Tender For Provision Of Amf Panel For Dg Set Of Different Capacity Under Ge 869 Ews At Leimakhong., Shillong-Meghalaya

Military Engineer Services-MES has published Tender For Provision Of Amf Panel For Dg Set Of Different Capacity Under Ge 869 Ews At Leimakhong.. Submission Date for this Tender is 05-02-2024. Diesel Generators Tenders in Shillong Meghalaya. Bidders can get complete Tender details and download the document.




Tender Notice

41506007
Corrigendum : Tender For Provision Of Amf Panel For Dg Set Of Different Capacity Under Ge 869 Ews At Leimakhong.
Open Tender
Indian
Meghalaya
Shillong
05-02-2024

Tender Details

Tender For Provision Of Amf Panel For Dg Set Of Different Capacity Under Ge 869 Ews At Leimakhong.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-Jan-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 05-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 71000.0 /-
Tender Value
INR 35.50 Lakhs /-

BOQ Items

Name of Work: PROVISION OF AMF PANEL FOR DG SET OF DIFFERENT CAPACITY UNDER GE 869 EWS AT LEIMAKHONG.
Sl. No. Item Description
1Supply, installation, testing and commissioning of factory made and tested AMF Panel 30 KVA Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
2(a)Under Voltage relay 415V AC for main -1 No (b) Under voltage relay 415 V AC for DG - 1 No (c) AC Timer 230 Volt , 2 No. +2 NC - 1 No. (d) DC Timer 12/24 V -1No. (e) Control MCB SP 6 Amp.230 V – 9 Nos. (f) Control MCB SP 16 Amp.230 V – 2 Nos. (g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos (j) LED Indicating Light for Main & Gen. ON – 2 Nos. (k) LED Indicating Light for battery Charger –1 No. (l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-60 A ) 96 mm X 96 mm with Selector switch - 1 Set. (n) CT Coil 60 / 5 A - 3 Nos. (o) DC Volt Meter 15/30 V - 1 No. (p) DC Amp Meter0-15 A - 1 No. (q) Trickle / Boost switch –2 Nos. (r) Auto / Manual Selector Switch -1 No. (s) Start & Stop Push Button- 2 Nos. (t) Hooter 12/24 V DC - 1 No. (u) Power Contactor 70 A 3 Pole 415V AC for DG - 1 No. (v) Power Contactor 70 A 3 Pole 415V AC for Main - 1 No. (w) Incoming MCCB 63 A 16 KA 3 Pole Thermal Magnetic release for Main & DG Supply - 2 Nos. (x) Control Relay - 1 Set. (y) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set. (z) PCC fundation as per manufacturers instruction.
3Supply, installation, testing and commissioning of factory made and tested AMF Panel 45 KVA Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
4(a)Under Voltage relay 415V AC for main -1 No. (b) Under voltage relay 415 V AC for DG - 1 No. (c) AC Timer 230 Volt , 2 No. +2 NC - 1 No. (d) DC Timer 12/24 V -1No. (e) Control MCB SP 6 Amp.230 V – 9 Nos. (f) Control MCB SP 16 Amp.230 V – 2 Nos. (g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos (j) LED Indicating Light for Main & Gen. ON – 2 Nos. (k) LED Indicating Light for battery Charger –1 No. (l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-100 A ) 96 mm X 96 mm with Selector switch - 1 Set. (n) CT Coil 100 / 5 A - 3 Nos. (o) DC Volt Meter 15/30 V - 1 No. (p) DC Amp Meter0-15 A - 1 No. (q) Trickle / Boost switch –2 Nos. (r) Auto / Manual Selector Switch ---1 No. (s) Start & Stop Push Button- 2 Nos. (t) Hooter 12/24 V DC - 1 No. (u) Power Contactor 95 A 3 Pole 415V AC for DG - 1 No. (v) Power Contactor 95 A 3 Pole 415V AC for Main - 1 No. (w) Incoming MCCB 100 A 16 KA 3 Pole Thermal Magnetic release for Main & DG Supply - 2 Nos (x) Control Relay - 1 Set. (y) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set. (z) PCC fundation as per manufacturers instruction.
5Supply, installation, testing and commissioning of factory made and tested AMF Panel 100 KVA Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
6(a)Under Voltage relay 415V AC for main -1 No. (b) Under voltage relay 415 V AC for DG - 1 No. (c) AC Timer 230 Volt , 2 No. +2 NC - 1 No. (d) DC Timer 12/24 V -1No. (e) Control MCB SP 6 Amp.230 V – 9 Nos. (f) Control MCB SP 16 Amp.230 V – 2 Nos. (g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos (j) LED Indicating Light for Main & Gen. ON – 2 Nos. (k) LED Indicating Light for battery Charger –1 No.
7(l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-200 A ) 96 mm X 96 mm with Selector switch - 1 Set. (n) CT Coil 200 / 5 A - 3 Nos. (o) DC Volt Meter 15/30 V - 1 No. (p) DC Amp Meter0-15 A - 1 No. (q) Trickle / Boost switch –2 Nos. (r) Auto / Manual Selector Switch ---1 No. (s) Start & Stop Push Button- 2 Nos. (t) Hooter 12/24 V DC - 1 No. (u) Power Contactor 185 A 3 Pole 415V AC for DG - 1 No. (v) Power Contactor 185 A 3 Pole 415V AC for Main - 1 No. (w) Incoming MCCB 200 A 25 KA 3 Pole Thermal Magnetic release for Main & DG Supply - 2 Nos (x) Control Relay - 1 Set. (y) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set. (z) PCC fundation as per manufacturers instruction.
8Supply, installation, testing and commissioning of factory made and tested AMF Panel 160 KVA Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
