cylinder liner suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
15Supply only piston ring set suitable for DG engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
16Supply only piston pin suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
17Supply only piston circlips suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
18Supply only "O" seal ring, first groove suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
19Supply only "O" seal ring, 2nd & 3rd groove suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
20Supply only main bearing upper & lower suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
21Supply only oil seal ring suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
22Supply only radiator cap suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
23Supply only thrust bearing suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins) )
24Supply only inlet/exhaust valvesuitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
25Supply only inlet/exhaust valve seat ring suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
26Supply only valve guide suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
27Supply only valve collet suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
28Supply only valve stem cap suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
29Supply only valve seal suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
30Supply only washer for cylinder head cover suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
31Supply only seal ring (rocker arm) suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
32Supply only water darin cock sub assy suitable for DG engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
33Supply only front oil seal suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
34Supply only rear oil seal suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar / Crompton Greaves)
35Supply only connecting rod bearing suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
36Supply only connecting rod bush suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
37Supply only oil sump washer suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
38Supply only inlet pipe for feed pump suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
39Supply only V-belt suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
40Supply only copper washer suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins) )
41Supply only HCT switch suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
42Supply only thermostat body suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
43Supply only radiator water inlet hose suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
44Supply only radiator water outlet hose suitable for DG set engine 15 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
45Supply only thermostat element suitable for DG set engine 35 to 62.5 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
46Supply only cylinder liner suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
47Supply only piston ring set suitable for DG set engine 82.5 KVA to 250 KVA complete all as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
48Supply only piston pin suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
49Supply only piston circlips suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
50Supply only O seal ring, first groove suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
51Supply only O seal ring, 2nd & 3rd groove suitable for DG set engine 82.5 KVA to 250 KVA KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
52Supply only main bearing upper & lower suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
53Supply only Oil seal ring suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
54Supply only radiator cap suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
55Supply only thrust bearing suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
56Supply only inlet/exhaust valvesuitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
57Supply only inlet/exhaust valve seat ring suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
58Supply only valve guide suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
59Supply only valve collet suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
60Supply only valve stem cap suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
61Supply only valve seal suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
62Supply only washer for cylinder head cover suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
63Supply only seal ring (rocker arm) suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
64Supply only water darin cock sub assy suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
65Supply only front oil seal suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
66Supply only rear oil seal suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
67Supply only connecting rod bearing suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
68Supply only connecting rod bush suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
69Supply only oil sump washer suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
70Supply only inlet pipe for feed pump suitable for Dgsetengine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
71Supply only V-belt suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
72Supply only copper washer suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
73Supply only HCT switch suitable for DG setengine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
74Supply only thermostat Body suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
75Supply only radiator water inlet hose suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
76Supply only radiator water outlet hose suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
77Supply only thermostat element suitable for DG set engine 82.5 KVA to 250 KVA, complete all as specified and as directed. (Make- Kirloskar/Crompton Greaves/Cummins)
78Dismantling the weak self starter, 24 Volt, motor of capacity & make as taken out mentioned above, segregating serviceable and semi/unserviceable parts, cleaning serviceable parts, drying, lubricating. Reassembling the self starter motor with cleaned serviceable parts along with the new parts for armature and testing, complete all as specified and as directed by Engr-in Charge.
79All as per item No. 78.00 here in before but for armature brake spring and testing complete.
80All as per item No. 78.00 here in before for bush set (set of 02 Nos) and testing complete.
81All as per item No. 78.00 here in before but for bush spring and testing complete
82All as per item No. 78.00 here in before but for bush holder and testing complete
83All as per item No. 78.00 here in before but for bushing commutator end and testing complete.
84All as per item No. 78.00 here in before but for carbon bush set and testing complete.
85All as per item No. 78.00 here in before but for drive bushing pinion drive lever and testing complete.
86All as per item No. 78.00 here in before but for end cap gasket and testing complete.
87All as per item No. 78.00 here in before but for field coil set (set of 4 Nos) and testing complete.
88All as per item No. 78.00 here in before but for magnetic switch and testing complete.
89S & F rectangular 03 Nos CT along with matching analog ammeter having dial range 0-150 Amp and connected with control panel cable not less than 1.5 Sqmm with number ferrul lugs etc, complete all as specified and as directed. Make: L & T/Schnider/ABB/Siemens
90S & F rectangularanalog voltmeter having dial range 0-400 Volt and connected with control panel cable not less than 1.5 Sqmm with number ferrul lugs etc, complete all as specified and as directed. Make: L & T/Schnider/ABB/Siemens
91S & F power pack, industrial type,150 AH, 12 Volt ,25 plate, along with copper lead and clamp, complete all as specified and as directed. Make: Exide/Amaron/AMCO
92S & F power pack, industrial type,180 AH, 12 Volt,25 plate, along with copper lead and clamp, complete all as specified and as directed. Make: Exide/Amaron/AMCO
93M & L for repair of fuel injection pump/PT pump including dismanting the fuel injection/PT pump, segregating serviceable and semi/unserviceable parts, replace all unserviceable parts and cleaning serviceable parts,drying,lubricating,re-assembling the FIP/PT pump with cleaned serviceable parts along with new parts as required, calibration, testing complete on computerised testing equipment, complete all as specified and as directed.
