Raja Ramana Centre For Advance Technology has published Tender For Supply, Installation, Testing And Commissioning Of Air Handling Units Along With Accessories Under Buy-Back Arrangements At Rrcat, Indore.. Submission Date for this Tender is 01-02-2024. Air Handling Unit Tenders in indore Madhya Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 05-Jan-2024 | Updation in BOQ Excel Sheet | BOQ | 23-01-2024 |
2 | 17-Jan-2024 | Pre bid Clarifications | Other | 23-01-2024 |
3 | 23-Jan-2024 | Extension of Tender Dates | Date | 30-01-2024 |
4 | 30-Jan-2024 | Extension of Tender Dates-2 | Date | 01-02-2024 |
5 | 30-Jan-2024 | Pre Bid Clarifications | Other | 01-02-2024 |
Sl. No. | Item Description |
1 | Supply, installation, testing and commissioning (SITC) Air Handling Units (AHU)s with direct driven fan, electric motor, cooling coil, humidifier, Pre filters, volume control dampers, heaters, etc and other associated accessories as per Sr. no. 1 of technical specification. |
2 | SITC of 35000 CFM AHU unit (minimum 85 TR) against dismantling and buyback of 2 old AHU units along with electrical panel having 15000CFM capacity. |
3 | SITC of 15500 CFM AHU unit (minimum 36 TR) against dismantling and buyback of 1 old AHU unit along with electrical panel having 15000 CFM capacity. |
4 | SITC of 9,200 CFM AHU unit (minimum 22 TR) against dismantling and buyback of 1 old AHU unit along with electrical panel having 8000CFM capacity. |
5 | SITC 13,000 CFM AHU unit (minimum 32 TR) against dismantling and buyback of 1 old AHU unit along with electrical panel having 11000CFM capacity. |
6 | Supply and installation of motorised fire cum smoke control damper complete with fire & smoke sensors, actuator, control panel and other accessories as per item no. 2 oftechnical specification. |
7 | Supply, fabrication, installation, testing and commissioning of GI ducts fabricated as per Item No. 3 of technical specification. The ducting shall be complete with bends, elbows, turning vanes (if required), reducers/transition pieces, MS flanged joints, 6 mm thick neoprene gasket, SS hardware, silicon sealant etc. as per site requirment to interconnect the machine (AHU etc) with existing duct system of Lab. |
8 | Supply and installation of 19 mm (min.) thick closed cell class "0" zero nitrile rubber insulation with 0.5 mm thick aluminium claddingcomplete with other accessories such as adhesive, jointing tap, SS/GI hardware etc. as per item no. 04 of technical specification. |
9 | Supply and installation of Acoustic insulation suitable as per Item no. 5 of technical specification |
10 | Supply, installation, testing and commissioning ofMS pipe of following sizes & thickness / class for chilled water system complete with all required flanges, fittings, gaskets, fasteners, Nitrile rubberinsulation covered with Aluminium Cladding etc. as per Item no. 6 of technical specification. |
11 | NB 50 mm |
12 | NB 65 mm |
13 | NB 80 mm |
14 | NB 100 mm |
15 | Supply, installation, testing and commissioning of flanged end, non rising spindle, PN-16, CI gate valves of following sizes for chilled water system complete with all required counter flanges, fittings, gaskets, fasteners, nitrile rubber insulation covered with aluminium cladding etc. as per Item no. 7 of technical specification. |
16 | CI Gate Valve size 50mm |
17 | CI Gate Valve size 65mm |
18 | CI Gate Valve size 80mm |
19 | CI Gate Valve size 100mm |
20 | Supply, installation, testing and commissioning of flanged end, PN-16, CI balancing valves of following sizes for chilled water system complete with all required counter flanges, fittings, gaskets, fasteners, nitrile rubber insulation covered with aluminium cladding etc. as per Item no. 08 of technical specification. |
21 | CI Globe/Balancing valves size 50mm |
22 | CI Globe/Balancing valves size 65mm |
23 | CI Globe/Balancing valves size 80mm |
24 | CI Globe/Balancing valves size 100mm |
25 | Supply, installation, testing and commissioning of flanged end, PN-16, CI Y-strainers of following sizes for chilled water system complete with all required counter flanges, fittings, gaskets, fasteners, nitrile rubberinsulation covered with aluminium cladding etc. as per Item no. 09 of technical specification. |
