Tender For C/O Jawan Barrack Type-B At Bop Hemanagsr (Now Ganganagar) Of 73 Bn Bsf (Now 170 Bn Bsf) Under Shq Bsf Shillong (Sh: Providing And Fixing Electrical Installations And Service Connections), ganganagar-Meghalaya

Border Security Force-BSF has published Tender For C/O Jawan Barrack Type-B At Bop Hemanagsr (Now Ganganagar) Of 73 Bn Bsf (Now 170 Bn Bsf) Under Shq Bsf Shillong (Sh: Providing And Fixing Electrical Installations And Service Connections). Submission Date for this Tender is 08-01-2024. Electrical Maintenance Tenders in ganganagar Meghalaya. Bidders can get complete Tender details and download the document.




Tender Notice

41405549
Tender For C/O Jawan Barrack Type-B At Bop Hemanagsr (Now Ganganagar) Of 73 Bn Bsf (Now 170 Bn Bsf) Under Shq Bsf Shillong (Sh: Providing And Fixing Electrical Installations And Service Connections)
Open Tender
Indian
Meghalaya
ganganagar
08-01-2024

Tender Details

C / O Jawan Barrack Type-B At Bop Hemanagsr ( Now Ganganagar ) Of 73 Bn Bsf ( Now 170 Bn Bsf ) Under Shq Bsf Shillong ( Sh: Providing And Fixing Electrical Installations And Service Connections )

Key Value

Document Fees
Refer document
EMD
INR 8499.0 /-
Tender Value
INR 4.24 Lakhs /-

BOQ Items

Name of Works: C/O Jawan Barrack Type-B at BOP Hemanagsr (Now Ganganagar) of 73 Bn BSF (Now 170 Bn BSF) under SHQ BSF Shillong (SH: Providing and fixing electrical installations and service connections)
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group-B)
2Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire)
3Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (2 X 4 sq. mm + 1 X 4 sq. mm earth wire)
4Supplying and fixing of following sizes of medium class PVC Conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (50 mm)
5Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
6Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
7Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
8Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
9Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (4 way (4 + 12), Double door)
10Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (63 Amps)
11Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (12 way , Double door)
12Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (2 x 6 sq. mm)
13Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Single pole)
14Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (40 Amps)
15Supplying, Installation, testing & Commissioning of4"long 18/20 watt LED batten (make Havells-Lumeline- LUMILINEBS18W LED865SPCWH)/ similar model of Crompton/ Philips / Havells/ SYSKA /Wipro) directly on ceilling / wall including connection with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, earthing etc. as required.
16Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor(Make: Havells-Efficiencia Neo (BLDC 26 W) or equivalent model of Usha/CG/etc) class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
17Supplying, Installation, testing & commissioning of LED square / round surface mounted 20 Watt LED downlighterwith PDC aluminum housing and PMMA diffuser Luminaire complete with electronic driver directly on ceiling including connection with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable, earthing etc. as required(Make :Crompton-ROYAL RIMLESS - R Model: LCRP-20-WW) or with similar model of Orient/Philips / Crompton / Osram/ Wipro / Havells).
18Supplying, Installation, testing & Commissioning of45 Watt rating LED street light luminaire, out door type with pressure die cast aluminium housing with heat resistant glass, IP66 protection, suitable for single phase, 50 Hz AC (MAKE Havells-ENDURASUNDOWNSL45WLED765PASYBOPC), including connection with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, earthing, Supplying and fixing of 32 mm dia X 0.50 metres long G.I. pipe (medium class) bracket for mounting of LED street light fitting directly on wall, bending the pipe to the required shape, 2 nos suitable size flat iron clamps with nuts, bolts and washer etc. as required.
19Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
20Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
21Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
22Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
23Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
24Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
25Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
26Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
27Supplying and Laying of aluminium conductor, XLPE Insulated, PVC Innersheathed, armoured power cable of 1.1 KV grade of 3.5×35 sq. mmsize direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.(Make Havells/Polycab/Universal/CCI/ Plaza/RRKable)