94M & L for repair of alternator 3 Phase 440V of capacity 15 to 62.5 KVA, including dismantling the alternator from its mounting by unscrewing the nut & bolts. Cleaning the whole assy of alternator, replace the commutator, carbon brush, rectifier, slip rings, slip ring end bearing, drive end bearing etc and re-assebling the all parts and mounted the alternator on its same place and do the connection as previous, complete all as specified and as directed.
95All as per item No. 94.00 here in before but capacity 82.5 KVA to 250 KVA, complete.
96All as per item No. 94.00 here in before but capacity 300 KVA to 750 KVA, complete all as specified and as directed.
97M & L for repair of AMF panel controller suitable for DG set of capacity 35 KVA to 62.5 KVA, complete.
98M & L for repair of AMF panel controller suitable for DG set of capacity 82.5 KVA to 200 KVA, complete all as specified and as directed.
99M & L for repair of AMF panel controller suitable for DG Set of capacity 250 KVA to 320 KVA, complete all as specified and as directed.
100M & L for repair of AMF panel controller suitable for DG set of capacity 400 KVA to 500 KVA, complete all as specified and as directed.
101M & L for repair of AMF panel controller suitable for DG set of capacity 750 KVA, complete all as specified and as directed.
102Repair to existing unserviceable automatic main failure (AMF) panel of capacity 15 to 250 KVA installed at various locations by carrying out the following repair work: (a) Disconnecting the incoming power supply and taking out and dismantling the electrical components from the AMF panel of any make and replacement of unserviceable/burn out/defective parts and cleaning/servicing entire interior and exterior serviceable parts and refixing the same in existing position including connections, testing and commissioning etc, complete all as specified and as directed. (Note: (i) Spare/parts shall be measured and paid seperately as "supply only" under respective items. (ii) Fixing charge for spare/parts shall deemed to be inclusive under this item.
103Supply only DIN type fuse bases suitable for fixing of 250 Amp fuse, complete all as specified and as directed.
104Supply only DIN type fuse bases suitable for fixing of 160 Amp fuse, complete all as specified and as directed.
105Supply only DIN type fuse of 250 Amp rating, size 01, complete all as specified and as directed.
106Supply only DIN type fuse of 125 Amp rating, size 01, complete all as specified and as directed.
107Supply only DIN type fuze of 160 Amp rating, size 01, complete all as specified and as directed.
108Supply only MCB, SP, 6-32 Amps, "C" Curve suitable for AMF panel 35-250 KVA complete all as specified and directed.
109Supply only MCB, SPN, 6-32 Amps, "C" Curve suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
110Supply only MCB, TPN, 6-32 Amps, "C" Curve suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
111Supply only instrument operating relay, coil voltage 12 volts DC suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
112Supply and fix in repair 4 pole power contactors type MCX-11 (50 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97013 or equivalent in Schneider/ABB/Legrand.
113Supply and fix in repair 4 pole power contactors type MCX-12 (63 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97014 or equivalent in Schneider/ABB/Legrand.
114Supply and fix in repair 4 pole power contactors type MCX-22 (100 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97017 or equivalent in Schneider/ABB/Legrand.
115Supply and fix in repair 4 pole power contactors type MCX-23 (130 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97018 or equivalent in Schneider/ABB/Legrand.
116Supply and fix in repair 4 pole power contactors type MCX-32 (160 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97020 or equivalent in Schneider/ABB/Legrand.
117Supply and fix in repair 4 pole power contactors type MCX-33 (200 Amp) with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97021 or equivalent in Schneider/ABB/Legrand.
118Supply and fix in repair 4 pole power contactors type MCX-34 (255 Amp)with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97022 or equivalent in Schneider/ABB/Legrand.
119Supply and fix in repair 4 pole power contactors type MCX-42 (360 Amp)with suitable coil voltage as per site requirement, complete all as specified and as directed. Make : L & T cat part No CS97024 or equivalent in Schneider/ABB/Legrand.