26 | CI Y-strainers size 50mm |
27 | CI Y-strainers size 65mm |
28 | CI Y-strainers size 80mm |
29 | CI Y-strainers size 100mm |
30 | Supply, installation, testing and commissioning of PN-16,2-way modulating with energy saving features. The valves shall be of following sizes for chilled water system complete with BMS compatibility and all required counter flanges and/ fittings, gaskets, fasteners, nitrile rubberinsulation covered with aluminium cladding etc. as per Item no. 10 of technical specification. |
31 | 2-way modulating energy valves size 50 mm |
32 | 2-way modulating energy valves size 65 mm |
33 | 2-way modulatingenergy valves size 100 mm |
34 | Supply, installation, testing and commissioning of flangless, PN 16 Butterfly valves of following sizes for chilled water system complete with all required nipples, fittings, nitrile rubberinsulation covered with aluminium cladding etc. as per Item no. 11 of technical specification. |
35 | Butterfly valves size 50mm |
36 | Butterfly valves size 65mm |
37 | Butterfly valves size 80mm |
38 | Butterfly valves size 100mm |
39 | Supply, installation, testing and commissioning of threaded end, PN 16/class-150 CI auto air vent having SS ball of 25 mm dia suitable for chilled water system complete with all required nipples, fittings, nitrile rubberinsulation covered with aluminium cladding etc. as per Item no. 12 of technical specification |
40 | Supply, fabrication, installation and painting of MS structure to support pipes, valves, flanges etc. required at site as per Item no. 13 of technical specification. |
41 | Fabrication, Supply and installation of 3mm thick AISI 304 Stainless Steel tray to support total base of AHU as per technical specification Item No. 14 |
42 | Supply, installation, testing and commissioning offollowing BMS compatible instruments for measurement and control of various parameters as per Item no. 15 of technical specification. |
43 | Humidistat with sensors for measuring & control of relative humidity and suitable for on-off operation of heaters of AHUs. |
44 | Airstat/air flow switch suitable for on-off operation of heaters of AHUs. |
45 | 0 to 50 deg C range stem type thermometers having 100 mm dia dial with suitable stainless steel thermo wells for measurement of water temperature. |
46 | 0 to 10 kg/sq. cm. range bourden tube type pressure gauge having 100 mm dia dial, U syphon and cockin stainless steel construction for measurement of water pressure. |
47 | Differential Pressure Switch / Sensor Transmitter |
48 | Temperature, RH and dew point meter at the outlet of AHU |
49 | Air flow sensor with transmiter for AHU |
50 | Controller: Supply, installation, testing and commissioning of standalone BACnet/IP based modular type, BMS compatible DDC controller / automation station having integral web browser, I/O module, flash memory for programmed logic storage communication ports (RS 485, Ethernet RJ 45, and USB/additional ethernet), etc. For Air Handling Unit (AHU) control, monitoring, status indication, data logging etc as per tender technical specification. |
51 | Temerature sensor and transmitter: Supply, installation, testing and commissioning of high accuracy (±0.03 deg.C @ 0 deg.C or better for the span of 0-35 deg. C) BMS compatible temperature sensor (1000 ohm platinum RTD type) and transmitter unit with associated cabling as per tender technical specifictions. |
52 | Relative humidity sensor and transmitter: Supply, installation, testing and commissioning of high accuracy (±1% or better for the span of 30% to 70%) Relative Humidity (RH) sensor and transmitter unit with associated cabling as per tender technical specifications. |
53 | Immersion type temperature sensors set: Supply, installation, testing and commissioning of BMS compatible immersion temperature sensor one (01) in supply and one (01) in return chilled water line ( 50/65/80 /100mm dia. MS) in AHUs as per technical specifications. |
54 | Smoke detectors set: Supply, installation, testing and commissioning of BMS compatible photoelectric type smoke detectors set suitable for HVAC duct mounting. A set shall include two numbers of smoke detectors, associated cabling, mounting arrangements, etc. as per the technical specifications |
55 | Development of BMS and integration with existing BMS: Development of building monitoring system (BMS) for all the AHUs s and integrating the BMS with the existing Siemens" make Desigo CC BMS installed at server grade computer (HMI station) as per technical specifications. |
56 | Electrical Panels : Design Fabrication, supply, installation, testing & commissioning of ,min IP-42 MCC switchboards with the following components suitable for use at 415 V, 3 phase 4 wire 50 Hz system, and suitable for a fault level of 50 KA symmetrical at 415 V complete as per Drawings, detailed specifications, instructions & approval of EIC and having following configurations: Note:- 1) VFD shall be BMS compatible & shall comply with the latest edition ofIEC 61800-3 & IEC 61000 standards 2) Electrical Panel shall have required no. of VFD feeders in line with the AHU design being offered. |
57 | Electrical Panel -1Incomer: 400A FP MCCB (Ics=50 kA) with Microprocessor trip release for O/L & S/C & E/F protection (LSIG). Main Bus bar - 1 Set 400 A TPN tinned copper bus bar having maximum current density of 1.6A/sq.mm to withstand symmetrical fault level of 50 KA at 415 V. Outgoing: 1) MCB feeders for heaters/preheaters/humidifier: 4P MCB D curve with power contactor suitable for as per the current rating of re-heater/preheater/humidifier,alongwithinterlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications. - 04 set. 2) VFD feeders with DOL bypass : TP MCCB (Ics=50 kA, microprocessor trip release for O/L&S/C&E/F protection (LSIG)fedVFD drives suitable to run 35,000CFM AHUAlong with Interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications required for 350000 CFM AHU. 3) Spare feeders:- • 63 A C-Curve TPN MCB with ON/OFF LED indicating lamp with 6A control SP MCB-2 sets. • 32 A C-Curve TPN with ON/OFF LED indicating lamp with 6A control SP MCB- 1sets. |
58 | Electrical Panel -2 Incomer:250A FP MCCB (Ics=50 kA) with Microprocessor trip release for O/L & S/C & E/F protection (LSIG) Main Bus bar - 1 Set 250 A TPN tinned copper bus bar having maximum current density of 1.6A/sq.mm to withstand symmetrical fault level of 50 KA at 415 V. Outgoing: 1) MCB feeders for heaters/preheaters/humidifier: 4P MCB D curve with power contactor suitable for as per the current rating of re-heater/preheater/humidifier, alongwithinterlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications. - 04 set. 2) VFD feeder with DOL bypass : TP MCCB (Ics=50 kA, microprocessor trip release for O/L&S/C&E/F protection (LSIG) fedVFD drive suitable to run 15,500CFM AHU Along with Interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications 3) Spare feeders:- • 63 A C-Curve TPN MCB with ON/OFF LED indicating lamp with 6A control SP MCB-1 sets. • 32 A C-Curve TPN with ON/OFF LED indicating lamp with 6A control SP MCB- 1 sets. |
59 | Electrical Panel -3Incomer: 125A FP MCCB (Ics=50 kA) with Microprocessor trip release for O/L & S/C & E/F protection (LSIG) Main Bus bar - 1 Set 125 A TPN tinned copper bus bar having maximum current density of 1.6A/sq.mm to withstand symmetrical fault level of 50 KA at 415 V. Outgoing: 1) MCB feeders for heaters/preheaters/humidifier: 4P MCB D curve with power contactor suitable for as per the current rating of re-heater/preheater/humidifier, interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications. - 04 set. 2) VFD feeder with DOL bypass : TP MCCB (Ics=50 kA, microprocessor trip release for O/L&S/C&E/F protection (LSIG) fedVFD drive suitable to run 13,000CFM AHU Along with Interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications- 3) Spare feeders:- • 32 A C-Curve TPN with ON/OFF LED indicating lamp with 6A control SP MCB- 1 sets. |
60 | Electrical Panel -4 Incomer: 125A FP MCCB (Ics=50 kA) with Microprocessor trip release for O/L & S/C & E/F protection (LSIG) Main Bus bar - 1 Set 125 A TPN tinned copper bus bar having maximum current density of 1.6A/sq.mm to withstand symmetrical fault level of 50 KA at 415 V. Outgoing: 1) MCB feeders for heaters/preheaters/humidifier: 4P MCB D curve with power contactor suitable for as per the current rating of re-heater/preheater/humidifier, interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications. - 04 set. 2) VFD feeder with DOL bypass : TP MCCB (Ics=50 kA, microprocessor trip release for O/L&S/C&E/F protection (LSIG)fedVFD drive suitable to run 9,200CFM AHUAlong with Interlocking with signal /communication wire as per recommendation of OEM/EIC & complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required and as per tender specifications. 3) Spare feeders:- • 32 A C-Curve TPN MCB with ON/OFF LED indicating lamp with 6A control SP MCB-2 sets. |
61 | Supply, installation, testing & commissioning of1.1 KV copper multi stranded conductor with XLPE insulation, extruded PVC inner sheathed, G.I flat steel strip armoured, extruded PVC outer sheathed FRLS cable conforming to IS 7098 Part-I with latest amendments, fixed on wall/column/slab/ Cable tray/trench/ shaft/pit/ on 5mm thick G.I. flat/angle support fixed with coach screws/grouted in wall/anchor fasteners, 2mm. thick G.I. fabricated saddle, all fixing accessories providing brass cable number tag & as pertechnical specifications & as per instructions of the E-I-C. & of the following sizes. |
62 | 4 Cx10 sq. mm Armoured power Cable |
63 | 4Cx16 sq. mm Armoured power Cable |
64 | Supply, Installation, Testing & Commissioning of Heavy duty Double compression end termination for following LT, XLPE insulated power cable using Brass gland, tinned Copper lugs suitable for crimping, end boxcomplete as required and as per tender specifications and as per of technical specification. |
65 | 4 Cx10 sq. mm Armoured power Cable |
66 | 4Cx16 sq. mm Armoured power Cable |
67 | Only Installation, Testing and Commisioning of 1100 V voltage grade Aluminium XLPE insulated, Armoured, FRLS PVC sheathed power cable on wall/trench by supply and fixing of clamps and other required hardware. |
68 | 3.5 C X 400/240/150/120 sq. mm. cable |
69 | 3.5 C X 70/50 sq. mm. cable |
70 | End termination of 1100 volt voltage grade Aluminium Armoured XLPE/PVC power cable by using double compression Nickel Plated Brass Gland, Aluminium Small/Medium/Long barrel Lug and earth clamps duly connected to the equipment ground through GI/Copper Conductor. This includes Supply of end jointing materials with all accessories. |
71 | 3.5 C X 240/150 sq. mm. |
72 | 3.5 C X 120/95/70/50 sq. mm. |
73 | Dismantling and stacking of existing L.T having following size including removal of switchgears, Cu/Al Bus bar, end termination of Power cables etc. and safe storing within the 2.5 km radius with suitable vehicle. |
74 | Size of panel > (1.1 X 1.1 X 0.3) to <( 2.0 X2.0 X 0.4) mtr. |
75 | Removing of following 1100 V voltage grade Aluminium PVC/XLPE insulated, Armoured, PVC sheathed electrical power cables already installed in L.T panels including disconnection of end termination from old panel, from wall & trench & safe storing within the 2.5 km radius with suitable vehicle. |
76 | 3.5 C X 400/240/150/120 sq. mm. cable |
77 | 3.5 C X 70/50/35/25 or 4 C X 25/16/10/6 sq. mm. cable |
78 | Supply & Installation of stuctural steel work including supply, cutting, fabricating, welding, necessory scaffolding erecting & fixing in position, including painting with a primer coat of approved steel primer & black steel paint. |
79 | Fabrication, Supply & Installation of wire mesh cable tray :- Electro zinc plated carbon steel wire mesh cable tray300 mm width and size height of 105 mm,including their standard mounting supports/brackets, clamps, connectors, hardware etc. all as per instruction of EIC and detail technical specifications. |
80 | Supply and installation of G. I. strip/wire of required size under ground at a depth of 600 mm from FGL including excavation, black bitumin painting, backfilling and consolidation of soil. Installtion along cable trays / walls using G. I. clamps/Saddle & spacer at interval of 500 mm / as per site requirements including required hardware. |
81 | Supply and laying GI earthing strip / wire with accessories in cable tray / wall. |