9(a)Under Voltage relay 415V AC for main -1 No. (b) Under voltage relay 415 V AC for DG - 1 No. (c) AC Timer 230 Volt , 2 No. +2 NC - 1 No. (d) DC Timer 12/24 V -1No. (e) Control MCB SP 6 Amp.230 V – 9 Nos. (f) Control MCB SP 16 Amp.230 V – 2 Nos. (g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos (j) LED Indicating Light for Main & Gen. ON – 2 Nos. (k) LED Indicating Light for battery Charger –1 No. (l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-400 A ) 96 mm X 96 mm with Selector switch - 1 Set. (n) CT Coil 400 / 5 A - 3 Nos. (o) DC Volt Meter 15/30 V - 1 No. (p) DC Amp Meter0-15 A - 1 No. (q) Trickle / Boost switch –2 Nos. (r) Auto / Manual Selector Switch ---1 No. (s) Start & Stop Push Button- 2 Nos. (t) Hooter 12/24 V DC - 1 No. (u) Power Contactor 300 A 3 Pole 415V AC for DG - 1 No. (v) Power Contactor 300 A 3 Pole 415V AC for Main - 1 No. (w) Incoming MCCB 400 A 35 KA 3 Pole Thermal Magnetic release for Main & DG Supply - 2 Nos (x) Control Relay - 1 Set. (y) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set. (z) PCC fundation as per manufacturers instruction.
10Supply, installation, testing and commissioning factory made and tested AMF Panel 600 KVA Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:-
11(a)Under Voltage relay 415V AC for main -1 No. (b) Under voltage relay 415 V AC for DG - 1 No. (c) AC Timer 230 Volt , 2 No. +2 NC - 1 No. (d) DC Timer 12/24 V -1No. (e) Control MCB SP 6 Amp.230 V – 9 Nos. (f) Control MCB SP 16 Amp.230 V – 2 Nos. (g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos (j) LED Indicating Light for Main & Gen. ON – 2 Nos. (k) LED Indicating Light for battery Charger –1 No. (l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-1000 A ) 96 mm X 96 mm with Selector switch - 1 Set. (n) CT Coil 1000 / 5 A - 3 Nos. (o) DC Volt Meter 15/30 V - 1 No. (p) DC Amp Meter0-15 A - 1 No. (q) Trickle / Boost switch –2 Nos. (r) Auto / Manual Selector Switch ---1 No. (s) Start & Stop Push Button- 2 Nos. (t) Hooter 12/24 V DC - 1 No. (u) Incoming ACB 1000 A 50 KA 4 Pole Electrical Draw Out (EDO) Thermal Magnetic release for Main & DG Supply - 2 Nos (v) Control Relay - 1 Set. (w) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set. (x) PCC fundation as per manufacturers instruction.
12Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil etc complete all as specified and as directed.
13Returning, filling in, of soil including spreading leveling, watering and well ramming in layers not exceeding 25 cmcomplete all as specified and as directed .
14Removing excavated material to a distance n.exc 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point completeall as specified and as directed
15Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cableincludingspreading and punning down to requirred thickness complete all as specified and as directed. (Note: Thickness of sand cushioning after punning down shall be measured for payment purpose)
16Supply and laying PCC cable cover class LVtype 1 flat size 250 x 150 x 40 mm laidin trenches for protection of under ground cable all as specified and as directed.
17Supply and laying and testing under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 35 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc complete all as specified and as directed. (Note : Earth work, PCC cable cover protection and sand cushioning will be measured and paid separately under respective item.)
18Supply and laying and testing under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 50 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc complete all as specified and as directed. (Note : Earth work, PCC cable cover protection and sand cushioning will be measured and paid separately under respective item.)
19Supply and laying and testing under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 95 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc including taking down unservicable cable complete all as specified and as directed. (Note : Earth work, PCC cable cover protection and sand cushioningwill be measured and paid separately under respective item.)
20Supply and laying and testing under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 150 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc complete all as specified and as directed. (Note : Earth work, PCC cable cover protection and sand cushioning will be measured and paid separately under respective item.)
21Supply and laying and testing under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 300 Sqmm 3.5 core laid in trenches as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc complete all as specified and as directed. (Note : Earth work, PCC cable cover protection and sand cushioning will be measured and paid separately under respective item.)
22Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised earthing lead of GI strip of 32 x 6mmby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 5 of MES Schedule Part-I(2009) complete including testing on completion, complete all as specified and as directed. (Note: Earth lead upto a length of 7.50 m from earthplate shall be deemed to be included in quoted rate.)