120Supply and fix in repair side mounting add-on aux contact block (1NO+1NC) suitable for MNX50-80/MCX22-23, complete all as specified and as directed. Make : L & T/Schneider/ABB/Legrand
121Supply and fix in replacement side mounting add-on aux contact block (1NO+1NC) suitable for MNX95-650/MCX32-47, complete all as specified and as directed. Make : L & T/Schneider/ABB/Legrand
122Supply only selector switch for Amp meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
123Supply only selector switch for Volt meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
124Supply only digital panel meter with built in transducer suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
125Supply only MCCB, 4 pole, 100-125 Amps, 36 KA suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
126Supply only MCCB, 4 pole, 200 Amps, 36 KA suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
127Supply onlyoil pressure meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
128Supply only LUB oil temp meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
129Supply onlyheat temp meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
130Supply only battery charging meter suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
131Supply only bottle fuse link size A4, 415 Volt AC, 50 Hz suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
132Supply only fuse holder suitable for bolted fuse links of fuse range 2-20 A suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
133Supply only signalling Device type LED, 230 V AC suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
134Supply only current transformer, copper wound suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
135Supply only switch selector for operating diesel generator suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
136Supply only automatic battery charger SMPS based, 12V DC suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
137Supply only automatic battery charger SMPS based, 24V DC suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
138Supply only delay timer 0.6 S-60M*2 C/O suitable for AMF Panel 35-250 KVA, complete all as specified and as directed.
139Supply only standard push button and selector actuators suitable for AMF panel 35-250 KVA, complete all as specified and as directed.
140Supply and fix in repair automatic voltage regulator suitable for any make and capacity from 63 KVA to 125 KVA, complete all as specified and as directed.
141Supply and fix in repair Automatic voltage regulator suitable for any make and capacity from 125 KVA to 250 KVA, complete all as specified and as directed.
142Supply and fix in repair microprocessor based automatic main failure controller, wall mounting with scrolling down/decrement key, scrolling up/increment key, supply voltage 9V to 36V Dc, operating and storage temperature 20 to +70 degree C, supply current standby <10mA, running 70mA, overall accuracy class - 1, AC voltage range L-N =350VRMS, digital output rating - open drain relay coil driver, 300MA, 32 V DC max, short circuit protected with glowing relay coil driver, 300 mA, 32 V Dc max short circuit protected with glowing LED indicates fault in the system (DG/mains) to input and output operating voltage, switch inputs (LLOP, LFL, HTC alarm, emergency stop), switch I/P switch outputs main contactor on, DG contactor on, start, stop, horizontal main I/P voltage, DG I/P voltage, load current with programming, parameter are mains low/high low (phase to neutral), DG Low/High voltage (phase to neutral), engine start delay, mains restore time, DG Low/High frequency, programmable CT ratio, phase unbalance voltage display parameters main & DG voltage, laod current, hour counter, KWH counter complete all as per existing one, complete all as specified and as directed.
143Supply and fix in repair switch selector for operating, manual/auto, complete all as specified and as directed.
144Supply and fix in repair based relay board module DC, complete all as specified and as directed.
145Supply and fix in repair microprocessor based digital AVF meter with scroll press facility alongwith accuracy class: 1.0 ( 11% of FS + 1 count), voltage input: 5 to 500 V, AC P-P, 50 to 250 V AC P-N, current input: 0.1 to 5 amps AC deirect selectable upto 600/5 ratio, Aux supply: 230 V AC, 50 Hz linear CT ration (only primary) connection (3p/$w, 3P#w, 1P/2W) complete all as per existing one, complete all as specified and as directed.
146Supply and fix in repair DC power instrument in sheet steel enclouser with capacity of input 220 V AC, 50 Hz and output 12 and 24 Volts by selecting the customize output 12 and 24 Volts and displaying Amp meter and LED indicator function complete all as per existing one, complete all as specified and as directed.
147M & L earthing complete with GI earth plate electrode 600mm x 600mm x 6mm thick burried directly in ground vertically to a depth not less than 2.25m below ground level with the top edge of earth plate at depth not less than 1.5m below ground level connected with galvanised earth strip of size 32x6mm dia by means of bolts, nuts,check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 50mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10mm dia round bar),including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed,including necessary earth work and disposal of spoil to a distance not exceeding 50m and necessarytesting on completion inclduing taking down old one, complete all as specified and as directed.
148Note: An amount of Rs.43269.00 indicated in tender documents as"Schedule of Credit" (Schedule "A" Part - II) shall be deducted from the total quoted amount of BOQ to arrive at the contract sum.
149Supply and fixing energy efficient ‘LED Flood Light120 W LED luminairewith Aluminium dia cast housing, toughened glass cover with IP 66 protection, CCT 5700 K including fixing arrangment on wall/pole / surface and connecting cable up to nearest ceilign rose into flexible PVC conduit. Make : Crompton/Havells/ Surya/Philips
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail